background image

Done

Next

8

To begin, press and hold the   and   

buttons until the display changes

System test 

number

Press

   

to turn on system

Press

   

to turn off system

Press

 

next

 

to advance to next test

Press

 

done

 

to terminate system test

System 

status

10

30

40

70

Heating system

Cooling system

Fan system

Comfort Control 

information 

(for reference only)

0  Heat and fan turn off.

1  Heat turns on. Fan also turns on immediately if Function 1 or 3 is 

set to “1” (see page ).

0  Compressor and fan turn off.

1  Compressor and fan turn on.

0  Fan turns off.

1  Fan turns on.

1 Software revision number (major revisions)

2 Software revision number (minor revisions)

3 Configuration identification code (major)

 Configuration identification code (minor)

5 Production configuration date code (week)

 Production configuration date code (year)

System Test

System Status 

Installer system test

CAUTION: EQUIPMENT DAMAGE HAZARD

Compressor protection (minimum off time) is bypassed during testing. To prevent  

equipment damage, avoid cycling the compressor quickly.

Follow the procedure below to test the heating, cooling and fan.

Содержание TCONT600AF11MA

Страница 1: ...TCONT600AF11MA Programmable Comfort Control Installation Instructions 69 1834 2 Pub No 18 HD25D20 3...

Страница 2: ...rienced technician Read these instructions carefully Failure to follow these instructions can damage the product or cause a hazardous condition Check the ratings in this booklet to verify that this pr...

Страница 3: ...s or chimneys Unheated uncooled areas such as an outside wall behind the Comfort Control NO NO NO Installation Pre installation checklist 2 Wallplate installation 3 Wiring 4 Wiring diagrams 5 Power op...

Страница 4: ...uide Wall anchors and mounting screws 2 each AA alkaline batteries 2 Programmable Comfort Control wallplate attached to back Required tools supplies No 2 Phillips screwdriver Small pocket screwdriver...

Страница 5: ...on wall level and mark hole positions with pencil 4 Drill holes at marked positions as shown below then tap in supplied wall anchors 5 Place wallplate over anchors insert and tighten mounting screws D...

Страница 6: ...nect to secondary side of heating system transformer Rc Cooling power Connect to secondary side of cooling system transformer Terminal block NOTES R Rc terminals In single transformer system leave met...

Страница 7: ...URNACE SINGLE STAGE COOLING SINGLE STAGE AIR CONDITIONER SINGLE STAGE GAS FURNACE 24VAC HOT 24VAC 600 COMFORT CONTROL TERMINAL BLOCK FAN COOLING HEATING FACTORY INSTALLED JUMPER SINGLE STAGE OIL FURNA...

Страница 8: ...back of thermostat optional if AC powered Battery Backup Power The Comfort Control can be powered by backup batteries when used with AC power During power interruptions the batteries will save time da...

Страница 9: ...12 CPH 3 Recommended for most compressors Other cycle rate options 1 2 4 5 or 6 CPH 0 Manual changeover Heat Cool Off 1 Auto changeover Heat Cool Auto Off See page 9 2 Auto changeover only Auto See pa...

Страница 10: ...e page 7 0 Compressor and fan turn off 1 Compressor and fan turn on 0 Fan turns off 1 Fan turns on 71 Software revision number major revisions 72 Software revision number minor revisions 73 Configurat...

Страница 11: ...n after shutdown This feature forces the compressor to wait for a few minutes before restarting During the wait time the message Cool On or Heat On heat pumps only will flash on the display When the s...

Страница 12: ...rature Low battery warning Current time day Current program period Wake Leave Return Sleep Temperature setting System status On when calling for heating or cooling flashes when waiting for compressor...

Страница 13: ...quipment to find the cause of the problem Check for loose or broken wires between the Comfort Control and the heating equipment Cooling system does not respond Cool On appears on screen Check for 24 V...

Страница 14: ...em Setting to Manual or Auto Changeover see page 7 Heat On is not displayed Change the System Setting to Heat and set the temperature level above the current room temperature Cool On is not displayed...

Страница 15: ...13...

Страница 16: ...Pub No 18 HD25D20 3 03 06 6200 Troup Highway Tyler TX 75711 9010 www trane com U S Registered Trademark Patents Pending 2006 American Standard All rights reserved...

Отзывы: