RT-SVX24Q-EN
159
Table 55.
Standard unit (no ERW) (economizer)
outside air damper travel adjustment/pressure drop
(
inches w.c.
) (continued)
25,000
0.37
0.45
0.69
0.92
1.24
23,000
0.31
0.37
0.57
0.76
1.04
Standard Unit with Energy Recovery
Wheel
Economizer Damper Adjustment - ERW units
Outside & Return Air Damper Operation
The outside air and return air damper actuators are
accessible through from the filter section of the unit.
The outside air and return air dampers have individual
actuators that are linked electronically. The actuators
are preset to 0 degrees from the factory. Refer to
“Table 46, p. 170,”
for the appropriate actuator position
for the unit and operating airflow (CFM).
To Adjust the Outside Air Damper Travel
1. Drill a 1/4" hole through the unit casing up stream
of the return air dampers and below the energy
recovery wheel. Use a location that will produce an
accurate reading with the least amount of
turbulence. Several locations may be necessary,
and average the reading.
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
IIm
mp
po
orrtta
an
ntt:: HIGH VOLTAGE IS PRESENT AT
TERMINAL BLOCK OR UNIT
DISCONNECT SWITCH.
2. Close the disconnect switch or circuit protector
switch that provides the supply power to the unit
terminal block or the unit mounted disconnect
switch.
3. Turn the 115 volt control circuit switch and the 24
volt control circuit switch to the “On” position.
4. Open the Human Interface access door, located in
the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer
to the latest edition of the applicable programming
manual for applications for the SERVICE TEST
screens and programming instructions.
5. Use to program the following system components
for operation by scrolling through the displays:
Supply Fan (On)
VFD Cmd (100%, if applicable)
RTM Occ/Unocc Output
(Unoccupied)
OA Damper Pos (0%)
Outside Air Bypass Damper Pos (0%)
Exhaust Air Bypass Damper Pos (0%)
6. Once the configuration for the components is
complete, press the NEXT key until the LCD
displays the “Start test in __Sec." screen. Press the
+ key to designate the delay before the test is to
start. This service test will begin after the TEST
START key is pressed and the delay designated in
this step has elapsed. Press the ENTER key to
confirm this choice.
W
WA
AR
RN
NIIN
NG
G
R
Ro
otta
attiin
ng
g C
Co
om
mp
po
on
ne
en
nttss!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n rro
otta
attiin
ng
g cco
om
mp
po
on
ne
en
nttss ccu
uttttiin
ng
g a
an
nd
d sslla
assh
hiin
ng
g
tte
ecch
hn
niicciia
an
n w
wh
hiicch
h cco
ou
ulld
d rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss
iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d..
7. Press the TEST START key to start the test.
Remember that the delay designated in step 6 must
elapse before the fan will begin to operate.
8. With the outside air dampers fully closed and the
supply fan operating at 100% airflow requirements,
measure the return static pressure at the location
determined in step 1.
9. Press the STOP key at the Human Interface Module
in the unit control panel to stop the fan operation.
10. Open the field supplied main power disconnect
switch upstream of the rooftop unit. Lock the
disconnect switch in the “Open” position while
working on the dampers.
11. Locate the static pressure reading in
“Table 46,
p. 170,”
and determine which damper needs to be
adjusted and the degree reading. Proceed to the
appropriate damper actuator procedure.
To Adjust the Outside Air Damper Actuators
1. Remove the shaft coupling from the damper shaft
by loosening the bolt and removing the retainer
clip. Be careful not to rotate the shaft.
2. Position the shaft coupling so that the indicator
points to the degree value obtained from
.
The shaft coupling is adjustable in 5 degree
increments.
3. Replace the retainer clip and tighten the shaft
coupling on the shaft (120-180 in-lbs).