22-1706-01-0400 (EN)
Performance
Data
VENT LENGTH TABLE
ALTITUDE
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET
FOR VENT AND INLET AIR (SEE NOTES)
0-7,000 Feet
2 INCH PIPE
2.5 INCH PIPE
3 INCH PIPE
TDX060R936V
200
200
200
TDX080R942V
50
120
200
TDX100R948V
Not Allowed
60
200
TDX120R960V
Not Allowed
Not Allowed
200
7,000-9,500 Feet
2 INCH PIPE
2.5 INCH PIPE
3 INCH PIPE
TDX060R936V
100
100
100
TDX080R942V
25
60
100
TDX100R948V
Not Allowed
30
100
TDX120R960V
Not Allowed
Not Allowed
100
9,500-12,000 Feet
2 INCH PIPE
2.5 INCH PIPE
3 INCH PIPE
TDX060R936V
50
50
50
TDX080R942V
Not Allowed
30
50
TDX100R948V
Not Allowed
Not Allowed
50
TDX120R960V
Not Allowed
Not Allowed
50
NOTES:
1. Minimum vent length for all models: 3' horizontal and vertical.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at
the top of the furnace).
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE
MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One
90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100A termination kit is used, the
equivalent length of pipe is 5 feet. BAYVENT200A/B equivalent length is 0 feet.
6. Pipe adapters are field supplied (except 120).