background image

12

SS-APG008H-EN

Expansion Valves

Expansion valves meter refrigerant into the evaporator
under controlled conditions. If there is too much refrigerant,
the refrigerant will not completely vaporize and the
remaining liquid will slug the compressor. If there is too little
refrigerant, the system won’t make capacity and there may
not be enough cooling for the compressor.

Note:

Expansion valves are pre-installed on the TWE

product and the superheat has been set properly.

When using air handling units beside the TWE,

Table 4, p.

26

lists expansion valves. Each evaporator distributor

requires a dedicated expansion valve in order to maintain
proper coil distribution. The expansion valve should be
selected to match the capacity of the coil that the distributor
feeds.

Example 1: 10-ton coil (one refrigerant circuit) with two
equal distributors

10 / 2 = 5

Each TXV should be selected for 5 tons. However, care
should be taken to ensure the condensing unit is capable of
operating at these conditions.

Example 2: 10-ton coil (one refrigerant circuit) with two
distributors and a 60/40 coil split

10 x .6 = 6 and 10 x .4 = 4

One TXV should be sized for 6 tons, and one TXV should
be sized for 4 tons. However, care should be taken to
ensure the condensing unit is capable of operating at these
conditions.

If the coil or distributors have a difference of only one circuit
tube, the difference should be ignored.

The proper balance for feeding refrigerant for a TTA/TWA
system is to provide 18°F of superheat— the difference
between the saturated and actual refrigerant temperature
leaving the evaporator. Expansion valve superheat is
preset from the factory, but it isn’t set to 18°F. Use the turns
listed in

Table 1, p. 12

to adjust them to the correct 18°F

superheat.

Table 1.

Expansion valves

Sporlan

Standard off-the-shelf nominal valve settings (90 PSIG air test setting)

Field adjust for 18°F

Valve

Superheat, °F

CW turns available

CCW turns available

Superheat change per turn

ERZE

(a)

or RCZE

12

4.5

4.5

2.4°F

2 1/2 CW

OZE

3.4°F

1 3/4 CW

(a)

May also be called BBIZE

Содержание Odyssey TTA0724 A Series

Страница 1: ...person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment June 2022...

Страница 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Страница 3: ...itutes or refrigerant additives WARNING Explosion Hazard Failure to follow instructions below could result in an explosion which could result in death or serious injury and equipment damage NEVER bypa...

Страница 4: ...g Routing and Component Selection 9 Liquid Lines 9 Line Sizing 9 Routing 9 Insulation 9 Components 9 Gas Line 10 Line Sizing 10 Routing 10 Insulation 11 Components 11 Expansion Valves 12 Controls 13 H...

Страница 5: ...r the evaporator inlet Operational problems can occur if these refrigerant lines are designed or installed improperly Figure 1 Interconnecting refrigerant lines in a typical split air conditioning sys...

Страница 6: ...equation based formulas to predict the entrainment velocities of R 410A refrigerant and POE oil These minimum velocities are reflected in the line sizes listed in the component selection summary table...

Страница 7: ...contact the manufacturer for review Figure 3 Allowable elevation difference TWA above indoor unit Not allowed for TWA units Note Regardless of orientation hot gas bypass HGBP lines are limited to 75...

Страница 8: ...nits Note Route refrigerant piping for minimum linear length minimum number of bends and fittings Important Read Application Guide SS APG008 EN thoroughly before installing this unit Note All liquid p...

Страница 9: ...or positioning the components in the liquid line Position the components as close to the indoor unit as possible The Component Selection tables found in Parts p 25 identify suitable components by part...

Страница 10: ...th Refrigerant Line Failure to follow instructions could cause a refrigerant line to explode under pressure which could result in death or serious injury Liquid refrigerant trapped between two valves...

Страница 11: ...promotes stable TXV operation Avoid Underground Refrigerant Lines Underground lines create risk due to refrigerant condensation during the off cycle installation debris inside the line including conde...

Страница 12: ...nsure the condensing unit is capable of operating at these conditions Example 2 10 ton coil one refrigerant circuit with two distributors and a 60 40 coil split 10 x 6 6 and 10 x 4 4 One TXV should be...

Страница 13: ...to the third party Simply stated this means that when a compressor turns on it shouldn t turn off until the expansion valve comes under control And once the compressor turns off it should be allowed...

Страница 14: ...g applications To prevent evaporator freeze up our equipment typically includes Trane Frostat coil frost protection Like hot gas bypass the Frostat system protects the coil from freezing but it does s...

Страница 15: ...OD and smaller of type L copper are suitable for use with R 410A Suction lines 3 1 8 OD must use type K or thicker wall Discharge lines liquid lines heat pump vapor lines and hot gas bypass lines 1 3...

Страница 16: ...enters the coil quickly turns to liquid The MCHE tube volume holds very little refrigerant so the refrigerant charge of the system is reduced However the tube volume is so small that if the flow of re...

Страница 17: ...are a field installed option and no longer come standard from the factory Figure 8 TTA cooling only unit and matched indoor coil typical arrangement Notes 1 If the total length of the liquid line exce...

Страница 18: ...1 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liquid line filter driers from the TWA heat pump and install new f...

Страница 19: ...and one check valve See Table 3 p 26 and for recommendations 2 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liqui...

Страница 20: ...s away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction heade...

Страница 21: ...10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction header conditions See Line Sizing Routi...

Страница 22: ...xpansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is...

Страница 23: ...e for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when...

Страница 24: ...m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction header conditions See Line Sizing Routing and Component Se...

Страница 25: ...Unit TTA1804 D TTA1804 C TTA2404 D TTA2404 C TTA3004 C Refrigerant ckts 2 1 Manifold 2 1 Manifold 1 Manifold Minimum step tons 7 5 8 6 13 4 10 12 5 GAS LINE Tube diameter in Horizontal drops 1 1 8 1...

Страница 26: ...products require two filters and two check valves one set oriented for liquid in the cooling direction and one set oriented for liquid in the heating direction For units with line lengths in excess o...

Страница 27: ...urated at 90 F Discharge Saturated at 125 F Note When calculating refrigerant charge the first step is to determine the unit charge and if the unit charge includes the first 25 foot of pipe This infor...

Страница 28: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications...

Отзывы: