18-GF74D1-1R-EN
19
TEM6A0B24H21SC, TEM6A0B30H21SC Airflow Performance with Auxiliary Heat
Airflow Settings
Dip Switch Settings
Nominal Airflow
See following tables for
heater application:
- Pressure Drop for
Electrical Heaters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
Switch 7
Switch 8
Low
ON
ON
601
Med-Lo
OFF
ON
661
Med-Hi
ON
OFF
781
High
OFF
OFF
973
TEM6A0C36H31SC, TEM6A0C42H41SC Airflow Performance with Auxiliary Heat
Airflow Settings
Dip Switch Settings
Nominal Airflow
See following tables for
heater application:
- Pressure Drop for
Electrical Heaters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
Switch 7
Switch 8
Low
ON
ON
696
Med-Lo
OFF
ON
825
Med-Hi
ON
OFF
1150
High
OFF
OFF
1298
TEM6A0C48H41SC, TEM6B0C60H51SA Airflow Performance with Auxiliary Heat
Airflow Settings
Dip Switch Settings
Nominal Airflow
See following tables for
heater application:
- Pressure Drop for
Electrical Heaters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
Switch 7
Switch 8
Low
ON
ON
1000
Med-Lo
OFF
ON
1130
Med-Hi
ON
OFF
1354
High
OFF
OFF
1596