Wiring Communication Link

The Tracer VV551 VAV controller communicates with the building automation system and with other controllers over a LonTalk® communication link. Comm5 is the Trane implementation of LonTalk® protocol. For instructions on
LonTalk® communication wiring, refer to the

Tracer Summit™ V17 Daily Operations Guide

, BMTX-SVU01 or to the installation manual for the applicable building automation system.

Input/Output Terminal Wiring

The input/output wiring terminals for the VV551 controller are a combination of fixed function and application-specific connections. All input/output terminal wiring for the VV551 controller must meet the following requirements:

• All wiring must be in accordance with the National Electrical Code™ (NEC) and local codes
• Use only 18–22 AWG, stranded, tinned-copper, unshielded, twisted-pair wire
• Binary input and output wiring should be a maximum length of 300 ft (100 m)
• Analog input and output wiring should be a maximum length of 300 ft (100 m)
• Do not run input/output wires in the same wire bundle with any A/C power wires
• A pressure sensor can be connected with up to 300 feet of tubing and up to 60 feet of wire

The following tables describe input/output terminals, ratings, and the heat/fan output configurations by application.

Table 1.

Inputs and output terminals

Analog Inputs

Input Description

Terminal

Label

Rating

Space temperature

• TB3_1 

• TB3_2

ZONE

10,000 

 at 77°F (25°C)

Space setpoint

• TB3_2 

• TB3_3

SET

1,000 



potentiometer

Primary/discharge air temperature • TB3_5 

• TB3_6

AUX

10,000 

 at 77°F (25°C)

Primary flow

• J2-1 GND 

• J2-2 signal 

• J2-3 VDC

FLOW

NA

Binary Input

 input Description

Terminal

Label

Rating

Occupancy/generic

• TB4_1 

• TB4_2

BI 1

Powered contact

Apply dry contact only

0 Vac = Open

24 Vac = Closed

Binary Outputs

Binary input

Terminal

Label

Rating

Heat 1

J9

HEAT 1

Triac, 24 Vac,

maximum output 12 VA

Heat 2

J10

HEAT 2

Triac, 24 Vac,

maximum output 12 VA

Heat 3/fan

J11

HEAT 3

Triac, 24 Vac,

maximum output 12 VA

Air valve close

J1-3

ACTUATOR

Triac, 24 Vac,

maximum output 12 VA

Air valve open

J1-4

ACTUATOR

Triac, 24 Vac,

maximum output 12 VA

Table 2.

Heat/fan output configurations by application

Heat 1

Heat 2

Heat 3

No Fan

Series or Parallel

No Reheat

None

None

None

Fan

Hot 

Water

2-Position

1 Stage Local Reheat

Local Hot Water ON/OFF

None

None

Fan

1 Stage Remote Heat

Remote Hot Water ON/OFF

None

None

Fan

2 Stages

Local Hot Water ON/OFF

Remote Hot Water ON/OFF

None

Fan

Modulating

Local Reheat

Local Hot Water Closed

Local Hot Water Open

None

Fan

Remote Reheat

Remote Hot Water Closed

Remote Hot Water Open

None

Fan

Both

Local Reheat

Remote Hot Water Closed

Remote Hot Water Open

Local Hot Water ON/OFF

Fan

(a)

(a) When the controller is configured with either a series or parallel fan, Heat 3 is used to control the fan and not the third stage of heat.

Remote Reheat

Local Hot Water Closed

Local Hot Water Open

Local Hot Water ON/OFF

Fan

(a)

Electric 

Heat

Local 

Reheat

PWM

1 Stage

Local PWM Electric Heat Stage 1 None

None

Fan

2 Stages

Local PWM Electric Heat Stage 1 Local PWM Electric Heat Stage 2 None

Fan

3 Stages

Local PWM Electric Heat Stage 1 Local PWM Electric Heat Stage 2 Local PWM Electric Heat Stage 3 Fan

(a)

Staged

1 Stage

Local Staged Electric Heat 1

None

None

Fan

2 Stages

Local Staged Electric Heat 1

Local Staged Electric Heat 2

None

Fan

3 Stages

Local Staged Electric Heat 1

Local Staged Electric Heat 2

Local Staged Electric Heat 3

Fan

(a)

Remote Heat

Remote Electric Heat Stage 1

None

None

Fan

Both

PWM

1 Stage

Local PWM Electric Heat Stage 1 Remote Electric Heat Stage 2

None

Fan

2 Stages

Local PWM Electric Heat Stage 1 Local PWM Electric Heat Stage 2 Remote Electric Heat Stage 3

Fan

(a)

Staged

1 Stage

Local Staged Electric Heat 1

Remote Electric Heat Stage 2

None

Fan

2 Stages

Local Staged Electric Heat 1

Local Staged Electric Heat 2

Remote Electric Heat Stage 3

Fan

(a)

Agency Listings and Compliance

The European Union (EU) Declaration of Conformity is available from
your local Trane

®

office.

BAS-SVN114G-EN 01 Jun 2020