background image

6200 Troup Highway
Tyler, TX 75707
www.trane.com

The manufacturer has a policy of continuous product and product data improve-
ment and it reserves the right to change design and specifications without notice.

© 2012 Trane

Section 19. Checkout Procedures

19.1 Operational And Checkout Procedures

CHECKOUT PrOCEDUrE

After installation has been completed, it is recommended that the entire system be checked against the following list:
  1.  Be sure unit suspension (if used) is secure and that there 

are no tools or loose debris in or around or on top of the 

unit.  ..............................................................................  [  ]

  2.  Properly insulate suction lines and fittings.  ..................  [  ]
  3.  Properly secure and isolate all refrigerant lines.  ..........  [  ]
  4.  Verify that all electrical connections are tight.  ..............  [  ]
  5.  Check all duct outlets; they must be open and unrestrict-

ed.  ................................................................................  [  ]

  6.  Check drain lines and be sure all joints are tight. 

 ........  [  ]

  7.  Be sure the return air filter is installed. .........................  [  ]
  8.  Verify that all dip switches have been set correctly for your 

application.  ..................................................................  [  ]

  9.  Operate complete system in each mode to  

verify proper performance. Verify operation of supplemen-

tary electric heater. .......................................................  [  ]

Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, 

all units must be operated and charge adjustments made in accordance with procedures found in the Service 

Facts of the Outdoor Unit.

Pb

FAULT

UNIT

48

33

32

17

16

1

64

49

B K Jumper

TEST

TRANE U.S. INC.

VD

D

PG

D

MC

LR

VS

S

PG

C

3.3

V

SC

L

SD

A

GN

D

HUM

PART NO. LABEL

BAR CODE

12

34

5

STATUS

Yo Jumper

+13.8V

C60

C59

R57

R58

R64

R65

R76

R78

S3

R110

R41

R68

C40

R9

3

R109

R12

R55

R23

R20

R49

R13

R14

D23

D19

D18

C46

C39

C6

C23

R80

R71

R67

R52

R75

R72

C41

R61

Q6

Q7

R1

R33

R34

J4

Q1

X1

U4

U3

TZ2

T2

T1

R99

R98

R97

R6

0

R96

R95

R21

R91

R8

7

R8

8

R70

R86

R83

R81

R66

R79

R77

R54

R103

R106

R4

R104

R5

1

R5

R47

R42

R39

R82

R37

R3

5

R3

1

R74

R89

R25

R18

R19

R10

R9

R8

R3

R2

R5

R7

Q8

MOV1

L2

L3

K1

J3

J6

J9

D36

D35

D1

D22

D29

D2

5

D24

D7

D4

D2

D28

C57

C54

C51

C49

C48

C47

C52

C43

C42

C36

C35

C3

4

C31

C30

C29

C7

C3

C2

C1

U1

C58

R105

C50

U2

R24

R17

D6

D3

R NET

R NET 2

R73

1

J8

Yo

R

B

O

Y1

J1

W2

W1

R63

R62

R56

D21

D20

C32

C33

R38

R36

R16

R15

R32

R11

R28

R27

R26

D13

D12

D5

D11

D10

C24

C25

C4

C5

C16

C17

D8

R50

R45

R85

R84

D16

D15

D31

D30

C26

C27

C44

C45

D32

D33

R94

R100

R101

R

10

7

K2

R

6

C53

C2

2

C1

9

C

15

C

12

C9

C8

C1

1

C1

4

C1

8

C2

1

D26

R69

C37

C38

L1

R102

D27

R40

R46

R43

Q3

Q

1

1

HP

OU

Airflow Control (AFC)

Unit Test Button

Unit Test Mode

Unit Test Mode will exit if any demand is given to the unit.
To enter Unit Test Mode:
  1.  Set System Switch on comfort control to Off
  2.  Cycle power to the unit, wait 5 seconds
  3.  Within thirty seconds, press and hold the Unit Test Button 

for 1-2 seconds

Sequence of Unit Test Mode

  1.  EVC drives the EEV motor to the 1st stage position for 5 

seconds

  2.  EVC drives the EEV motor to the 2nd stage position for 5 

seconds

  3.  AFC energizes the blower at 50% and then continues 

to ramp until it reaches 100% cooling airflow. Humidifier 

contacts close when the blower starts

  4.  EHC energizes the W1, W2, and W3 circuit relay(s) for 5 

seconds in 5 second intervals

  5.  All relays de-energize and the blower shuts off after five 

seconds.  

If a fault occurs during the Unit Test Mode, the LED will flash 

the code and continue the test

Fault reporting

This unit stores the last four faults that have occurred. Each 

device will report the last four faults after each power 

cycle of the unit. See the Fault Table section in the 

Service Facts for a list of fault codes

Clearing Faults

To clear the last four faults of all control boards: 
  1.  Press and hold the Unit Test Button for 10-12 seconds.
  2.  Release the Unit Test button and “wait” 5 seconds. 
  3.  Cycle 230VAC power to the unit. (the blower panel can 

be removed to achieve this)

Содержание TAM7A0A24H21SB

Страница 1: ...ferred to your installing dealer or local distributor See the TAM7 Service Facts document for information on reading the Control Board LEDs Air Flow Tables and Troubleshooting Flowcharts Note The manu...

