Accessories

Options

Accessory Items

Water Regulating Valve Assembly

The water regulating valve assembly
consists of a direct acting valve and a
reverse acting valve installed on the
water-out side of the unit. The direct
acting valve opens in response to an
increase in discharge pressure during
the cooling cycle. The reverse acting
valve opens in response to a decrease in
suction pressure during the heating
cycle. Water regulating valves should be
used where low flow, and low or high
fluid temperature conditions could occur.
This option is beneficial with open loop
systems, but not necessary. 

See Figure

A-1 for water regulating valve assembly.

Motorized Water Valve for Open-Loop
Systems

The motorized water valve is installed on
the return line of the system between the
loop and the loop pump module. This
isolation device is less expensive and a
very effective alternative to the water
regulating valve.

When the compressor begins running,
the valve will open, allowing water to
flow through the unit. As the compressor
shuts down, the valve slowly closes off.
The main purpose of the motorized
valve is to shut off the flow of water
through the unit when the unit is off,
thus reducing water consumption. The
motorized valve must be fast opening to
prevent compressor trip-out, and slow
closing to prevent water-hammer.

Pump Module

The pump module and the hose kit make
a complete self-contained pumping
package for distributed pumping system.
These kits contain all the necessary
components for the installation,
operation and maintenance of the water
circuit of a closed loop geothermal
application. Standard pump module
features include insulated Grundfos
pumps, insulated cabinet, bronze pump,
and 3-way brass valves. The module is
factory piped, wired, and mounted. 

See

Figure A-2 for pump module assembly.
Literature number WSHPC-IN-5 (72-
9006-03) will provide electrical and
dimensional requirements for the PMCA
and PMBA products.

Hose Kits

The basic hose kit consists of a stainless
steel outer braid with an inner core or
tube made of a non-toxic synthetic
polymer. The couplings are designed
with solid male pipe thread at one end,
and a ground-joint cone seat swivel
female with a male adapter at the
opposite end. The hoses are suitable for
water temperatures ranging between
33 F and 211 F [.55 C and 99.4 C] without
the use of glycol.

Additional options can be provided to
accompany the hose kit design. These
kits consist of a manual shut off/
balancing device on the supply and
return, or a self balancing device. The
specialized hose kits can be ordered with
or without a strainer. 

See Figure A-3 for

the WSHP hose kit.

Figure A-2 – Pump Module Assembly

Figure A-1 – Water Regulating Valve

Assembly

See WSHP-SVX01A-EN for more
detailed specifications on hose kit
options. Hose kit options include:

 Circuit setter hose kit

 Manual balancing hose kit

 Automatic self-balancing hose kit

Figure A-3 – WSHP Hose Kit

Содержание GECA

Страница 1: ...Trane Axiom Water Source Comfort System Standard Efficiency Console Model GECA 50 Hz WSHP PRC004 EN February 2001...

Страница 2: ...vides both fundamental performance requirements exceptional quality and added features to enhance maintenance ability and sound attenuation The design offers Dual sloped plastic drain pan Hot gas rehe...

Страница 3: ...4 EN Introduction Model Number Description General Data Features and Benefits Performance Data Fan Sound Control Wiring Dimensional Data Accessories Mechanical Specifications Contents 2 4 5 6 24 42 43...

Страница 4: ...Status and Condensate Overflow Sensor DIGIT 20 TEMPERATURE SENSOR 0 No Additional Temperature Sensor 1 Entering Water Sensor 2 Return Air Mixed Air Temperature Sensor 3 Entering Water Mixed Air Temper...

Страница 5: ...x 779 1 x 7 3 4 x 30 5 8 25 4 x 197 x 779 Blower Wheel Size in mm 2 5 1 4 x 8 1 8 133 x 206 2 5 1 4 x 8 1 8 133 x 206 Table GD 2 Physical Data GECA 012 015 Model GECA 012 015 012 015 Unit Size Length...

Страница 6: ...ctrostatic powder paint coating in the following colors Deluxe beige Cameo white Soft dove Building Block Design The console configuration maintains a tri building block design It includes Cabinetry C...

Страница 7: ...condensate piping to the unit It also provides space for the high and low voltage connections See Figure FB 3 for right hand piping Left Hand Piping Console units ordered with a left hand piping conne...

Страница 8: ...be free from contaminants and conditions such as drilling fragments dirt or oil This reduces the possibility of these contaminants damaging the compressor motor Schrader Connections The connections f...

Страница 9: ...ering device This thermal expansion valve TXV allows the unit to operate with an entering fluid temperature from 25 F to 110 F 3 9 C to 43 3 C and entering air temperatures from 40 F to 90 F 4 4 C to...

Страница 10: ...y includes a colorless odorless adhesive to retain dirt particles within the filter media after fiber contact The filter is accessible through the return air portion of the unit subbase Panel removal...

Страница 11: ...it Acoustic lining has been used to quiet compressor noise The unit airside acoustic performance has been engineered to obtain the quietest acoustic performance through the fan and fan housing selecti...

Страница 12: ...bove 60 F 15 6 C the boilerless controller returns the unit to normal compressor heating operation and locks out the electric heater This option is ONLY available on heat pump units See Figure FB 22 f...

Страница 13: ...rating in the reheat mode the humidistat signals the reheat relay coil to energize allowing the high pressure refrigerant gas to flow from the compressor through the reversing valve into the reheat va...

Страница 14: ...27 for the console basic 24V control box 50 VA transformer Compressor contactor Compressor run capacitor General alarm 24 volt when a fault is detected Low pressure switch High pressure switch Lockout...

Страница 15: ...for 24V stand alone system controls Safety Devices All unit safety devices are provided to prevent compressor damage Low Pressure Switch The low pressure switch prevents compressor operation under low...

Страница 16: ...ure time delay Compressor delay on start Reversing valve coil for heating and cooling units only Optional Condensate overflow Optional Night setback Optional Hot gas reheat for dehumidification Option...

Страница 17: ...available as factory wired An external Class II 24VAC signal will energize the relay coil on terminals R1 and R2 Terminals C common NO normally open and NC normally closed will be provided for the re...

Страница 18: ...ompressor ON FLASH ON OFF Brownout Condition ON FLASH ON Soft Lockout low pressure ON FLASH FLASH Soft Lockout high pressure ON ON ON Manual Lockout low pressure ON ON FLASH Manual Lockout high pressu...

Страница 19: ...ndependently of one another with a mercury bulb or electronic digital thermostat With a multiple unit installation the units may be daisy chained directly to the Trane Tracer loop controller TLC pump...

Страница 20: ...ed unoccupied mode Fan and filter status Reversing valve coil for heating and cooling units only Two speed fan motor unit mounted fan speed switch 18 pole terminal strip for low voltage hook up Option...

Страница 21: ...limit and recommends unit maintenance as required Data Sharing The Tracer ZN 510 controller is capable of sending or receiving data set points fan request or space temperature to and from other contr...

Страница 22: ...to the controller Someone is pressing the service button or the controller has failed RED LED FLASHES once every second Restore the unit to normal operation with RoverTM GREEN LED ON continuously Powe...

Страница 23: ...uilding automation system or through Trane s Rover service tool This type of application would most commonly be used for a large space s that may require more than one unit In addition to this applica...

Страница 24: ...12 8 77 1 7 7 9 6 4 0 80 0 61 13 0 9 9 88 0 2 9 250 7 9 0 61 13 0 1 8 8 0 6 4 0 80 0 61 13 1 9 9 87 5 3 1 250 8 0 0 61 13 1 1 9 8 0 6 4 0 80 0 60 13 2 9 9 87 0 3 3 250 8 0 0 61 13 1 2 1 8 0 6 4 0 80 0...

Страница 25: ...31 1 88 0 80 0 61 13 0 2 90 31 1 8 7 425 2 31 0 61 13 0 0 11 2 34 1 88 0 80 0 61 13 1 2 90 30 8 9 3 425 2 34 0 61 13 1 0 12 2 34 1 88 0 80 0 60 13 2 2 90 30 6 9 9 425 2 34 0 61 13 1 0 13 2 34 1 88 0...

Страница 26: ...1 6 2 0 60 3 5 38 6 3 3 250 7 1 0 60 3 4 2 1 7 2 6 3 0 60 3 5 39 2 3 8 250 7 2 0 61 3 5 1 2 7 5 6 6 0 61 3 6 42 4 1 5 250 7 5 0 61 3 6 1 4 7 6 6 8 0 61 3 7 44 6 2 1 250 7 6 0 61 3 7 1 6 7 8 6 9 0 61 3...

Страница 27: ...9 9 425 2 08 0 60 3 4 0 13 2 11 1 85 0 60 3 5 4 0 11 4 425 2 11 0 61 3 5 0 08 2 20 1 93 0 61 3 6 5 8 4 5 425 2 20 0 61 3 6 0 09 2 23 1 99 0 61 3 7 7 0 6 3 425 2 23 0 61 3 7 0 10 2 29 2 02 0 61 3 7 7...

Страница 28: ...3 333 11 2 0 84 13 3 2 6 11 3 8 4 0 75 0 83 13 6 13 9 87 5 7 0 333 11 3 0 84 13 4 2 7 11 3 8 4 0 75 0 82 13 7 13 9 86 9 7 8 333 11 3 0 84 13 5 2 9 11 3 8 4 0 75 0 82 13 7 13 9 86 3 8 5 333 11 3 0 84 1...

Страница 29: ...3 31 2 46 0 75 0 83 13 6 4 07 30 8 21 0 565 3 31 0 84 13 4 0 17 3 31 2 46 0 75 0 82 13 7 4 07 30 5 23 4 565 3 31 0 84 13 5 0 18 3 31 2 46 0 75 0 82 13 7 4 07 30 2 25 5 565 3 31 0 84 13 5 0 09 3 14 2...

Страница 30: ...0 3 3 39 5 8 6 333 10 2 0 91 3 3 1 5 10 5 8 4 0 91 3 4 43 8 2 9 333 10 5 0 91 3 4 1 8 10 7 8 6 0 91 3 4 45 6 4 1 333 10 7 0 92 3 4 2 1 10 9 8 8 0 92 3 5 46 6 5 0 333 10 9 0 93 3 4 55 2 3 11 0 9 0 0 93...

Страница 31: ...9 2 37 0 90 3 3 4 2 25 8 565 2 99 0 91 3 3 0 09 3 08 2 46 0 91 3 4 6 6 8 7 565 3 08 0 91 3 4 0 11 3 14 2 52 0 91 3 4 7 6 12 3 565 3 14 0 92 3 4 0 13 3 19 2 58 0 92 3 5 8 1 15 0 565 3 19 0 93 3 4 12 8...

Страница 32: ...13 6 16 0 87 7 8 6 400 13 2 0 99 13 4 3 0 13 2 10 3 0 78 0 97 13 7 16 0 87 4 9 0 400 13 2 0 99 13 4 3 2 13 2 10 3 0 78 0 96 13 7 16 0 86 9 9 8 400 13 2 0 98 13 5 3 5 13 3 10 3 0 78 0 96 13 8 16 0 85 9...

Страница 33: ...25 8 679 3 87 0 99 13 4 0 19 3 87 3 02 0 78 0 97 13 7 4 69 30 8 27 0 679 3 87 0 99 13 4 0 20 3 87 3 02 0 78 0 96 13 7 4 69 30 5 29 4 679 3 87 0 98 13 5 0 22 3 90 3 02 0 78 0 96 13 8 4 69 29 9 34 8 679...

Страница 34: ...11 2 0 93 3 5 3 5 11 3 9 2 0 92 3 6 39 8 11 6 400 11 3 0 94 3 5 1 8 11 5 9 4 0 93 3 7 44 8 4 1 400 11 5 0 93 3 6 2 3 12 0 9 8 0 94 3 7 46 7 6 0 400 12 0 0 95 3 7 2 6 12 2 9 9 0 95 3 7 47 3 7 1 400 12...

