ACC-SVN231A-EN
13
Wiring – FIADMPR102*/103*
1. Using the supplied harness connect PPF87 to the
actuator connector.
2. Route harness to fresh air options module located in
the return section and connect to FAOM-J11.
3. After installation is complete, Symbio™ 700 UC unit
configuration will need to be updated to reflected
installed option.
Figure 9.
Fresh air options module
R
BL
O
R
P
BL
BK
R
BL
BK
R
BL
O
BK R BL
FRESH AIR OPTIONS MODULE
(FOM)
24 VAC OUT
Spare Universal IO 2
Spare Transducer Zeroing Pin
Common
P13
24 VDC OUT
OA Damper Feedback
OA Damper OUT
Common
P10
24 VDC OUT
Spare Universal IO 1
Spare Transducer Zeroing Pin
Common
P12
Return Air Humidity Input
Common
24 VDC OUT
24 VDC OUT
P9
Outdoor Air Humidity Input
Return Air Temp Input
Spare Binary Output 1
Common
P6
Spare Binary Output 2
Common
P7
Spare Binary Output 3
Common
P8
P2
24 V
AC OU
T
RA S
m
oke D
e
tector
Input
Com
m
o
n
P1
P4
GND
Address 3
GND
Address 1
GND
Address 2
Address 4
GND
J11
Spare Univ
ers
a
l Input 5
Com
m
o
n
P14
Cl
ogge
d Fil
te
r Sw
itch IN
24 V
AC OU
T
P15
Spare
B
inary
Inpu
t
3
P16
Spare
B
inary
Inpu
t
4
P17
Spare
B
inary
Inpu
t
5
P18
Spare Analog Output 4
Common
Spare
A
n
alog
O
u
tp
ut
3
Com
m
o
n
P21
Spare
B
inary
Outp
ut
4
P20
24 V
DC OU
T
Spare Univ
ers
a
l Input 7
Spare
U
n
iv
e
rsal
Input 6
J4
Spare
A
n
alog
O
u
tp
ut
2
Com
m
o
n
J5
P19
J6
3
P11
1
2
1
2
J2
3
1
2
J1
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
4
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
3
4
5
6
5
6
1
2
1
2
1
2
1
2
1
2
3
4
3
4
5
6
5
6
7
8
7
8
Modbus
+
Modbus
-
Com
m
o
n
1
2
3
1
2
3
1
2
3
P3
Modbus
+
Modbus -
C
o
mmo
n
1
2
3
24 V
AC OU
T
Com
m
o
n
IMC
+
IMC
-
1
2
3
4
IMC Bus
(White)
P5
White
BK R BL O
24 V
AC OU
T
Com
m
o
n
IMC
+
IMC
-
1
2
3
4
TO UC-P4
SHEET 3
1
2
3
4
Common
Spare Universal IO 1 (Alt)
5 VDC OUT
Common
5 VDC OUT
Spare Universal IO 2 (Alt)
Spare
B
inary
Inpu
t
2
24 V
AC OU
T
24 V
AC OU
T
24 V
AC OU
T
24 V
AC OU
T
Com
m
o
n
Supply
V
o
ltage IN
3
1
2
(Black)
ECA
24 V? IN
DAMPER POSITION IN
DAMPER POSITION OUT
IMC Bus
(White)
(Red)
(Gray)
(Blue)
(White)
(White)
(Black)
(White)
(Purple)
(White)
(Mint)
(Red)
(Pink)
(Orange)
(Green)
(Green)
(Green)
(Blue)
(Yellow)
(Black)
(Black)
(Green)
(Brown)
3
1
2
3
1
2
RASD
24 VAC IN
Smoke Detector OUT
3
1
2
Common
CFS
BK R
BK R
1
2
1
2
1
2
1
1
Common
4 4
BK
O
1
2
1
2
Oponal Return Air Humidity Sensor
-H°
RAH
3
R
Y
1
2
1
2
Oponal Outdoor Air Humidity Sensor
-H°
OAH
4
t°
RAT
BL
BR
1
2
1
2
Oponal Return Air Temp Sensor
2
FRESH AIR OPTIONS MODULE ONLY PRESENT ON CERTAIN UNIT CONFIGURATIONS. SEE INSET A FOR
UNITS WITHOUT FRESH AIR OPTIONS MODULE.
1
BK R BL O
BK R BL O
White
BK R BL O
1
2
3
4
1
2
3
4
White
BK R BL O
1
2
3
4
TO IOM-P4
SHEET 5
1
2
3
4
TO AIRFI
1
INSET A
BK R
BK R
XFR
2
1
White
BK R BL O
1
2
3
4
TO AIRFI
3
4
2
RETURN AIR TEMP SENSOR PRESENT ON UNITS WITH DIFFERENTIAL DRY BULB, REFERENCE ENTHALPY,
AND COMPARATIVE ENTHALPY CONTROL
RETURN AIR HUMIDITY SENSOR PRESENT ON UNITS WITH REFERENCE ENTHALPY AND COMPARATIVE
ENTHALPY CONTROL
RETURN AIR HUMIDITY SENSOR PRESENT ON UNITS WITH COMPARATIVE ENTHALPY CONTROL
PPF62
PPF63
PPF64
PPF87
PPM87
PPF88
PPM88
PPF86
PPM86
BK
2
1
TO LINE 320
Sheet 6
J11-1
TO LINE 322
Sheet 6
J8-1
3
1
2
ECA
24 V? IN
DAMPER POSITION IN
DAMPER POSITION OUT
Common
4
BK
R
BL
O
3
1
2
4
Oponal Horizontal Low Leak
Oponal Economizer
Oponal Economizer
Oponal Return Air Smoke Detector
Oponal Power Exhaust
Содержание Precedent FIADMPR102 Series
Страница 14: ...Notes 14 ACC SVN231A EN...
Страница 15: ...Notes ACC SVN231A EN 15...