Installation Electrical
RTAF-SVX001K-EN
51
AFD Drive Programming
Field replacement drives must be programmed via the
keypad interface. Program parameters sequentially by ID
values as defined in tables below.
Table 24. Non-compressor specific parameter settings
ID
Description
Setting
0-03
Region Settings
[1] North American
0-20
Display Line 1.1 Small
[1612] Motor Voltage
0-24
Display Line 3 Large
[1617] Speed (rpm)
0-40
[Hand on] Key on LCP
[0] Disabled
0-41
[Off] Key on LCP
[0] Disabled
0-60
Main Menu Password
999
0-61 Access to Main Menu w/o Password
[1] LCP: Read-only
1-03
Torque Characteristics
[0] Compressor Torque
1-21
Motor Power [HP]
See table below
(a)
1-22
Motor Voltage
See table below
1-23
Motor Frequency
60Hz
1-24
Motor Current
See table below
1-25
Motor Nominal Speed
See table below
1-71
Start Delay
0s
1-73
Flying Start
[0] Disabled
1-78
Compressor Start Max Speed [Hz]
30Hz
1-79
Compressor Start Max Time to Trip
10s
1-82 Min Speed for Function at Stop [Hz]
10Hz
1-87
Trip Speed Low [Hz]
25Hz
3-02
Minimum Reference
30Hz
3-03
(b)
Minimum Reference
See
3-41
Ramp 1 Ramp Up Time
5s
3-42
Ramp 1 Ramp Down Time
5s
3-82
Starting Ramp Up Time
3s
4-10
Motor Speed Direction
[0] Clockwise
4-12
Motor Speed Low Limit [Hz]
30Hz
4-18
Current Limit
128.4%
4-19
Max Output Frequency
See table below
4-
Motor Speed High Limit [Hz]
See
5-12
Terminal 27 Digital Input
[2] Coast Inverse
5-13
Terminal 29 Digital Input
[0] No Operation
5-40.0
Function Relay 1
[5] Running
5-40.1
Function Relay 2
[3] Drive Rdy/Rem Ctrl
5-41.0
On Delay, Relay 1
1s
5-41.1
On Delay, Relay 2
1s
5-42.0
Off Delay, Relay 1
1s
5-42.1
Off Delay, Relay 2
1s
6-10
Terminal 53 Low Voltage
2V
6-14
Terminal 53 Low Ref./Feedb. Value
30Hz
6-
Terminal 53 High Ref./Feedb. Value
See
6-50
Terminal 42 Output
[133] Motor Cur. 4-
20mA
14-03
Overmodulation
[0] Off
14-10
Mains Failure
[4] Kinetic Back-up
14-11
Mains Voltage at Mains Fault
See table below
14-20
Reset Mode
[1] Automatic Reset x 1
14-30 Current Lim Ctrl. Proportional Gain
25%
14-31 Current Lim Ctrl. Integration Time
1s
14-50
RFI Filter
[0] Off
14-51
DC Link Compensation
[1] On
22-75
Short Cycle Protection
[1] Enabled
22-76
Interval Between Starts
60s
(a) For unit sizes 115 to 215, see
. For unit sizes 230 to 520 tons,
see
.
(b) Parameter for 230 to 520 ton units only.
Table 24. Non-compressor specific parameter settings
(continued)
ID
Description
Setting
Table 25. Compressor-specific parameter settings, 115 to 215 tons — 60Hz
(a)
Parameters
L1
L2
M3
M4
N3
ID
Description
460V 380V 575V 460V 380V 575V 460V 380V 575V 460V 380V 575V 460V 380V 575V
1-21 Motor Power (hp)
86
86
86
102
102
102
122
122
122
144
144
144
177
177
177
1-22 Motor Voltage (V) 460V
380V
575V
460V
380V
575V
460V
380V
575V
460V
380V
575V
460V
380V
575V
1-24 Motor Current (A) 91A
110A
73A
109A
132A
87A
128A
154A
101A
151A
182A
120A
183A
221A
146A
1-25
Motor Nominal
Speed (rpm)
3461
3460
3461
3459
3466
3461
3502
3505
3503
3494
3494
3494
3494
3495
3493
4-19
Max Output
Frequency (Hz)
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
14-11
Voltage at Main
Fault (V)
391V
323V
489V
391V
323V
489V
391V
323V
489V
391V
323V
489V
391V
323V
489V
(a) 400V/50 Hz units use 380V/60Hz compressor settings.