4.  Local Unit shutdown, Local fan and operation mode change 

The THS04 is able to switched OFF

ON unit by pressing during 3seconds the ON/Off button (button 3 

Figure4)  

Fan mode can be switched AUTO 

 ON by pressing during 3seconds the Fan button (button 2 Figure4).  

Unit mode can be switched AUTO 

COOL 

HEAT by pressing during 3seconds the Mode button (button 

1 Figure4) 

Important:

 Fan mode or Unit mode switch can only be performed after switching the unit in OFF (pressing 

during 3seconds the ON/Off button) 

 

Figure 6 

5.  Occupancy mode change  

When Time/Day scheduler is activated under PGD1, it is possible to temporary override scheduler 

occupancy mode with THS04. 

THS04 Occupancy override will switch unit to occupied state if scheduler active time band has set it in 

unoccupied and vice-versa. 

When Time/Day scheduler is not activated, the THS04 Occupancy override will switch temporary unit from 

unoccupied to occupied. 

To override minimum fresh air occupancy mode, a simple push on button 4 (Figure. 4) will move the state 

of the unit from unoccupied to occupied. THS04 displays active occupied / unoccupied minimum fresh air 
state with the logo of figure 7 

 

Figure 7 

Occupied mode override will remain active until override timer expires. It is possible to edit the override 

timer under PGD1: Setting-THS04 : Occupancy Override timer 

 60 minutes (default value). 

If Occupancy Override timer value is set at zero. It will disable the timer function and let unit fresh air 

occupancy state unchanged if no other actions are performed on button 4. 

6.  Active temperature setpoint override command 

It is possible with THS04 to override the active temperature setpoint by an offset of +/- 2°C. Turning the 

button 5 (Figure.4) will offset the active setpoint (Cooling or Heating depending of current mode of unit).  

Push

3s

Unit

ON

OFF

Push

Fan

AUTO

ON

Push

Unit mode

AUTO

COOL

HEAT

Unit OFF

Unit OFF

Push

Unit fresh air occupancy

Содержание THS04

Страница 1: ...RT SVU010B GB User Guide THS04 wall thermostat ...

Страница 2: ...d to that communication J9 FBus1 This is based on three wires plus minus reference circle Vout is not used cf Figure 1 Figure 1 On THS04 those three signals are Rx Tx Rx Tx GND cf Figure 2 Figure 2 b Power supply In addition to communication signals THS04 requires power supply X201 to be connected to GND of THS04 X200 to be connected to 24V of THS04 ...

Страница 3: ... mode On Auto 4 Fan speed min intermediate nominal 6 Key on logged as user 7 Set on modification of temperature setpoint will be taken in account when Set switches off 9 Occupancy of current Timeband scheduler 10 Current day 11 Unit status Alarm Compressors On Off Indoor Fans On Off Auxiliary Heating On Off 12 hh mm time if unit is in local control BAS if unit is controlled by BAS Off if unit is s...

Страница 4: ...sh to stop start the unit 4 Clock button Simple push to switch occupancy fresh air management Occupied Unoccupied when unit is ON In case of scheduler enabled the simple push switch the unit fresh air occupancy mode temporary during override timer 5 Push Rotate button menu navigation and temperature setpoint change In case of scheduler enabled the setpoint change switch the unit Heating Cooling zo...

Страница 5: ...re is no need of password to change unit and fan mode or edit setpoint and occupancy state However it is possible to enable the password by changing setting in PGD1 Setting THS04 Access Level Enable When activated the password has to be entered on the THS04 under Menu 2 See Figure 5 Password Disable by default 3 Set Setpoint1 Wait 3s Wait 3s Tc Cooling setpoint change Edit Wait 3s Th Heating setpo...

Страница 6: ... override will switch temporary unit from unoccupied to occupied To override minimum fresh air occupancy mode a simple push on button 4 Figure 4 will move the state of the unit from unoccupied to occupied THS04 displays active occupied unoccupied minimum fresh air state with the logo of figure 7 Figure 7 Occupied mode override will remain active until override timer expires It is possible to edit ...

Страница 7: ... It is possible to adjust the controller time and date under PGD1 Setting Clock and password Time and Date settings Version History Oct 2017 Simplify default level and remove password to change mode occupancy and setpoint Implementation started with CH536 release 1 52 Trane optimizes the performance of homes and buildings around the world A business of Ingersoll Rand the leader in creating and sus...

Отзывы: