Installation
PART-SVN237B-EN
15
Installation Procedure
Figure 11.
Compressor terminal box
New compressor terminal box
Motor NP D-Axis
Inductance (MDIx)
308 µH 475 µH 332 µH 317 µH 378 µH 332 µH 250 µH 219 µH 244 µH 170 µH 212 µH 270 µH
Motor NP Q-Axis
Inductance (MQIx)
308 µH 475 µH 332 µH 317 µH 378 µH 332 µH 250 µH 219 µH 244 µH 170 µH 212 µH 270 µH
Stator Resistance
(MSRx)
2106
µ
Ω
2780
µ
Ω
1960
µ
Ω
2240
µ
Ω
2840
µ
Ω
1960
µ
Ω
1380
µ
Ω
1220
µ
Ω
1440
µ
Ω
940 µ
Ω
1500
µ
Ω
2040
µ
Ω
Active Harmonic
Damping (AHDx)
Disable
Reset to Defaults
(RDFx)
No
Input Choke
Impedance (IMPx)
3%
Rectifier Type (RCTx)
6 Pulse
Leakage Signals
(MLIx)
200 µH 280 µH 230 µH 230 µH 300 µH 270 µH 190 µH 180 µH 185 µH 135 µH 175 µH 215 µH
(a) Motor information is stored in the 6th and 7th digit of the model number. For example, the digits in bold of this model number correspond to the
information in the tables above: CHHSR
B1
A1A0.
(b) Motor model EB is unique in that it has dual ratings at both 460V and 380V. For 200V/230V/460V/575V chillers use the left most EB column. For
380V/400V chillers use the right most EB column.
(c) For certain models, a lesser RLA is used since the installed AFD3 drive is smaller on chillers with 1
st
Generation GP4 Classic Compressors. Refer to
to decipher the generation of the failed compressor being replaced. Program the appropriate RLA per the 1
st
Gen or 2
nd
Gen row in the
table.
Table 8.
Programming values for AFD3 drive (continued)
AFD3 Parameter
Name (FCAT)
GP4 Gen
Replacing
GP4 VarVi Service Model Number
(a)
FA
EA
EB
(b)
CA
BA
EB
(b)
FC
FB
EC
FD
CB
BB