Troubleshooting
Checklist
Problem
Heating
Cooling Cause
Correction
No response to any
thermostat setting
X
X
Main power off
Check fuses
X
X
Defective control transformer
Replace
X
X
Broken or loose connection
Repair
X
X
Defective thermostat
Replace
X
X
Transformer
Reset Transformer
Unit short cycles
X
X
Thermostat or sensor improperly located
Relocate
X
X
Unit contains unit mounted thermostat
Change jumper on thermostat from 2-
degrees to 4-degrees
Blower runs, but compressor does not
X
X
Defective compressor overload
Replace (if external)
X
X
Defective compressor contactor
Replace
X
X
Supply Voltage too low
Correct
X
X
Defective compressor capacitor
Replace
X
X
Defective windings
Replace
X
X
Limit switches open
Check cause/Replace or repair
Insufficient capacity
X
X
Dirty filter
Replace/clean
X
X
Blower RPM too low
Correct
X
X
Loss of conditioned air due to leaks in
ductwork
Repair leaks
X
Introduction of excessively hot return-air
Correct
X
Introduction of excessively cold return-air
Correct
X
X
Low on refrigerant charge
Locate leak, repair and recharge by
weight (not by superheat)
X
X
Restricted thermal expansion valve
Replace
X
X
Defective reversing valve
See WSHP-IOM-# for touch test chart
X
X
Thermostat improperly located
Relocate
X
X
Unit undersized
Recalculate heat gains/losses
X
X
Inadequate water flow
Increase GPM
X
X
Scaling in heat exchanger
Clean or replace
X
Water too hot
Decrease temperature
X
Water too cold
Increase temperature
High pressure switch open
X
Inadequate GPM
Increase water flow to unit
X
Water too hot
Decrease temperature
X
Inadequate air flow
Check, clean blower and coil
X
Dirty filter
Clean/replace
X
X
Overcharged with refrigerant
Decrease charge
X
X
Defective pressure switch
Check or replace
High head pressure
X
Trash in heat exchanger
Backflush
X
Low water flow
Increase GPM
X
X
Overcharge of refrigerant
Decrease charge
X
X
Non-condensable in system
Evacuate and recharge by weight
X
X
Water too hot
Decrease temperature
X
Dirty filter
Clean / replace
X
Inadequate air flow
Check, clean blower and coil
Low suction pressure
X
X
Undercharged
Locate leak, repair and recharge
X
X
Restricted thermal expansion valve
Repair / replace
X
Inadequate air flow
Check, clean blower and coil
X
Dirty filter
Clean/replace
X
Inadequate GPM
Increase GPM
Low Pressure switch open
X
Inadequate GPM
Increase GPM
X
Water too cold
Increase temperature
X
Inadequate air flow
Increase CFM
X
Dirty filter
Clean/replace
X
X
Undercharged with refrigerant
Increase charge
X
X
Defective pressure switch
Replace
X
X
Heat transfer fluid too cold
Raise water temperature
Содержание GECA -006
Страница 6: ...6 GECA SVX01B EN Dimensions Weights Cabinet RH no Pump Kit...
Страница 7: ...GECA SVX01B EN 7 Dimensions Weights Subbase RH no Pump Kit...
Страница 8: ...8 GECA SVX01B EN Dimensions Weights Cabinet LH no Pump Kit...
Страница 9: ...GECA SVX01B EN 9 Dimensions Weights Subbase LH no Pump Kit...
Страница 10: ...10 GECA SVX01B EN Dimensions Weights Cabinet RH Extended Length...
Страница 11: ...GECA SVX01B EN 11 Dimensions Weights Subbase RH Extended Length...
Страница 12: ...12 GECA SVX01B EN Dimensions Weights Cabinet LH Extended Length...
Страница 13: ...GECA SVX01B EN 13 Dimensions Weights Subbase LH Extended Length...
Страница 14: ...14 GECA SVX01B EN Dimensions Weights Cabinet RH Low Height Unit...
Страница 15: ...GECA SVX01B EN 15 Dimensions Weights Cabinet LH Low Height Unit...
Страница 16: ...16 GECA SVX01B EN Dimensions Weights Chassis RH...
Страница 17: ...GECA SVX01B EN 17 Dimensions Weights Chassis LH...
Страница 18: ...18 GECA SVX01B EN Dimensions Weights Pump Kit Option...
Страница 40: ...40 GECA SVX01B EN Unit Wiring Basic 115V 60 HZ 1 PH...
Страница 41: ...GECA SVX01B EN 41 Unit Wiring Basic 220 240V 50 HZ 1 PH...
Страница 42: ...42 GECA SVX01B EN Unit Wiring Deluxe 230V 60 HZ 1 PH...
Страница 43: ...GECA SVX01B EN 43 Unit Wiring Deluxe 220 240V 50 HZ 1 PH...
Страница 44: ...44 GECA SVX01B EN Unit Wiring Tracer ZN510 265V 60 HZ 1 PH...
Страница 45: ...GECA SVX01B EN 45 Unit Wiring Tracer ZN510 220 240V 50 HZ 1 PH...