User Settings allow the user to customize various settings on the XR724 control.  To access User Settings simply press 

the Menu button once and “User Settings” will be displayed.  To enter the User Settings menu, press the Select button, 

then use the Next button to navigate through the options below.  The default setting will be shown in brackets.  After 

each selection press the Done button to save changes. Certain menu selections, which are marked by an asterisk ( * ), 

may or may not be present depending on other menu settings.

The following is a guide of the menu options available by pressing the Menu button. Certain menu selections, which 

are marked by an asterisk ( * ), may or may not be present depending on other menu settings.

* Only appears as a menu item if Dehumidify is set to Yes, Aux Relay is set to Dehumidifier, or Aux Relay is set to 

Humidity.

USER SETTINGS

HUMIDITY *

MENU OPTIONS

HUMIDITY

Setting

Range

Description

Cooling RH Target*

30% to 60% [50%]

Select the desired indoor relative humidity during cooling mode. Dehu-

midification must be enabled in the Installer Settings for this option to be 

available.

Heating RH Target*

10% to 45%  [40%]

Select the desired indoor relative humidity during heating mode.  

Humidification must be enabled in the Installer Settings for this option to 

be available.

Once all selections have been made, press the 

Done button to exit and return to menu. Press Next to navigate to the next setting.

THERMOSTAT

Setting

Range / Sub Setting

Description / Range of Sub Settings

Temperature Scale

[Fahrenheit], Celsius

Select the temperature display scale

Max Heat Setpoint

55 - [90] Degrees

Select the highest heating setpoint allowed

Min Cooling Setpoint

[60] - 99 Degrees

Select the lowest cooling setpoint allowed

Time/Date*

Set Hour

1 - 12 AM, 1 - 12 PM [12PM]

Set Minutes

0 - 59 [0]

Day of Week

[Sun], Mon, Tue, Wed, Thr, Fri, Sat

Year 

[2013] - 2113

Month

[Jan], Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec

Date

[1] - 31

DST Enable

[Yes], No

Continuous Fan Airflow*

35% - 100% [50%]

Select the desired fan speed when the Fan Mode selected is Continuous 

(variable speed blower required). Only available if ID Fan Type = Variable.

Fan Circulate On Time

[10] - 55 minutes

Select the desired amount of time the fan will cycle per hour when the Fan 

Mode selected is Circ

Once all selections have been made, press the 

Done button to exit and return to menu. Press Next to navigate to the next setting.  

XR724 USER GUIDE

If connected with Nexia, 

then time and date are 

provided by the network

Содержание NEXIA XR724

Страница 1: ...Instructions 18 HD82D1 1B EN Contents User Guide Features 2 Operation 3 User settings 4 Schedules 5 Display settings 5 Sensor settings 5 WiFi settings 6 Nexia settings 6 Installer settings 7 Test Mod...

Страница 2: ...pecifications XR724 Features Specification Description Product Model TCONT724AS42DAA Product XR724 HVAC System comfort control WiFi communications enabled Size 5 75 wide x 3 5 height x 1 depth Display...

Страница 3: ...screen The current mode is displayed at the top of the screen Adjust the setpoint by pressing the up or down arrows To change setpoint mode press the MODE button The setpoints will push each other if...

Страница 4: ...H Target 10 to 45 40 Select the desired indoor relative humidity during heating mode Humidification must be enabled in the Installer Settings for this option to be available Once all selections have b...

Страница 5: ...have been made press the Done button to exit and return to menu Press Next to navigate to the next setting USER SETTINGS continued SCHEDULES Setting Range Sub Settings Description Range of Sub Settin...

Страница 6: ...tries Retries X Number of connection retries Connection Time Disconnected OR X hours Connection hours RSSI RSSI xx DBM Connection signal strength Once all selections have been made press the Done butt...

Страница 7: ...5 90 Sec in 5 sec increments Off Delay Cooling 0 5 90 Sec in 5 sec increments On Delay Heating 0 5 90 Sec in 5 sec increments Off Delay Heating 0 5 90 Sec in 5 sec increments Fan type Variable On Dela...

Страница 8: ...type setting HP only Once all selections have been made press the Done button to exit and return to menu Press Next to navigate to the next setting RESTORE DEFAULTS Setting Action Description Restore...

Страница 9: ...F 0 5 0 1 0 Heating HP Normal Less Aggressive More Aggressive Comp Heat Delta Stage 1 ON 0 5 1 0 5 Comp Heat Delta Stage 2 ON 1 5 2 1 0 Indoor Heat Delta Stage 1 ON 2 5 3 1 5 Indoor Heat Delta Stage 2...

Страница 10: ...the Nexia mobile app to enroll into Nexia To enroll download the Nexia app from the Google Play Store or App Store then launch the app Once in the app click Connect New Device select 724 thermostat t...

Страница 11: ...1B EN XR724 NEXIA Enrollment continued XR724 USER GUIDE Even though open networks no password and WEP WiFi encryption are supported it is recommended to use a more secure network encryption such as W...

Страница 12: ...12 18 HD82D1 1B EN XR724 NEXIA Enrollment continued XR724 USER GUIDE...

Страница 13: ...13 18 HD82D1 1B EN XR724 Nexia WiFi Reconfiguration XR724 NEXIA Enrollment continued PRESS PRESS XR724 USER GUIDE...

