Field Installed Assembly and Installation
8
ACC-SVN261A-EN
5. Secure the economizer assembly with two screws 22 at the
bottom of the corner posts.
6. Install 21 and secure with three screws 23.
7. Using field supplied silicone, apply sealant around
economizer hood 24.
Figure 7.
Removing the bottom blockoff
Figure 8.
Fastening the economizer and bottom
blockoff
Horizontal Configuration
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is present
with a voltmeter.
The economizer must be removed from the rooftop unit and
reconfigured for horizontal operation.
1. Remove filter access panel.
2. Remove 2, shown in
. (Leave the screws
loosely in place.)
3. Remove the bottom three screws and top two screws from
the economizer panel.
4. Remove 15, shown in
.
5. Pull the economizer assembly and end panel out of the
unit.
6. Reconfigure the damper for horizontal operation. See
“Reconfigure the Damper (for Horizontal Installation only),”
p. 6
for instructions, and then return to this procedure.
7. If optional sensors for humidity and temperature
monitoring are to be used (FIAENTH001* and
FIAENTH002*), install them now. Use the instructions
provided in those kits.
8. Remove supply and return duct covers from the horizontal
openings and install over the downflow openings.
9. Reinstall the economizer. See
for instructions.
Minimum Position Setting
To adjust the minimum position setting and check out the
economizer, the power must be connected.
1. Close the unit disconnect and place the zone sensor fan
selector in the fan
ON
position and the heat/cool selector
in the
OFF
position. This will place the damper in the
minimum ventilation position.
2. To adjust the minimum position setting for the required
ventilation air, use the Symbio™ service and installation
mobile app or Symbio™ 700 on-board UI to adjust the
economizer minimum position setpoint BAS in the
fresh/return air settings menu. The damper will open to this
setting each time the blower circuit is energized.
When adjusting minimum position, the damper may
move to the new setting in several small steps. Once the
damper has remained in position for 10 - 15 seconds
21
22
21
23
(second screw
not visible)