Страница 35: ...679 3 28 0 93 3 5 0 22 3 31 2 70 0 92 3 6 4 3 34 8 679 3 31 0 94 3 5 0 11 3 37 2 75 0 93 3 7 7 1 12 3 679 3 37 0 93 3 6 0 15 3 52 2 87 0 94 3 7 8 2 18 0 679 3 52 0 95 3 7 0 16 3 57 2 90 0 95 3 7 8 5...

Страница 36: ...6 5 6 8 425 14 8 1 11 13 4 4 0 14 8 11 4 0 77 1 09 13 7 18 4 85 9 7 5 425 14 8 1 11 13 4 4 2 14 9 11 4 0 77 1 08 13 7 18 4 85 4 8 3 425 14 9 1 10 13 5 4 5 14 9 11 4 0 77 1 08 13 8 18 4 85 0 9 1 425 14...

Страница 37: ...3 20 4 722 4 34 1 11 13 4 0 25 4 34 3 34 0 77 1 09 13 7 5 39 29 9 22 5 722 4 34 1 11 13 4 0 26 4 37 3 34 0 77 1 08 13 7 5 39 29 7 24 9 722 4 37 1 10 13 5 0 28 4 37 3 34 0 77 1 08 13 8 5 39 29 4 27 3 7...

Страница 38: ...8 4 425 12 5 1 10 3 3 4 5 12 6 10 6 1 08 3 4 40 3 9 2 425 12 6 1 11 3 3 2 5 13 0 11 0 1 10 3 4 45 2 3 6 425 13 0 1 11 3 4 3 0 13 5 11 6 1 12 3 5 47 3 4 8 425 13 5 1 13 3 5 3 5 13 8 11 8 1 13 3 6 48 3...

Страница 39: ...2 722 3 66 1 10 3 3 0 28 3 69 3 11 1 08 3 4 4 6 27 6 722 3 69 1 11 3 3 0 16 3 81 3 22 1 10 3 4 7 3 10 8 722 3 81 1 11 3 4 0 19 3 96 3 40 1 12 3 5 8 5 14 4 722 3 96 1 13 3 5 0 22 4 04 3 46 1 13 3 6 9 1...

Страница 40: ...1 256 0 997 66 2 19 0 1 000 0 644 0 824 1 000 1 173 1 319 1 319 1 319 1 319 1 000 72 1 22 3 1 100 0 598 0 776 0 951 1 291 1 451 1 451 1 451 1 002 77 1 25 1 1 187 0 582 0 759 1 104 1 434 1 566 1 566 1...

Страница 41: ...1 256 0 959 68 0 20 0 1 000 0 644 0 824 1 000 1 173 1 319 1 319 1 319 1 319 1 000 73 0 22 8 0 985 0 598 0 776 0 951 1 291 1 451 1 451 1 451 1 041 78 0 25 6 0 970 0 582 0 759 1 104 1 434 1 566 1 566 1...

Страница 42: ...RC004 EN 42 Table PD 15 Fan Performance Model Number Min CFM Max CFM 006 Low 200 200 High 250 250 009 Low 267 267 High 333 333 012 Low 333 333 High 400 400 015 Low 333 333 High 425 425 Fan Performance...

Страница 43: ...se refer to the TOPPS selection program Figure PD 1 Elevation View of Noise Control What is Sound Pressure Sound pressure is a pressure disturbance in the atmosphere whose intensity is influenced not...

Страница 44: ...ests in precisely the same environment As in the case of sound pressure it is useful to express sound power on a logarithmic scale What are NC and dBA Both NC and dBA are single number descriptors use...

Страница 45: ...vels are tabulated in performance Table PD 20 Test results are given for each of the four cabinet sizes Measurements were taken for the largest tonnage of each cabinet size Mock up test data provides...

Страница 46: ...WSHP PRC004 EN 46 Control Wiring Basic Controls 220 240V 50 HZ 1 PH...

Страница 47: ...47 WSHP PRC004 EN Control Wiring Deluxe Controls 220 240V 50 HZ 1 PH...

Страница 48: ...WSHP PRC004 EN 48 220 240V 50 HZ 1 PH Control Wiring Tracer ZN 510 Controls...

Страница 49: ...own below This enables panel removal from the unit for service maintenance ability Without Pallet With Pallet Unit Weight Chassis Weight Unit Weight Chassis Weight Unit Size lbs kg lbs kg lbs kg lbs k...

Страница 50: ...WSHP PRC004 EN 50 Dimensional Data LH Cabinet Std Length Height Left Hand Piping Connection GECA 006 015 1 25 4 mm...

Страница 51: ...51 WSHP PRC004 EN Dimensional Data RH Cabinet Std Length Height Right Hand Piping Connection GECA 006 015 1 25 4 mm...

Страница 52: ...WSHP PRC004 EN 52 Dimensional Data LH Extended Length Cabinet Left Hand Piping Connection Extended Length GECA 006 015 1 25 4 mm...

Страница 53: ...53 WSHP PRC004 EN Dimensional Data RH Extended Length Cabinet Right Hand Piping Connection Extended Length GECA 006 015 1 25 4 mm...

Страница 54: ...WSHP PRC004 EN 54 Dimensional Data LH Std Length Low Ht Cabinet Left Hand Piping Connection Low Height Unit GECA 006 015 1 25 4 mm...

Страница 55: ...55 WSHP PRC004 EN Dimensional Data RH Std Length Low Ht Cabinet Right Hand Piping Connection Low Height Unit GECA 006 015 1 25 4 mm...

Страница 56: ...WSHP PRC004 EN 56 Dimensional Data LH Chassis ONLY Left Hand Piping Connection Chassis Only GECA 006 015 1 25 4 mm...

Страница 57: ...57 WSHP PRC004 EN Dimensional Data RH Chassis ONLY Right Hand Piping Connection Chassis Only GECA 006 015 1 25 4 mm...

Страница 58: ...n switching includes ON AUTO Fahrenheit or Celsius Thermostat X13511042010 Auto Manual Changeover Thermostat Digital 3 stage heat 2 stage cool with HEAT OFF COOL AUTO 7 day programmable Fan Switching...

Страница 59: ...ual Changeover Thermostat Mercury 0 stage heat 1 stage cool with COOL OFF Non programmable Fan Switching includes FAN ON AUTO Thermostat X13510589010 Subbase X13530034010 Auto Changeover Thermostat Me...

Страница 60: ...hangeover with OFF AUTO Non programmable Fan switching includes AUTO ON 2 LEDs light emitting diodes Adjustable dead band Thermostat X13510599010 Subbase X13530070010 Auto Changeover Thermostat Mercur...

Страница 61: ...0586010 Subbase X13530053010 Auto Changeover Thermostat Digital 2 stage heat 1 stage cool with AUTO COOL OFF HEAT EM HT 7 day programmable Fan switching includes ON AUTO 12 degree night set back 2 LED...

Страница 62: ...10 and TUC compatible Internal setpoint Communication jack Zone Sensor Tracer ZN 510 and TUC compatible External setpoint Communication jack Zone Sensor Tracer ZN 510 and TUC compatible External setpo...

Страница 63: ...module and the hose kit make a complete self contained pumping package for distributed pumping system These kits contain all the necessary components for the installation operation and maintenance of...

Страница 64: ...gerant and controls shall be provided through a single access panel at the front of the unit chassis Insulation for the internal parts and surfaces exposed to the conditioned air stream shall be made...

Страница 65: ...out protection low pressure time delay compressor delay on start and an open relay for night setback or pump request Optional wiring from the factory for night setback condensate overflow hot gas rehe...

Страница 66: ...te of flow to within 10 percent of the specified amount over a 40 to 1 differential pressure operating range of 2 to 80 PSID The operational temperature shall be rated from fluid freezing to 225 F 107...

Страница 67: ...67 WSHP PRC004 EN...

Страница 68: ...nge design and specifications without notice Literature Order Number File Number Supersedes Stocking Location The Trane Company An American Standard Company www trane com For more information contact...

Отзывы: