Figure 34.
Flashing installation location
Detail A
Base rail
.060 gap between
bottom of panel and
top of flashing
Lower panel
Upper panel
(4) Screw:
10-16 x 0.750
self-driller
(9) Guard: Perpendicular-
to-airflow flashing
or
(12) Guard: Direction-
of-airflow flashing
(8) Tape:
0.12T x 1.00W
gray Butyl
Figure 35.
Flashing for corner seams
Assembled view
Detail C
Apply caulk
(14) Adhesive/sealant:
Flex polyurethane
(12) Guard:
Direction-of-
airflow flashing
(4) Screw:
10-16 x 0.750
self-driller
(9) Guard:
Perpendicular-to-
airflow flashing
(8) Tape:
0.12T x 1.00W
gray Butyl
Figure 36.
Flashing seam cover installation
Detail D
(4) Screw:
10-16 x 0.750
self-driller
(13) Guard:
Flashing seam cover
Note: Install flashing seam
cover on all flashing seams
(4) Screw:
10-16 x 0.750
self-driller
(13) Guard:
Flashing seam cover
Installation - Mechanical
28
CLCH-SVX013B-EN
Flashing Installation for Stacked Unit With
Second Level Shorter Than First
1. Ensure that first level roof section is properly sealed
with Butyl tape (item 8) and/or caulk (Item 14) at the
ends. See
Figure 37.
Seal first level with caulk or Butyl tape
Confirm Butyl
tape or caulk fills
area between roof
and second level unit.
2. Bend end tabs by hand and apply Butyl tape (Item 8) to
flashing. See
Figure 38.
Bend end tabs and apply Butyl tape to
flashing.
3. Secure to base rail with screws (Item 4).
4. Apply caulk (Item 14) to ensure a water tight seal. See