Table 33.
Electrical service sizing data—motors — air-cooled and evaporative condensing
Nom Tons
No of Fans
460V
575V
380V
FLA
FLA
FLA
90-105 (AC)
6
16.2
13.2
15
120, 130, 150 (AC)
8
21.6
17.6
20
100 (EC)
2
11.8
N/A
N/A
118, 128, 140, 162 (EC)
2
11.8
N/A
N/A
Table 34.
Electrical service sizing data—supply,
exhaust/return fan motors — air-cooled and
evaporative condensing
Motor HP
460 V
575 V
380 V
FLA
FLA
FLA
Supply Fan Motors
15
18.0
15.0
22.0
20
24.7
19.5
28.0
25
30.5
24.8
34.0
30
36.6
29.0
41.0
40
49.0
39.0
54.0
50
59.0
47.2
68.0
60
71.0
57.0
81.0
75
88.0
70.0
103.0
100
115.0
92.0
N/A
Exhaust/Return Fan Motors
7.5
9.8
7.8
12.1
10
12.6
10.1
15.2
15
18.0
15.0
22.0
20
24.7
19.5
28.0
25
30.5
24.8
35.0
30
36.6
29.0
41.0
40
49.0
39.0
54.0
50
59.0
47.2
68.0
60
71.0
57.0
81.0
Table 35.
Electrical service sizing data—electric heat
module (electric heat units only)
Module kW
Voltage
460
575
380
FLA
FLA
FLA
90 / 56
108.3
86.6
85.1
140 / 88
168.4
134.7
133.7
265 / 166
318.8
255
252.2
300 / 188
360.8
288.7
285.6
Note:
Electric heat FLA are determined at 480, 600,
380 volts.
Table 36.
Electrical service sizing data—control
power transformer (heating mode only) —
air-cooled and evaporative condensing
Nom Tons AC/EC
Digit 2 Unit
Function
Voltage
460
575
380
FLA
FLA
FLA
90-150/100-162
E, L, S, X
3
3
4
90, 105/100, 118
F (850 mbh)
4
4
5
F (1100 mbh)
4
4
5
F (1800 mbh)
4
4
5
120-150/128-162
F (1100 mbh)
4
4
5
F (1800 mbh)
4
4
5
F (2500 mbh)
4
4
5
Table 37.
Electrical service sizing data—crankcase
heater — air-cooled and evaporative
condensing
Nom Tons
AC/EC
Voltage
460
575
380
FLA (add)
FLA(add)
FLA(add)
All
1
1
1
Table 38.
Voltage utilization range
Unit Voltage
Range
460/60/3
414-506
575/60/3
(a)
517-633
342-418
(a)
Units with air-cooled condensers only.