![Trane PM014 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/trane/pm014/pm014_installation-operation-and-maintenance-manual_1149782015.webp)
BAS-SVX33F-EN
15
Installing the Power Supply Module
Separating the IMC Bus for Large Systems
For large systems with heavier loads than the PM014 can power alone, the IMC bus can be
separated into sections that are sized for single power supply modules. Follow the recommended
method described below to separate the IMC bus. An alternative method is also described on
.
Note: The power supply module is not designed to supply power in parallel with other power
supplies.
Recommended method for separating the IMC bus
Note: This method preserves the power supply module warranty.
3. Perform lockout/tagout procedures for line voltage power to the cabinet.
4. Using two parallel DIN rails, position two power supply modules directly above or beneath one
another as shown in
5. Wire the two power supply modules together by using the IMC terminal blocks. Do not wire the
Vdc terminals.
Important:
To prevent power flow between modules, the Vdc terminals must not be wired.
Figure 7.
Recommended method when separating the IMC bus
PM014
PM014
24
VAC
XFMR
OUT
24
VAC
24
VAC
XFMR
OUT
24
VAC
24 Vdc
terminal
24 Vdc
terminal
Содержание PM014
Страница 19: ......