![Trane LonWorks TR200 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/trane/lonworks-tr200/lonworks-tr200_instruction-manual_1150281057.webp)
not change but the adjustable frequency drive will trip and display: Alarm
67
Option Changed
.
[0]
None
[1]
FC RS-485
[2]
FC USB
[3] *
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30]
External Can
This parameter cannot be adjusted while the motor is running.
8-03 Control Timeout Time
Range:
Function:
60.0 s*
[1.0 - 18000.0 s]
Enter the maximum time expected to pass between the reception of two
consecutive messages. If this time is exceeded, it indicates that the serial
communication has stopped. The function selected in par.8-04
Control Timeout Function
will then be carried out.
In LonWorks, the following variables will trigger the Control Word Time
parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-04 Control Timeout Function
Option:
Function:
Select the timeout function. The timeout function is activated when the
control word fails to be updated within the time period specified in par.
8-03
. Choice [20] only appears after setting the
Metasys N2 protocol.
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override Release
Parameters
8-2
TR200 LonWorks
Содержание LonWorks TR200
Страница 9: ...Copyright 2 2 TR200 LonWorks...
Страница 13: ...Introduction 3 4 TR200 LonWorks...
Страница 21: ...How to install 4 8 TR200 LonWorks...
Страница 45: ...Configuration of the system 5 24 TR200 LonWorks...
Страница 51: ...How to Control the Adjustable Frequency Drive 6 6 TR200 LonWorks...