Operation
43
BAS-SVX08D-E4
Table 16 - Data Point List for Rooftops, UCP2/UCP3 and Reliatel controllers
Data
Type
Offset
Point Description
Function
Modbus
Index
00001
0
ICS Diagnostic Reset (1 = Yes 0 = No)
bit
00002
1
Factory Test (*** Factory Use Only ***) (1 = Yes 0 = No)
bit
00003
2
ICS Slave Mode Requested (1 = Yes 0 = No)
bit
00004
3
Unit Control Source (1 = ICS 0 = Local)
bit
00005
4
Supply Fan Mode (1 = On (Continuous) 0 = Auto)
bit
00006
5
Econ Drive Open (1 = Drive Open 0 = Auto)
bit
00007
6
Econ Drive Closed (1 = Drive Closed 0 = Auto)
bit
00008
7
Econ Drive to Min Pos (1 = Drive to Min Position 0 = Auto)
bit
Economizer Control (bits 00009 00010)
0 0 Economizer Disabled
00009-00010
8-9
0 1 Economizer Disabled
1 0 Use Local Economizer Enthalpy Request (AUTO)
1 1 Override Local Economizer Enthalpy Request (ENABLED)
bit
00011
10
ICS Manual Heat/Cool Override (1 = Manual 0 = Auto)
bit
00012
11
ICS Manual Override Selection (1 = Cool 0 = Heat)
bit
00013
12
ICS Unit Stop Request (1 = Off 0 = Auto)
bit
00014
13
Supply Air Tempering Request (1 = Enable 0 = Disable)
bit
00015
14
Emergency Heat Mode Req (Heat Pump Only) (1 = Em Heat 0 = Auto)
bit
00016
15
Emergency Stop Request (1 = Yes 0 = No)
bit
00017
16
Auxiliary Heat Lockout (1 = Not Locked Out 0 = Lock Out)
bit
00018
17
Compressor Lockout (Lockout Both) (1 = Not Locked Out 0 = Lock Out)
bit
40001
0
Slave State Number ( 0 to 10 and 12)
None
40002
1
Economizer Damper Minimum Position ( 0 to 50 %)
Percentage
40003
2
ICS Zone Cooling Setpoint
Temperature
40004
3
ICS Zone Heating Setpoint
Temperature
40005
4
Number of Cooling Stages to be Enabled ( 0 to 3 )
None
40006
5
Number of Heating Stages to be Enabled ( 0 to 3 )
None
Bit 0 Econ Drive to Min Pos (1 = Drive to Min Position 0 = Auto)
Bit 1 Econ Drive Closed (1 = Drive Closed 0 = Auto)
Bit 2 Econ Drive Open (1 = Drive Open 0 = Auto)
40007
6
Bit 3 Supply Fan Mode (1 = On (Continuous) 0 = Auto)
Bit 4 Unit Control Source (1 = ICS 0 = Local)
Bit 5 ICS Slave Mode Requested (1 = Yes 0 = No)
Bit 6 Factory Test (*** Factory Use Only ***) (1 = Yes 0 = No)
Bit 7 ICS Diagnostic Reset (1 = Yes 0 = No)
bitfield
Bit 0 Emergency Stop Request (1 = Yes 0 = No)
Bit 1 Emergency Heat Mode Req (Heat Pump Only) (1 = Em Heat 0 = Auto)
Bit 2 Supply Air Tempering Request (1 = Enable 0 = Disable)
Bit 3 ICS Unit Stop Request (1 = Off 0 = Auto)
Bit 4 ICS Manual Override Selection (1 = Cool 0 = Heat)
40008
7
Bit 5 ICS Manual Heat/Cool Override (1 = Manual 0 = Auto)
Bit 6, 7 Economizer Control (bits 7 6)
0 0 Economizer Disabled
0 1 Economizer Disabled
1 0 Use Local Economizer Enthalpy Request (AUTO)
1 1 Override Local Economizer Enthalpy Request (ENABLED)
bitfield
Binary
Outputs
5/15
Analog
Outputs
6/16
Unit