background image

ACC-SVN231A-EN

13 

Wiring – FIADMPR102*/103*

1. Using the supplied harness connect PPF87 to the 

actuator connector. 

2. Route harness to fresh air options module located in 

the return section and connect to FAOM-J11. 

3. After installation is complete, Symbio™ 700 UC unit 

configuration will need to be updated to reflected 
installed option.

Figure 9.

Fresh air options module

R

BL

O

R

P

BL

BK

R

BL

BK

R

BL

O

 BK       R      BL

FRESH AIR OPTIONS MODULE

(FOM)

24 VAC OUT

Spare Universal IO 2

Spare Transducer Zeroing Pin

Common

P13

24 VDC OUT

OA Damper Feedback

OA Damper OUT

Common

P10

24 VDC OUT

Spare Universal IO 1

Spare Transducer Zeroing Pin

Common

P12

Return Air Humidity Input

Common

24 VDC OUT

24 VDC OUT

P9

Outdoor Air Humidity Input

Return Air Temp Input

Spare Binary Output 1

Common

P6

Spare Binary Output 2

Common

P7

Spare Binary Output 3

Common

P8

P2

24 V

AC OU

T

RA S

m

oke D

e

tector 

Input

Com

m

o

n

P1

P4

GND

Address 3

GND

Address 1

GND

Address 2

Address 4

GND

J11

Spare Univ

ers

a

l Input 5

Com

m

o

n

P14

Cl

ogge

d Fil

te

r Sw

itch IN

24 V

AC OU

T

P15

Spare

 B

inary

 Inpu

3

P16

Spare

 B

inary

 Inpu

4

P17

Spare

 B

inary

 Inpu

5

P18

Spare Analog Output 4

Common

Spare

 A

n

alog

 O

u

tp

ut 

3

Com

m

o

n

P21

Spare

 B

inary

 Outp

ut

 4

P20

24 V

DC OU

T

Spare Univ

ers

a

l Input 7

Spare

 U

n

iv

e

rsal

 Input 6

J4

Spare

 A

n

alog

 O

u

tp

ut 

2

Com

m

o

n

J5

P19

J6

3

P11

1

2

1

2

J2

3

1

2

J1

1

2

3

4

1

2

3

4

1

2

1

2

3

4

3

4

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

3

4

3

4

5

6

5

6

1

2

1

2

1

2

1

2

1

2

3

4

3

4

5

6

5

6

7

8

7

8

Modbus

 +

Modbus

 -

Com

m

o

n

1

2

3

1

2

3

1

2

3

P3

Modbus

 +

Modbus -

C

o

mmo

n

1

2

3

24 V

AC OU

T

Com

m

o

n

IMC

 +

IMC

 -

1

2

3

4

IMC Bus

(White)

P5

White

 BK       R      BL       O

24 V

AC OU

T

Com

m

o

n

IMC

 +

IMC

 -

1

2

3

4

TO UC-P4

SHEET 3

1

2

3

4

Common

Spare Universal IO 1 (Alt)

5 VDC OUT

Common

5 VDC OUT

Spare Universal IO 2 (Alt)

Spare

 B

inary

 Inpu

2

24 V

AC OU

T

24 V

AC OU

T

24 V

AC OU

T

24 V

AC OU

T

Com

m

o

n

Supply

 V

o

ltage IN

3

1

2

(Black)

ECA

24 V? IN

DAMPER POSITION IN

DAMPER POSITION OUT

IMC Bus

(White)

(Red)

(Gray)

(Blue)

(White)

(White)

(Black)

(White)

(Purple)

(White)

(Mint)

(Red)

(Pink)

(Orange)

(Green)

(Green)

(Green)

(Blue)

(Yellow)

(Black)

(Black)

(Green)

(Brown)

3

1

2

3

1

2

RASD

24 VAC IN

 Smoke Detector OUT

3

1

2

Common

CFS

 BK       R

 BK       R

1

2

1

2

1

2

1

1

Common

4 4

BK

O

1

2

1

2

Oponal Return Air Humidity Sensor

-H° 

RAH

3

R

Y

1

2

1

2

Oponal Outdoor Air Humidity Sensor

-H° 

OAH

4

t° 

RAT

BL

BR

1

2

1

2

Oponal Return Air Temp Sensor

2

FRESH AIR OPTIONS MODULE ONLY PRESENT ON CERTAIN UNIT CONFIGURATIONS. SEE INSET A FOR 
UNITS WITHOUT FRESH AIR OPTIONS MODULE.

1

 BK       R      BL       O

 BK       R      BL       O

White

 BK       R      BL       O

1

2

3

4

1

2

3

4

White

 BK       R      BL       O

1

2

3

4

TO IOM-P4

SHEET 5

1

2

3

4

TO AIRFI

1

INSET A

 BK       R

 BK                        R

XFR

2

1

White

 BK       R      BL       O

1

2

3

4

TO AIRFI

3

4

2

RETURN AIR TEMP SENSOR PRESENT ON UNITS WITH DIFFERENTIAL DRY BULB, REFERENCE ENTHALPY, 
AND COMPARATIVE ENTHALPY CONTROL

RETURN AIR HUMIDITY SENSOR PRESENT ON UNITS WITH REFERENCE ENTHALPY AND COMPARATIVE 
ENTHALPY CONTROL

RETURN AIR HUMIDITY SENSOR PRESENT ON UNITS WITH COMPARATIVE ENTHALPY CONTROL

PPF62

PPF63

PPF64

PPF87

PPM87

PPF88

PPM88

PPF86

PPM86

 BK 

2

1

TO LINE 320

Sheet 6

J11-1

TO LINE 322

Sheet 6

J8-1

3

1

2

ECA

24 V? IN

DAMPER POSITION IN

DAMPER POSITION OUT

Common

4

BK

R

BL

O

3

1

2

4

Oponal Horizontal Low Leak  

Oponal Economizer 

Oponal Economizer 

Oponal Return Air Smoke Detector

Oponal Power Exhaust 

Содержание Precedent FIADMPR102 Series

Страница 1: ...0 W D GS 150 300 SAFETY WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can b...

Страница 2: ...hat is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appl...

Страница 3: ...cies those regulations supersede these policies Non Trane personnel should always follow local regulations Introduction ACC SVN231A EN 3 Copyright This document and the information in it are the prope...

Страница 4: ...PR102 6 Factory Installed Damper Set Up 7 Downflow Configuration 7 General Information FIADMPR103 8 Inspection 8 Parts List 8 Installation FIADMPR103 9 Field Installed Damper 9 Factory Installed Dampe...

Страница 5: ...rted within 15 days 4 If concealed damage is discovered stop unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must pr...

Страница 6: ...around the channel in the cabinet post Then pivot the damper into the opening in the cabinet Refer to Figure 2 p 6 3 Once the damper is in place lift the damper and panel assembly to align the upper t...

Страница 7: ...ntly energized Verify that no power is present with a voltmeter 1 Remove filter access panel 2 Remove bottom blockoff from its shipping location See Figure 4 p 7 Figure 4 Remove bottom blockoff 3 Remo...

Страница 8: ...ed damage must be reported within 15 days 4 If concealed damage is discovered stop unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if poss...

Страница 9: ...r lockout tagout procedures to ensure the power cannot be inadvertently energized Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged 2 Remove unit end panel r...

Страница 10: ...d panel See Figure 6 p 10 Lay blockoff angle aside for later installation Figure 6 Remove lower screws 3 Do not remove the screws in the upper row of the end panel 4 Grasp the bottom of the end panel...

Страница 11: ...assembly is in its operating position a Holding the blockoff angle with the holes at the bottom and the bottom angle outward tilt the top forward and insert it into the opening between the economizer...

Страница 12: ...g for the required ventilation air use the Symbio service and installation mobile app or Symbio 700 on board UI to adjust the economizer minimum position setpoint BAS in the fresh return air settings...

Страница 13: ...bus Common 1 2 3 24 VAC OUT Common IMC IMC 1 2 3 4 IMC Bus White P5 White BK R BL O 24 VAC OUT Common IMC IMC 1 2 3 4 TO UC P4 SHEET 3 1 2 3 4 Common Spare Universal IO 1 Alt 5 VDC OUT Common 5 VDC OU...

Страница 14: ...Notes 14 ACC SVN231A EN...

Страница 15: ...Notes ACC SVN231A EN 15...

Страница 16: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Отзывы:

Похожие инструкции для Precedent FIADMPR102 Series