Страница 2: ...rwise puncture the unit cabinet in any location other than the ones illustrated in this Installer Guide or in an approved accessory s In staller Guide Important Under no conditions should metal strapp...

Страница 3: ...only in the first 3 4 of front bottom of unit in cross member Important Due to the unique design of this unit which allows the electrical wiring to be routed within the insulation do not screw cut or...

Страница 4: ...Turn screws on Heater panel 2 Pull panel straight out away from cabinet 3 Set aside Removal of the Line Set panel is required for all refrig erant line brazing and some condensate line assembly depen...

Страница 5: ...5kW Breaker RS 485 Control 1 Ph C BAYEVAC10LG3AA Electric Heater 10kW Lugs RS 485 Control 3 Ph A to C BAYEVBC15LG3AA Electric Heater 15kW Lugs RS 485 Control 3 Ph B to C BAYSUPFLGAA Supply Duct Flange...

Страница 6: ...To reassemble cabinet follow the steps in reverse order Ensure electrical connections are secure and the plug clips are engaged 4 1 Disassemble cabinet for installation in tight areas or as needed Se...

Страница 7: ...pread the top of the diverter slightly outwards and then pulling down and out through the blower opening as illustrated STEP 2 Disconnect the two wiring connections routed to the blower assembly STEP...

Страница 8: ...the sensor must be replaced after the coil is placed back into the cabinet STEP 6 Slide Coil assembly out of unit using built in coil support channels and set aside STEP 7 Use a 5 16 Allen wrench on...

Страница 9: ...9 1 2 STEP 8 Lift the Coil section up and away from the Blower section Set aside...

Страница 10: ...emove the top panel and all cross members Use a manual driver to avoid stripping screw holes Note Cross Members are removed by rotating them toward the door opening and then lifting up and out of the...

Страница 11: ...laced Important Under no conditions should metal strap ping be attached to the unit to be used as support mechanisms for carrying or suspension purposes Approved carrying 1 Hold by the cross members w...

Страница 12: ...ht lbs TAM7A0A24H21SB 49 9 x 17 5 x 21 8 28 1 120 TAM7A0B30H21SB 55 7 x 21 3 x 21 8 33 9 133 TAM7A0C36H31SB 56 9 x 23 5 x 21 8 35 1 143 TAM7A0C42H31SB 56 9 x 23 5 x 21 8 35 1 158 TAM7A0C48H41SB 61 7 x...

Страница 13: ...ctory suitable for four way application They are shipped in the down flow orientation 6 2 Four Way Conversion Upflow Condensate Drains Refrigerant Connections Downflow Condensate Drains Downflow Confi...

Страница 14: ...izontal Left Condensate Drains Low Voltage Connections inside unit Refrigerant Connections Horizontal Left Configuration Low Voltage Connections inside unit Horizontal Right Condensate Drains Airflow...

Страница 15: ...ve or utility room Review local codes to determine limitations if the unit is installed without a return air duct Ducted Return Non Ducted Return Supply Duct Plenum Accessory with safety guard CAUTION...

Страница 16: ...es can be made for installation and future maintenance Installation of the air handler must be made prior to or at the same time as the installation of the outdoor unit in order to allow access for re...

Страница 17: ...llation A i r f l o w Airflow Airflow 7 1 Secure Coil STEP 1 Remove Coil Panel STEP 2 Remove screw from documentation packet STEP 3 While the air handler is in the upflow position use the supplied scr...

Страница 18: ...s STEP 1 Prepare the location site as appropriate for your application and per national state and local code requirements STEP 2 Set the unit in position Representative Illustration Typical Downflow I...

Страница 19: ...do not screw cut or otherwise puncture the unit cabinet in any location other than the ones illustrated in this Installer Guide or in an approved ac cessory s Installer Guide Important Make certain th...

Страница 20: ...the air handler Reference ACCA Manual D Manual S and Manual RS along with the air handler Product Data and Service Facts for additional information Note Side return is not approved without Side Return...

Страница 21: ...ng may be required 2 All AHRI listed systems are tested with 25 feet of refrigeration tubing the rated tubing diameters are located in the electronic performance data system 3 If the refrigeration lin...

Страница 22: ...il refrigerant connec tion stubs until ready to make connections STEP 2 Remove the plastic cap and Schrader valve core from the gas line STEP 3 Wrap the vapor sensor with a wet rag Important Care must...

Страница 23: ...wet rag 3 Braze the refrigerant line connections Important Care must be taken during solder cap removal and brazing to avoid damage to unit compo nents and wiring STEP 8 Pressurize the refrigerant lin...

Страница 24: ...he Line Set panel Important Do not open the service valves until the refrigerant lines and indoor coil leak check and evacu ation are complete STEP 10 Evacuate until the micron gauge reads no higher t...

Страница 25: ...n lines away from air handler so they do not interfere with access panels Slope the drain lines downward a minimum of 1 4 per foot support per local codes Do not use reducing fittings in the condensat...

Страница 26: ...pending on climate and application needs Provide a means of drainage to prevent winter freeze up of condensate line Optional depend ing on climate and application needs STEP 6 Support the condensate p...

Страница 27: ...24 VOLTS WIRE SIZE MAX WIRE LENGTH 18 AWG 150 Ft 16 AWG 225 Ft 14 AWG 300 Ft 13 2 Low Voltage Hook up Instructions STEP 1 Route control wiring to unit Remove the external sheathing of the wiring appr...

Страница 28: ...nly Remove the control board completely from the con trol pocket Rotate the control board 180 degrees Place the control board 2 3 inches back into the control pocket Attach wiring per appropriate hook...

Страница 29: ...e stage of heat YI andYO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly Internally mounted condensate switch is optional a...

Страница 30: ...W2 and W3 together if comfort control has only one stage of heat YI andYO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly I...

Страница 31: ...TEMP EVAP A Y R 410 TRANE U S INC J3 OVR GAS TEMP FLOW 12V GND TEMP EVAP Pb FAULT UNIT 48 33 32 17 16 1 64 49 BK Jumper TEST TRANE U S INC V D D P G D M C L R V S S P G C 3 3 V S C L S D A G N D HUM 5...

Страница 32: ...ompressors 20 SEER 2 Compressors 16 SEER 2 Stages 19 SEER 2 Stages 20 SEER 2 Stages Note This dip switch should be changed while the power is off or no demand is present The power must be shut off and...

Страница 33: ...ol AFC INDOOR MODEL S2 1 S2 2 COOLING CFM TON HEATING CFM TON OFF OFF 400 430 OFF ON 360 390 ON OFF 380 410 ON ON 420 450 OFF OFF 400 430 OFF ON 360 390 ON OFF 380 410 ON ON 420 450 OFF OFF 370 420 OF...

Страница 34: ...FM mode Torque mode is optional and is recommended for high static applications High static conditions dramatically increase energy consumption with variable speed motors Evaluate the blower performan...

Страница 35: ...19 D18 C46 C39 C6 C23 R80 R71 R67 R52 R75 R72 C41 R33 R J4 Q1 X1 U4 U3 T2 T1 R97 R60 R21 R91 R87 R88 R70 R86 R66 R54 R106 R104 R42 R39 R82 R74 R25 R18 R19 R10 R9 R8 R2 R5 R7 Q8 MO L2 L3 K1 J6 J9 D36 D...

Страница 36: ...res are located within the wire pass through pro vided in the panel STEP 7 Slide control plate assembly into the control pocket until fully seated The control plate should be flush with the outer edge...

Страница 37: ...s injury WARNING 14 2 Make Electrical Connections Conduit Entry Points STEP 3 Route conduit if used to the entry point and connect 1 Use one hand to secure the conduit nut from inside of the heater co...

Страница 38: ...g on the inside of the Heater Compartment in the cabinet If an electric heater IS being installed see the Installer s Guide shipped with the electric heater Connect L1 L2 and ground wiring to pigtail...

Страница 39: ...3 24 4 EEV 3 4 3 8 TAM7A0B30H21SB 55 7 21 3 18 4 45 5 18 4 9 2 24 8 EEV 3 4 3 8 TAM7A0C36H31SB 56 9 23 5 20 5 46 7 20 5 10 3 24 2 EEV 7 8 3 8 TAM7A0C42H31SB 56 9 23 5 20 5 46 7 20 5 10 3 24 5 EEV 7 8...

Страница 40: ...ted by the 7th digit in model number Table 16 1 Filter Sizes Sytem Matched with Indoor Unit Model No Outdoor Unit Model No Subcooling 16 SEER HP TAM7A0B30H21SB 4A6H6024E G 4TWX6024E G 9 TAM7A0C36H31SB...

Страница 41: ...ower disconnect s to apply power to the indoor and outdoor units STEP 4 Set the system thermostat to ON OFF DONE CANCEL ON OFF ON DONE CANCEL STEP 1 Make sure all panels are securely in place and that...

Страница 42: ...o the G terminal of the AFC 4 The AFC micro processor sends a command to the se rial communicating blower motor to run at the 1st stage cooling cfm 1st stage cooling cfm is a multiplier of 2nd stage c...

Страница 43: ...correct cfm The EHC determines the amount of heat per stage by either factory programming or by the kW jumper position 5 The AFC micro processor sends a command to the serial communicating blower moto...

Страница 44: ...R54 R103 R106 R4 R104 R51 R5 R47 R42 R39 R82 R37 R35 R31 R74 R89 R25 R18 R19 R10 R9 R8 R3 R2 R5 R7 Q8 MOV1 L2 L3 K1 J3 J6 J9 D36 D35 D1 D22 D29 D25 D24 D7 D4 D2 D28 C57 C54 C51 C49 C48 C47 C52 C43 C4...

Отзывы: