10
PKG-SVX027C-EN
General Data
Table 1. SCWM water-cooled self-contained, 40 to 80 tons
Tonnage
40L Ton 40 Ton 50L Ton 50 Ton 60L Ton 60 Ton 70L Ton
(a)
70 Ton
80L Ton
80 Ton
Compressor Data
Quantity
1VS- 1FS 1VS- 1FS 1VS- 2FS 1VS- 2FS 1VS- 2FS 1VS- 2FS
1VS- 3FS
1VS- 3FS
1VS- 3FS
1VS- 3FS
Nominal Ton/Comp
10T- 15T 15T- 15T 10T- 13T 15T- 13T 10T- 15T 15T- 15T
10T- 13T
15T- 13T
10T- 15T
15T- 15T
Circuits
2
2
3
3
3
3
4
4
4
4
Evaporator Coil Data
Rows
4
4
3
3
4
4
4
4
4
4
4
4
4
4
Sq. Ft.
25.5
25.5
33
33
38
38
19.8 33.3 19.8 33.3 19.8 33.3 19.8 33.3
Fins/in
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13
13.5 13.5 13.5 13.5 13.5 13.5
Number of Coils
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Condenser Data
Minimumum GPM w/o Econ
(b)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Minimum GPM w/ Econ
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Maximum GPM
140
140
210
210
210
210
280
280
280
280
Evaporator Fan Data
Quantity
3
3
3
3
4
4
5
5
5
5
Diameter
500 mm
500 mm
500 mm
500 mm
500 mm
500 mm
500 mm
500 mm
500 mm
500 mm
Power consumption kW
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
Minimum Design cfm
(c)
11000
11000
13750
13750
16500
16500
19250
19250
22000
22000
Maximum Design cfm
16000
16000
20000
20000
24000
24000
28000
28000
32000
32000
Refrigerant Charge, lbs. R-410A
(d)
Circuit A
17
18
17
18
17
18
20
21
20
21
Circuit B
19
19
18
18
19
19
18
18
19
19
Circuit C
x
x
18
18
19
19
18
18
19
19
Circuit D
x
x
x
x
x
x
17
17
18
18
Filter Data, Water-Cooled Units
Number - Size (in.)
9 - 24"x 20"
12 - 24"x 20"
15 - 24"x 24"
Number of Compressors
10 HP - Variable Speed
1
0
1
0
1
0
1
0
1
0
15 HP - Variable Speed
0
1
0
1
0
1
0
1
0
1
13 HP - Fixed Speed
0
0
2
2
0
0
3
3
0
0
15 HP - Fixed Speed
1
1
0
0
2
2
0
0
3
3
Number of fans/unit
No. of fans
3
4
5
Note:
All performance data is provided in the Performance Selection Program. Contact Trane Sales at 770-988-8338 for more information.
(a)
Split coils
(b)
All performance data is provided in the Performance Selection Program. Contact MJC Sales at 770-988-8338 for more information.
(c)
Minimum air flow at part load is 35% of full load design CFM.
(d)
Refrigerant charge shown is a general guideline, charge to sub-cooling as described in IOM. Note that occasionally a TXV adjustment may need to be made
but only after adequate sub-cooling has been reached.