Troubleshooting
This section provides information about the following:
•
•
“Troubleshooting Procedures,” p. 50
Diagnostics
The following table provides information about controller diagnostics.
WARNING
Live Electrical Components!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live components could
result in death or serious injury.
Table 13. Controller Diagnostics
Diagnostic
Air Valve
Fan
Reheat
Discharge air temperature failure (space
temperature control)
Normal
Normal
Normal
Discharge air temperature failure (ventilation
flow control without reheat)
Normal
Do not care
Do not care
Discharge air temperature failure (ventilation
flow control with reheat)
Closed
Do not care
Off
Discharge air temperature failure (flow tracking
control)
Normal
Do not care
Do not care
Low airflow (space temperature control)
Normal
Normal
Local electric heat is Off; local
hydronic and all remote heat is
normal
Low airflow (ventilation flow control)
Normal
Do not care
Local electric heat is Off; local
hydronic is normal; remote is Don't
Care
Supply air temperature failure (space
temperature control)
Normal
Normal
Local electric heat is Off
(a)
; local
hydronic and all remote heat is
normal
Supply air temperature failure (ventilation flow
control)
Normal
Do not care
Normal
Supply air temperature failure (flow tracking
control)
Normal
Do not care
Do not care
Space temperature fail (space temperature
control)
(b)
Occupied: cool minimum flow
setpoint Unoccupied: closed
Series fan enabled;
parallel fan Off
Off
Space temperature fail (ventilation flow
control)
Normal
Do not care
Normal
Space temperature fail (flow tracking control)
Normal
Do not care
Do not care
Local setpoint failure
Normal
Normal
Normal
Flow sensor failure or flow sensor calibration
failure (space temperature control)
Normal pressure dependent control Normal
Normal
Flow sensor failure or flow sensor calibration
failure (ventilation flow control)
Normal pressure dependent control Do not care
Normal
Flow sensor failure or flow sensor calibration
failure (flow tracking control)
If the configured airflow tracking
offset is positive, configure
maximum airflow If the configured
airflow tracking offset is negative,
configure minimum airflow
Do not care
Do not care