Field Installed Assembly and Installation

8

 ACC-SVN261A-EN

5. Secure the economizer assembly with two screws 22 at the 

bottom of the corner posts.

6. Install 21 and secure with three screws 23.
7. Using field supplied silicone, apply sealant around 

economizer hood 24.

Figure 7.

Removing the bottom blockoff

Figure 8.

Fastening the economizer and bottom 
blockoff

Horizontal Configuration

WARNING

Hazardous Voltage!

Failure to disconnect power before servicing could 
result in death or serious injury. 
Disconnect all electric power, including remote 
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be 
inadvertently energized. Verify that no power is present 
with a voltmeter.

The economizer must be removed from the rooftop unit and 
reconfigured for horizontal operation.
1. Remove filter access panel.
2. Remove 2, shown in 

Figure 1, p. 6

(Leave the screws 

loosely in place.)

3. Remove the bottom three screws and top two screws from 

the economizer panel.

4. Remove 15, shown in 

Figure 5, p. 7

.

5. Pull the economizer assembly and end panel out of the 

unit.

6. Reconfigure the damper for horizontal operation. See 

“Reconfigure the Damper (for Horizontal Installation only),” 
p. 6

 for instructions, and then return to this procedure.

7. If optional sensors for humidity and temperature 

monitoring are to be used (FIAENTH001* and 
FIAENTH002*), install them now. Use the instructions 
provided in those kits.

8. Remove supply and return duct covers from the horizontal 

openings and install over the downflow openings.

9. Reinstall the economizer. See 

“Install Economizer into the 

Rooftop Unit,” p. 7

 for instructions.

Minimum Position Setting

To adjust the minimum position setting and check out the 
economizer, the power must be connected.
1. Close the unit disconnect and place the zone sensor fan 

selector in the fan 

ON

 position and the heat/cool selector 

in the 

OFF

 position. This will place the damper in the 

minimum ventilation position.

2. To adjust the minimum position setting for the required 

ventilation air, use the Symbio™ service and installation 
mobile app or Symbio™ 700 on-board UI to adjust the 
economizer minimum position setpoint BAS in the 

fresh/return air settings menu. The damper will open to this 
setting each time the blower circuit is energized.

When adjusting minimum position, the damper may 

move to the new setting in several small steps. Once the 
damper has remained in position for 10 - 15 seconds 

21

22

21

23

(second screw

not visible)

Содержание Precedent FIAECON002 Series

Страница 1: ...es specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precaut...

Страница 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Страница 3: ...cies those regulations supersede these policies Non Trane personnel should always follow local regulations Introduction ACC SVN261A EN 3 Copyright This document and the information in it are the prope...

Страница 4: ...re the Damper for Horizontal Installation only 6 Optional Sensors 7 Install Duct Blockoff Plate Downflow Units only 7 Install Economizer into the Rooftop Unit 7 Symbio Wiring Connections 7 Factory Ins...

Страница 5: ...Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur after delivery 6 Notify the c...

Страница 6: ...ws into 6 See below figure Figure 2 Assembling the end panel Reconfigure the Damper for Horizontal Installation only The economizer damper is pre configured at the factory for downflow applications Re...

Страница 7: ...side the filter section 3 will slip over the three screws 9 Align the holes in the plate with the holes in the panel 10 Secure the bottom right with a screw 22 11 Install the bottom blockoff 21 and se...

Страница 8: ...ation See Reconfigure theDamper forHorizontal Installation only p 6 for instructions and then return to this procedure 7 If optional sensors for humidity and temperature monitoring are to be used FIAE...

Страница 9: ...tdoor Air Humidity Sensor Return Air Temperature Sensor Return Air Humidity Sensor Reference Enthalpy Outside Air Enthalpy Reference Enthalpy Setpoint Econ Enthalpy Offset AND Outside Air Temperature...

Страница 10: ...Notes 10 ACC SVN261A EN...

Страница 11: ...Notes ACC SVN261A EN 11...

Страница 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Отзывы: