Parts Ordering
RLC-SVN005B-EN
47
Starter Power Leads
The power leads traveling from the incoming power lines
to the solid state starter panel and then from the solid state
starter panel to the compressor motor terminals can be
obtained locally or ordered from Trane Service Parts.
Two wiring kits are necessary for each unit.
Circuit Breaker with Shunt Trip
The Benshaw solid state starter requires a shunt trip circuit
breaker. If the existing starter has a circuit breaker without
a shunt trip device, either a shunt trip element needs to be
added to the circuit breaker or the circuit breaker needs to
be upgraded to include a shunt trip device. The addition of
the shunt trip circuit breaker/device may require some
mechanical modifications to the cabinet.
Additional Components
Some additional components are necessary for proper
operation. Refer to each specific unit section to determine
which additional components are necessary.
Note:
Secure locally any required low voltage wire, bolts,
nuts and other hardware as required.
Service Components
In the event of an MX logic module failure, the MX logic
module is NO LONGER AVAILABLE. See
for
information on MX-to-MX2 logic module conversion.
Production Change
All units ordered with a solid state starter after February
2005 were manufactured with the Benshaw Redistart Solid
State Starter.
Questions
Contact the Product Technical Service department in
Pueblo, Colorado with questions regarding this
Installation Guide. They can be contacted at
[email protected].
Table 7.
Starter power lead kits
Unit Type
Max Panel RLA
Kits
RTHA/RTHB
0-300 amps
(130-150 ton ONLY)
WIR04920 and WIR04924
(motor terminal lugs - 3/8”)
0-300 amps
(180 ton and larger)
WIR04919 and WIR04923
(motor terminal lugs - 5/8”)
301-476 amps
WIR04918 and WIR04922
477-598/500 amps
WIR04917 and WIR04921
RTHC
0-300 amps
WIR04927 and WIR04930
301-476 amps
WIR04926 and WIR04929
477-598/500 amps
WIR04925 and WIR04928
RTHD
0-207 amps
WIR04833 and WIR04838
208-300 amps
WIR04832 and WIR04837
301-397 amps
WIR04831 and WIR04836
398-476 amps
WIR04830 and WIR04835
477-598/500 amps
WIR04829 and WIR04834
Table 8.
Additional Components
Part Description
Part Number
Cabinet Fan
FAN03692
Pilot Relay 2K300, 1K300,
2K400, 1K400, 1K11
RLY02467
Shunt Trip
(Breaker)
Required with all Benshaw SSS. Contact Trane
Service Parts or select and obtain locally per
state and local NEC codes.
Remote
SSS display
BRD03541 KPMX3CBL2M
MX2: NEMA 4 Remote Keypad with 2 m Cable
BRD03599 MX-2M-RKO-00
MX: NEMA 4 Remote Keypad with 2 m Cable
CAUTION safety label
LBL00419 (Qty 2/unit required)
Table 9.
Service components
Part Description
Part Number
Kit - MX2 Logic Module Conversion
KIT16751