Страница 14: ...14 18 HD82D1 1B EN XR724 Nexia WiFi Reconfiguration continued XR724 USER GUIDE...

Страница 15: ...15 18 HD82D1 1B EN XR724 Nexia WiFi Reconfiguration continued XR724 USER GUIDE...

Страница 16: ...16 18 HD82D1 1B EN XR724 Nexia WiFi Reconfiguration continued XR724 USER GUIDE...

Страница 17: ...17 18 HD82D1 1B EN XR724 Nexia WiFi Reconfiguration continued XR724 USER GUIDE...

Страница 18: ...nsiderations The XR724 Control is designed for installation in climate controlled living spaces It is recommended to place the unit in central locations with good circulation Avoid exterior walls and...

Страница 19: ...wall plate to wall using two screws provided Do not overtighten AU X C J2 AU X NC C R W1 W2 O B G BK J2 J1 RS RS OD T OD T AU X NO Y1 Y2 J1 AUX C J2 AUX NC C R W1 W2 O B G BK J2 J1 RS RS ODT ODT AUX...

Страница 20: ...R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 YO VS Air Handler Electric Heat One or Two Stage Cooling Only Note 1 Note 2 Note 2 Note 3 Note 5 Note 4 Fie...

Страница 21: ...on Outdoor Sensor Remote Sensor W3 Non VS Air Handler Electric Heat One Stage Cooling Only Note 1 Note 2 O Non VS Air Handler Electric Heat Heat Cool Diagram 4 2 Stage Cooling w GAM5B Model Air Handle...

Страница 22: ...In R B C Y B Notes 1 YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly 2 If third party condensate overflow switche...

Страница 23: ...W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 Non VS Air Handler Electric Heat Heat Cool Diagram 8 1 Stage Cooling w TEM3 Model Air Handler G W1 R B C W2 One...

Страница 24: ...iring to avoid interference Remote Temperature Sensor Connections and Operation Note 1 Note 4 Note 3 Aux relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sens...

Страница 25: ...gram 12 1 or 2 Stage Cooling w Variable Speed Gas Furnace G W1 Y1 R B C Y2 BK W2 One or Two stage Cooling Only Y1 R B Y2 Notes 1 Cut remove the factory installed BK jumper at the indoor unit 2 Y2 R co...

Страница 26: ...14 1 or 2 Stage Cooling w Variable Speed Oil Furnace G W1 Y1 R B C Y2 BK W2 One or Two Stage Cooling Only Y1 R B Y2 Notes 1 Cut remove the factory installed BK jumper at the indoor unit 2 Y2 R connect...

Страница 27: ...un sensor wires in the same bundle with HVAC wires Keep away from high voltage wiring to avoid interference Remote Temperature Sensor Connections and Operation Note 1 Note 2 Package Unit G W Y R B C A...

Страница 28: ...Thermostat Connection Outdoor Sensor Remote Sensor O W3 X2 O YO Variable Speed Air Handler Electric Heat One or Two stage Heat Pump Note 2 Note 3 Note 4 Note 1 Variable Speed Air Handler Electric Hea...

Страница 29: ...2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O W3 X2 O Note 1 Note 2 Non VS Air Handler Electric Heat Heat Pump Diagram 4 2 Stage Heat Pump w GAM5B Model Air Handler...

Страница 30: ...ram 6 1 Stage Heat Pump w GAF2 36M Model Air Handler G W1 YI R B C Y One stage Heat Pump Y R B Notes 1 YI and YO connections must be made as shown for freeze protection and internally mounted condensa...

Страница 31: ...C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 X2 O Note 1 Non VS Air Handler Electric Heat Heat Pump Diagram 8 1 Stage Heat Pump w TEM3 Model Air H...

Страница 32: ...sor Connections and Operation Aux relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O W3 X2 O Note 2 Note 3 Note 1 Air Handler Electric He...

Страница 33: ...run sensor wires in the same bundle with HVAC wires Keep away from high voltage wiring to avoid interference Remote Temperature Sensor Connections and Operation X2 Note 1 Note 2 Package Unit G W1 Y R...

Страница 34: ...Temperature Sensor Connections and Operation Aux relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O O X2 Note 1 Note 2 Note 3 Non VS One...

Страница 35: ...x relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O X2 O T T R1 Oil Burner Primary R1 Note 2 Note 1 Note 3 Note 4 Note 4 Non Variable Sp...

Страница 36: ...in the same bundle with HVAC wires Keep away from high voltage wiring to avoid interference Remote Temperature Sensor Connections and Operation X2 Note 2 Note 1 Note 3 Package Unit G W1 Y R B C W2 Aux...

Страница 37: ...a separate cable from the Comfort Control cable IMPORTANT Follow directions below for averaging These instructions replace the averaging information found in the Installer s Guide for the ZZSENSAL0400...

Страница 38: ...tings Comfort Settings Menu Cooling will not come on 1 System mode is not set to Cool Auto or setpoint is set too high 2 Delta On for cooling is set too high 3 Minimum off time delay is being enforced...

Страница 39: ...couraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the e...

Страница 40: ...rature Order Number 18 HD82D1 1B EN File number 18 HD82D1 1B EN Supersedes New Date 08 30 19 Trane has a policy of continuous product and product data improvement and it reserves the right to change d...

Отзывы: