CNT-SVX09E-EN
5
Overview and Specifications
This guide provides installation and configuration information for the Tracer™ MP503 input/output
(I/O) module, as well as a description of its operations. The overview includes a product description,
specifications, and descriptions of additional components needed in some MP503 applications.
Product Description
The MP503 I/O module is a field-installed device used to monitor inputs and control binary outputs.
The module has four universal inputs that can be configured as binary, thermistor, 0–20 mA, or 0–
10 Vdc, as well as four binary outputs.
Storage Environment
If a MP503 I/O module is to be stored for a substantial amount of time, store it in an indoor
environment that meets the following requirements:
•
Temperature: –40° to 185°F (–40° to 85°C)
•
Relative humidity: 5–95%, non-condensing
Operating Environment
Operate a MP503 I/O module in an environment that meets the following requirements:
•
Temperature: –40°F to 158°F (–40°C to 70°C)
•
Relative humidity: 5–95%, non-condensing
Dimensions
Plastic Cover Model
•
Height: 5.375 in. (137 mm)
•
Width: 6.875 in. (175 mm)
•
Depth: 2 in. (51 mm)
Metal Cover Model
•
Height: 9.0 in (25 mm)
•
Width: 10.37in. (263 mm)
•
Depth: 2.25 in. (58 mm)
Clearances
For wiring, ventilation, and maintenance, provide the following minimum clearances for the
MP503:
Plastic Cover Model
•
Front: 4.0 in. (102 mm)
•
Each side: 1.0 in. (25 mm)
•
Top and bottom: 4.0 in. (102 mm)
Metal Cover Model
•
Front: 24.0 in. (610 mm)
•
Each side: 2.0 in. (51 mm)
•
Top and bottom: 1.0 in. (25 mm)