background image

Auxiliary

  drain  line  should  be  run  to  a  place  where  it  will  be 

noticeable  if  it  becomes  operational.  Homeowner  should  be 
warned  that  a  problem 

exists 

  if  water  should    begin  running 

from the 

auxiliary 

drain line. 

Plug the unused drain connection with the plugs provided in the 
parts  bag,  using a  thin  layer  of  teflon  paste,  silicone or  teflon 
tape to form a water tight seal. 

Test  condensate  drain  pan  and  drain  line  after  installation  is 
complete. Pour water into drain pan, enough to fill drain trap and 
line. Check to make sure drain pan is draining completely, no 
leaks are found in drain line fittings, and water is draining from 
the termination of the primary drain line.

Be  sure  to  insulate  the   drain  piping  and  drain  socket  since 

condensation may cause water leakage.

Be sure to install a drain trap at the drain outlet since the inside 
of  the  unit  is  at  negative  pressure  relative  to  atmospheric 
pressure during operation.

13

8.

 

AIR FILTER (not factory-installed)

External 

filter

 or other means of 

filtration

 is required. Units should be 

sized for a 

maximum 

of 300 feet/min air velocity or what is recomm- 

ended for the type filter installed.

Filter application and placement are critical to airflow, which may affect 
the  heating  and  cooling  system  performance.  Reduced  airflow  can 
shorten  the  life  of  the  system’s  major  components,  such  as  motor, 
limits,  elements,  heat  relays,  evaporator  coil  or  compressor. 
Consequently,  we  recommend that  the  return  air  duct  system  have 
only  one  filter  location.  For  systems  with  a  return  air  filter  grill  or 
multiple filter grills, can have a filter installed at each of the return air 
openings.

If adding high efficiency filters or electronic air filtration systems, it is 
very important that the air flow is not reduced. If air flow is reduced the 
overall  performance  and  efficiency  of  the  unit  will  be  reduced.  It  is 
strongly  recommended  that  a  professional  installation  technician  is 
contacted to ensure installation of these such filtration systems  are 
installed correctly.

IMPORTANT: 

Do not double filter the return air duct system. Do not 

filter the supply air duct system. This will change the performance of 
the unit and reduce airflow .

7.1 CONDENSATE DRAIN TUBING

Consult local codes for specific requirements. 

IMPORTANT: 

1. When making drain fitting connections to the drain pan, use a thin
layer of Teflon paste, silicone or Teflon tape and install, hand tighten.
2. When  making  drain  fitting  connections  to  drain  pan,  do  not
overtighten. Over tightening fittings can split pipe connections on the
drain pan.

Install drain lines so they do not block service access to front of 
the unit. Minimum clearance of 24 inches is required for filter, coil 
or blower removal and service access. 

Make  sure  unit  is  level  or  pitched  slightly  toward  primary  drain 
connection so that water will drain completely from the pan. (See 
Fig.11) 

Do not reduce drain line size less than connection size provided 
on condensate drain pan. Use 3/4

PVC piping for drain piping 

connections. 

All drain lines must be pitched downward away from the unit a 
minimum of 1/8

per foot of line to ensure proper drainage. 

Do not connect condensate drain line to a closed or open sewer 
pipe.  Run  condensate  to  an  open  drain  or  run  line  to  a  safe 
outdoor area. 

The drain line should be insulated where necessary to prevent 
sweating and damage due to condensate forming on the outside 
surface of the line. 

Make  provisions  for  disconnecting  and  cleaning  of  the  primary 
drain line should it become necessary. Install a 3 inch trap in the 
primary drain line as close to the unit as possible. Make sure that 
the top of the trap is below connection to the drain pan to allow 
complete drainage of pan (See Fig. 11). 

Fig.11 CONDENSATE DRAIN TRAP

CONDENSATE DRAIN TRAP

DO NOT OVERTIGHTEN DRAIN FITTING

TOWARD DRAIN CONNECTION 

UNIT MUST BE SLIGHTLY INCLINED 

3"

3"3"

UNIT

TO APPROVED DRAIN

DO NOT OPERATE UNIT WITHOUT 

CONDENSATE DRAIN TRAP.

Содержание OXBOX J4AH4P Series

Страница 1: ...Failure to follow these instruction may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death RECOGNIZ...

Страница 2: ......

Страница 3: ...orizontal left or downflow Multiple electrical entry locations Field installed electric heater kits 5 7 5 10 15 20 kW available as an accessory Dual front panel design for ease of maintenance Blower a...

Страница 4: ...e possibly resulting in fire electrical shock property damage personal injury or death The unit must be permanently grounded Failure to do so can result in electrical shock causing personal injury or...

