Furnace Heating 1st Stage Lockout – Once enabled, 
select an outdoor temperature which forces 2nd stage 
furnace heating operation.

7.6  Humidifier Operation

The 824 has the ability to control a humidifier through the 
normally open dry AUX Contacts on the Control Sub-base. 
Humidification is only enabled while in heating mode of 
operation. Control options are:

• 

RH Control – Dry contacts are closed anytime the 
indoor humidity is less than the heating target relative 
humidity. 

• 

Frost Control – The 824 Control references the 
outdoor temperature and structure integrity to offset 
the heating target relative humidity. This helps to 
limit the risk of frost or condensation from forming 
on interior walls and windows. A scale of 1 to 10 is 
provided based on the insulation properties and 
expected leakage of the home (1=Leaky with poor 
insulation, 10=Very Tight with good insulation). An 
outdoor temperature sensor must be connected and 
enabled for frost control to be available.

Frost Control Structure Integrity Scale

Leaky, Poor Insulation

Average

Good Insulation, Tight

1

2

3

4

5

6

7

8

9

10

The 824 Control can be setup to allow humidification 
anytime in heating mode or only when actively heating. 
The airflow during Humidifier-only is factory set to 100% 
but can be adjusted between 35%-100% (this requires 
a variable speed indoor blower with BK connected). 
All humidifier control options are located in the 
Installer Setup>Accessories Settings.

7.7  recovery

The 824 control utilizes a Stage Inhibit to limit equipment 
staging. This inhibit can be defeated in the following two 
manners.

7.7.1 Aggressive recovery

Disables stage inhibits in heating and cooling mode anytime 
the setpoint is adjusted more than 2°F

7.7.2 Heating Aggressive recovery

Disable stage inhibit in heating mode only when the outdoor 
temperature falls below the selected outdoor temperature

7.8  Ventilation Operation

The 824 has the ability to control a Ventilation system 
through the normally open dry AUX Contacts on the 824 
Control Sub-base. The blower is not interlocked on a call 
for ventilation. The ventilation run time per hour can be 
adjusted to meet ASHRAE 62.2 standards. A temperature 
override can be set to prevent ventilation operation when 

the outdoor temperature exceeds the minimum or maximum 
outdoor temperature selections. If outdoor temperature 
overrides are enabled the user can select to accumulate 
the missed ventilation run time. Options are below:

• 

Accumulate missed ventilation run time in 4 
hour increments and make up when the outdoor 
temperature is within the min/max settings.

• 

Accumulate missed ventilation run time in 24 
hour increments and make up when the outdoor 
temperature is within the min/max settings

• 

Accumulate missed ventilation run time in 4 hour 
increments and make up at the end of 4 hour period.

• 

Accumulate missed ventilation run time in 24 hour 
increments and make up at the end of 24 hour period.

All Ventilation control options are located in the 
Installer Setup>Accessories Settings.

7.9  Warm Air Discharge

Enabling Warm Air Discharge with BK connected will 
reduce the variable speed blower air flow by 20% when 
in compressor heating operation. Warm Air Discharge 
only applies to compressor heating and is disabled when 
hydronic, fossil fuel or electric heat (including supplemental 
heat) modes are activated. Warm Air Discharge can be 
enabled in Installer Setup>Comfort Settings.

7.10  Wet Heat (Hydronic) Operation

A hot water coil can be applied to either a variable speed 
or non-variable speed indoor unit. The hot water coil can 
be the sole source of heat or used as auxiliary heat when 
applied with a heat pump. When applied with a heat pump, 
wet heat is considered auxiliary heat and will operate in-
conjunction with heat pump heat. Switching the system 
mode to emergency heat would disable the heat pump and 
cycle the wet heat only. 
If applied with a variable speed air handler with BK 
connected, the blower speed during wet heat only heating 
will vary based on the system load value. The airflow will 
range from 35% to 100% depending on the system load 
value. When applied with a heat pump, the blower speed 
during heat pump and wet heat operation will be the higher 
of the two air flows. There are separate blower “On” and 
“Off” delays for wet heat in the 824 Control. 
The 824 Control is designed to operate forced air systems 
and should not be applied to non-forced air systems (radiant 
floors, radiators, etc…)
The hydronic heat blower delay options can be accessed 
by navigating to Installer > Setup > Airflow Settings.

Содержание TCONT824

Страница 1: ...is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information...

Страница 2: ...erious injury 1 Safety 2 2 Product Specifications 3 3 General Information 3 3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4...

Страница 3: ...ndoor Humidity Display Range 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit...

Страница 4: ...Control in recessed areas near metal objects or near structures i e doors appliances entertainment centers or shelving units Do not mount the Control closer than 2 inches to any pipes duct work or ot...

Страница 5: ...le in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4 of insulation from each...

Страница 6: ...STAGE HEAT COOL W NON VARIABLE SPEED BLOWER 14 DIAGRAM 16 AMERISTAR 1 STAGE COOLING PAGE DIAGRAM DESCRIPTION 16 DIAGRAM 17 1 OR 2 STAGE HEAT PUMP W TAM7 MODEL AIR HANDLER 16 DIAGRAM 18 1 STAGE HEAT P...

Страница 7: ...e installed wire between Y1 of the 824 and YI of the airflow control board 4 R and Y2 connections at outdoor unit are required only for two stage units Caution Do not run Outdoor Remote sensor wires i...

Страница 8: ...GE COOLING W GAM5B MODEL AIR HANDLER 824 COMFORT CONTROL INDOOR UNIT OUTDOOR UNIT NOTES 1 Y terminal must be connected at indoor unit for selected compressor air flow AUX 1 AUX 2 24VAC HOT COMMON SOV...

Страница 9: ...OR UNIT AUX 1 AUX 2 24VAC HOT COMMON SOV COOLING FAN HEATING ODT RS AUX1 AUX1 AUX2 AUX2 RC RH B C O Y1 Y2 YI YO G BK W1 W2 W3 ODT ODT RS1 RS1 R B O G W B Y Optional Outdoor Sensor Optional Remote Sens...

Страница 10: ...dle with HVAC wires Also keep away from high voltage wiring to avoid interference 824 COMFORT CONTROL 7 1 STAGE COOLING W GAT2 GAM2 MODEL AIR HANDLER INDOOR UNIT OUTDOOR UNIT AUX 1 AUX 2 24VAC HOT COM...

Страница 11: ...e 824 COMFORT CONTROL INDOOR UNIT OUTDOOR UNIT Diagram 10 1 or 2 Stage Cooling w TEM6 Air Handler NOTES 1 Cut and remove the BK jumper at the indoor unit 2 R Y2 connections at outdoor are only require...

Страница 12: ...per at the indoor unit IFC Board some units may require DIP switch settings 2 R Y2 connections at outdoor are only required for two stage units 824 COMFORT CONTROL 12 1 OR 2 STAGE COOLING W VARIABLE S...

Страница 13: ...nd taped off 824 COMFORT CONTROL 14 PACKAGE 1 OR 2 STAGE HEAT COOL w VARIABLE SPEED BLOWER PACKAGE UNIT 1 13 1 OR 2 STAGE COOLING w S9V2 FURNACE NOTES 1 Cut and remove the BK jumper at the indoor unit...

Страница 14: ...age wiring to avoid interference 824 COMFORT CONTROL 15 PACKAGE 1 STAGE HEAT COOL W NON VARIABLE SPEED BLOWER PACKAGE UNIT AUX 1 AUX 2 24VAC HOT COMMON SOV COOLING FAN HEATING ODT RS AUX1 AUX1 AUX2 AU...

Страница 15: ...824 Programmable Wi Fi Comfort Control 18 HD72D1 6 15...

Страница 16: ...24 and YI of the airflow control board 4 Connection to X2 is not required for this configuration Caution Do not run Outdoor Remote sensor wires in the same bundle with HVAC wires Also keep away from h...

Страница 17: ...not required for this configuration Caution Do not run Outdoor Remote sensor wires in the same bundle with HVAC wires Also keep away from high voltage wiring to avoid interference 1 X2 AUX 1 AUX 2 24V...

Страница 18: ...y from high voltage wiring to avoid interference X2 AUX 1 AUX 2 24VAC HOT COMMON SOV COOLING FAN HEATING ODT RS AUX1 AUX1 AUX2 AUX2 RC RH B C O Y1 Y2 O YI YO Y G BK W1 W2 G W W3 ODT ODT RS1 RS1 O R B...

Страница 19: ...o X2 is not required for this configuration Caution Do not run Outdoor Remote sensor wires in the same bundle with HVAC wires Also keep away from high voltage wiring to avoid interference X2 AUX 1 AUX...

Страница 20: ...the same bundle with HVAC wires Also keep away from high voltage wiring to avoid interference X2 AUX 1 AUX 2 24VAC HOT COMMON SOV COOLING FAN HEATING ODT RS AUX1 AUX1 AUX2 AUX2 R RH B C O Y1 Y2 Y2 G...

Страница 21: ...l board ICMC to enable pulse width control of the variable speed indoor blower Ensure clipped wires are capped and taped off 824 COMFORT CONTROL PACKAGE UNIT 1 Caution Do not run Outdoor Remote sensor...

Страница 22: ...st 2 B C at the Control is 24v common and must be connected to C at the Indoor and Outdoor Units 3 O at the Control must be connected to B at the Outdoor Unit for SOV operation SOV must also be config...

Страница 23: ...cted to the 824 3 Connection to X2 is not required for this configuration Optional Outdoor Sensor Optional Remote Sensor 2 1 3 Caution Do not run Outdoor Remote sensor wires in the same bundle with HV...

Страница 24: ...Do not run Outdoor Remote sensor wires in the same bundle with HVAC wires Also keep away from high voltage wiring to avoid interference 32 1 OR 2 STAGE HEAT PUMP w S9V2 FURNACE NOTES 1 Cut and remove...

Страница 25: ...824 Programmable Wi Fi Comfort Control 18 HD72D1 6 25...

Страница 26: ...Wizard The Installation Wizard appears when 1 the 824 Control is powered on for the first time 2 when the Restore Factory Defaults function is invoked Home Menu Service Technician Access Proceed Rest...

Страница 27: ...mber of cycles per hour during 1st stage cooling operation 2nd Stage Compressor Cooling Cycles Per Hour 2 to 6 Cph 3 Select the number of cycles per hour during 2nd stage cooling operation Compressor...

Страница 28: ...our for ventilation system Outdoor Temperature Ventilation Override Disable Enable Select whether an outdoor temperature override is allowed Outdoor temperature sensor must be connected and enabled to...

Страница 29: ...e Rate for additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater t...

Страница 30: ...n 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100 45 Seconds 100 30...

Страница 31: ...Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F to 120 F Select an outdoor temperature to force the system to 2nd stage comp...

Страница 32: ...75 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage coolin...

Страница 33: ...W1 W1 to W2 W1 to W2 W2 to W3 W2 to W3 LV 100 LV 200 LV 300 STAGE 4 STAGE 1 STAGE 2 STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2...

Страница 34: ...f operation based on the following rules Heating Indoor temperature is equal or less than heating setpoint Cooling Indoor temperature is equal to or greater than cooling setpoint or within 1 F of cool...

Страница 35: ...n variable speed blowers If enabled continuous fan operation will be interrupted when indoor RH exceeds desired cooling RH target A humidity icon will be displayed along with the fan icon to indicate...

Страница 36: ...allowing compressor or auxiliary heat again Restrict Compressor and Aux Heat 70 65 60 55 50 45 40 35 30 Aux Heat Only Compressor Only Comp or Aux Heat Allowed Compressor Lockout Set to 40 Minimum 10...

Страница 37: ...standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperature override...

Страница 38: ...Flash Drive Access Save Logs by navigating to Service Menu Save Logs 8 3 Diagnostics Within the Diagnostic screen are two items related to alerts Current Alerts Alerts which are currently active Alert...

Страница 39: ...ge of operation Load Value Fan Status Indoor Temperature Indoor Relative Humidity Heating and Cooling Setpoints Relative Humidity Setpoints Dehumidifier Status Outdoor Temperature Outdoor Relative Hum...

Страница 40: ...eck repair system Fan runs all the time 1 Fan mode is set to On Circulate or Clean mode 2 Field wiring issue 3 There is a failure in the indoor unit 1 Check Control settings to see if fan is set to On...

Страница 41: ...use harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the fo...

Страница 42: ...Installation Guide 42 18 HD72D1 6...

Страница 43: ...824 Programmable Wi Fi Comfort Control 18 HD72D1 6 43...

Страница 44: ...6 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations inclu...

Отзывы: