CNT-SVX04A-EN
12
Physical specifications
Board dimensions
Height:
5.25 in. (133 mm)
Width:
5.50 in. (140 mm)
Depth:
2.25 in. (57 mm)
Operating environment
32
°
to 140
°
F (0
°
to 60
°
C)
5% to 95% relative humidity, non-condensing
Storage environment
-40
°
to 185
°
F (-40
°
to 85
°
C)
5% to 95% relative humidity, non-condensing
Agency listings
UL and CUL 916 Energy Management System
Agency compliance
IEC 1000-4-2 (ESD), IEC 1000-4-4 (EFT), IEC 1000-4-5 (Surge)
Power requirements
18 to 32 VAC (24 VAC nominal)
50 or 60 Hz
570 mA AC
Binary inputs
Table 3
Binary inputs (typically 24 mA AC)
Note:
Each binary input associates an input signal of 0 VAC with open contacts and 24 VAC with closed
contacts.
Description
Terminals
Terminal function
Binary input 1
(BI 1)
J2-1
24 VAC
J2-2
Input
Binary input 2
(BI 2)
J2-3
24 VAC
J2-4
Input
Binary input 3
(BI 3)
J2-5
24 VAC
J2-6
Input
Binary input 4
(BI 4)
J2-7
24 VAC
J2-8
Input