Страница 5: ...t desired applications Top and side power and control wiring accessible screw terminals for control wiring all combine to make the installation easy and minimize installation cost See Fig 6 CAUTION Ma...

Страница 6: ...ts inside the installation space opening Respectively condensation may form on the surface of the insulation Be sure to use insulation that is designed for use with HVAC Systems Condensation may form...

Страница 7: ...LOW UNIT SHOWN UNIT MAY BE INSTALLED UPFLOW DOWNFLOW HORIZONTAL RIGHT OR LEFT AIR SUPPLY Fig 6 DIMENSIONS NOTE 25 CLEARANCE IS REQUIRED IN THE FRONT OF THE UNIT FOR FILTER AND COIL MAINTENANCE SUPPLY...

Страница 8: ...breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit breaker into location in opening Repeat above operation for remaining breaker s if more th...

Страница 9: ...DOWNFLOW STRAPS REAR WATER CATCHER TOP AIR STOP DRAIN CONNECTION DRAIN CONNECTION FRONT WATER CATCHER STRAPS THIS SYSTEM IS CHARGED WITH NITROGEN BEFORE SHIPMENT 42K 48K 60K 36K 30K 24k 18K A 1 4 A RA...

Страница 10: ...ng metal conduit when installed in accordance with electrical codes to the unit cabinet Grounding may also be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compar...

Страница 11: ...240 208 5 7 5 10 5 7 5 10 15 5 7 5 10 5 7 5 10 5 7 5 10 15 20 15 20 15 20 60 18 30 36 42 MIN Circuit Ampacity MAX Fuse or Breaker HACR Ampacity Heat Kit Model Air Handler Model kW Electric Heat 5 7 5...

Страница 12: ...rrent A CFM 999 953 905 847 757 681 610 543 411 Watts 316 310 306 302 288 279 270 256 240 Current A 1 38 1 36 1 34 1 32 1 28 1 24 1 21 1 16 1 10 CFM 1176 1127 1086 1028 944 842 746 668 569 Watts 342 3...

Страница 13: ...r should use only industry recognized procedures Heat pump systems require a specified airflow for electric heat operating Each ton of cooling requires between 350 and 450 cubic feet of air per minute...

Страница 14: ...return ductwork grills special filters accessories etc are accounted for in total resistance See airflow performance tables in this manual Design the duct system in accordance with ACCA Manual D Desig...

Страница 15: ...ecommended that a professional installation technician is contacted to ensure installation of these such filtration systems are installed correctly IMPORTANT Do not double filter the return air duct s...

Страница 16: ...FILTER RAILS FILTER COVER MANUAL BOLT 9 FILTER INSTALLATION DIMENSIONS AIR FILTER REMOVAL DIMENSIONAL DATA 18 24 16 8 426 20 4 518 1 25 4 19 6 14 8 30 36 18 3 466 21 6 548 1 25 4 20 8 16 3 42 48 60 20...

Страница 17: ...OR HP SYSTEMS RED GREEN 24RC G Fan Y1 Comp W1 B THERMOSTAT INDOOR UNIT OUTDOOR UNIT G R C Y C BLACK YELLOW BLACK RED GREEN W2 G Fan Y1 Comp W1 B THERMOSTAT INDOOR UNIT OUTDOOR UNIT G R C C B BLACK YEL...

Страница 18: ...d blue wire and connect with FAN terminal while medium speed red wire connect with M1 terminal CAPACITANCE CN7 CN8 CN4 CN1 CN11 M1 CN3 LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED OPTIONAL LOW FACTOR...

Страница 19: ...D FL BLUE 4 1 3 2 CB2 30A W2 L1 L2 L1 L2 LS ELEMENTS 0 C 1 4 8 2 6 RELAY2 POWER RED RED BLACK FL FL BLUE BLUE 4 1 3 2 CB1 60A W1 WHITE L1 L2 L1 L2 BLUE RED LS LS ELEMENTS ELEMENTS BROWN BLACK 1 2 3 4...

Страница 20: ...combination Use Table 3 for TXV kit part numbers A TXV may be required to achieve minimum efficiency ratings or for long refrigerant line set applications Reference AHRI for system combination rating...

Страница 21: ...5 105 26 19 11 6 5 5 100 27 21 13 7 6 5 95 29 23 14 9 6 5 90 30 25 18 12 7 5 85 32 26 20 15 9 6 80 34 28 22 17 11 6 75 35 30 24 19 13 7 70 37 32 26 21 16 10 65 38 34 29 24 19 13 60 40 36 31 27 22 17 5...

Страница 22: ......

Отзывы: