Start-Up and Shutdown
RTAF-SVX001K-EN
61
Power Up Diagram
The Power up chart shows the respective AdaptiView
screens during a power up of the Symbio™ 800 and
display. This process takes 15 seconds for the Symbio™
800 and 100 seconds for the display. On all power ups, the
software model always will transition through the
'Stopped' Software state independent of the last mode. If
the last mode before power down was 'Auto', the
transition from 'Stopped' to 'Starting' occurs, but it is not
apparent to the user.
Figure 39.
Sequence of operation: power up diagram
Stopped
Stopped
External
Power
Applied
Symbio 800 Fully
Operational
Booting Symbio 800
(15 Seconds)
Operator Display and
Symbio 800 Start Booting
Last Mode
Auto
Last Mode
Stop
IPC Bus Comm Begins
Booting Operator Display
(45 Seconds)
Display Finishes Booting
Display Starts Loading Data
Loading Display Data
(55 Seconds)
Display Finished Loading Data
See Figure 1
Remain in
“Stop”
indefinitely until
“Auto” command
See
“Stopped To Starting”
Starting Sequence
See “Power Up to
Starting” Sequence Diagram
Starting Sequence
See “Power Up to
Starting” Sequence Diagram
Symbio 800 Boot Up
Symbio 800 Boot Up
IF
Minimum Time Until First
Compressor Restarts
(39 Seconds)
Continue Along
Starting Sequence See
“Power Up to Starting”
*Display will show either Auto or Stop button active once it is fully loaded
Stopped
External
Power
Applied
Symbio 800 Fully
Operational
Booting Symbio 800
(15 Seconds)
Operator Display and
Symbio 800 Start Booting
Last Mode
Auto
Last Mode
Stop
IPC Bus Comm Begins
Booting Operator Display
(45 Seconds)
Display Finishes Booting
Display Starts Loading Data
Loading Display Data
(55 Seconds)
Display Finished Loading Data
See Figure 1
Remain in
“Stop”
indefinitely until
“Auto” command
See
“Stopped To Starting”
Starting Sequence
See “Power Up to
Starting” Sequence Diagram
Symbio 800 Boot Up
IF
Minimum Time Until First
Compressor Restarts
(39 Seconds)
Continue Along
Starting Sequence See
“Power Up to Starting”