Figure 25.
Photograph of IT solid state starter — RTHC
RTHC Units with IT (or Wye-Delta) Starter
RLC-SVN005B-EN
27
Installation of Benshaw Starter
Once all of the above components are removed, see
for the approximate locations of the new
components.
The Benshaw Redistart SSS is supplied with current
transformers. The current transformers wired to the chiller
need to remain installed as shipped from the factory. The
current transformers supplied with the solid state starter
need to be installed as close to the original current
transformers as possible for proper operation. See
for proper installation location of the
Benshaw current transformers.
Note:
Benshaw CTs are polarity sensitive. For specific
details on mounting of the Benshaw Solid State
Starter, refer to the “Benshaw Solid State Starter
Hardware Manuel” pages 20-32. The manual ships
with the Benshaw starters.
Figure 26.
Location of Benshaw starter and additional components (highlighted) — RTHC
"ENSHAW
2EDISTART
3OLID
3TATE
3TARTER
&AN
#4
#4
#4