Installation

10

 ACC-SVN232A-EN

Minimum Position Setting 

To adjust the minimum position setting and check out the 
economizer, the power must be connected.

1. Close the unit disconnect and place the zone sensor fan 

selector in the fan 

ON

 position and the heat/cool 

selector in the 

OFF

 position. This will place the damper 

in the minimum ventilation position.

2. To adjust the minimum position setting for the 

required ventilation air, use the Symbio™ service and 
installation mobile app or Symbio™ 700 on-board UI 
to adjust the economizer minimum position setpoint 
BAS in the fresh/return air settings menu. The damper 
will open to this setting each time the blower circuit is 
energized.

When adjusting minimum position, the damper may 

move to the new setting in several small steps. Once 
the damper has remained in position for 10 - 15 

seconds without movement, it can be assumed it is at 
the new position.

3. Replace the filter access panel.

The damper will close when the blower circuit is

de-energized.

Dry Bulb Settings

Standard economizer dry bulb changeover is field 
selectable and has a range of 50-140ºF.

Reference Enthalpy Settings

Economizer enthalpy changeover is field selectable and 
has a range of 50-140ºF. The default is 60ºF. This selection 
can be made using the Symbio service and installation 
mobile app or Symbio™ 700 on-board UI.

Wiring Connections

Refer to main unit schematic sheet 6 for electrical 
connections to Fresh air module located in return section 
control box, See 

Figure 17, p. 10

.

After installation is complete, the Symbio™ 700 UC 
configuration will need to be updated to enable this 
installed feature. Refer to Symbio Applications Guide.

Table 1.

Precedent economizer control options

Control Option

Enable Conditions

Optional Sensors Required

Comparative Enthalpy

Outside Air Enthalpy < Return Air Enthalpy – Econ Enthalpy 
Offset AND Outside Air Temperature < Economizer Drybulb 
Setpoint – Econ DryBulb Offset

Outdoor Air Temperature Sensor
Outdoor Air Humidity Sensor
Return Air Temperature Sensor
Return Air Humidity Sensor

Reference Enthalpy

Outside Air Enthalpy < Reference Enthalpy Setpoint – Econ 
Enthalpy Offset AND Outside Air Temperature < Economizer 
Drybulb Setpoint - Econ DryBulb Offset

Outdoor Air Temperature Sensor
Outdoor Air Humidity Sensor

Dry Bulb

OA Temp < [Economizer Outdoor Air Enable Setpoint BAS - 
Economizer Dry Bulb Enable Offset]

Outdoor Air Temperature Sensor

Differential Dry Bulb

OA Temp < RA Temp - Economizer Dry Bulb Enable Offset - 
Economizer Dry Bulb Disable Return Air Offset

Outdoor Air Temperature Sensor
Return Air Temperature Sensor

Figure 17.

Fresh air options module location

Fresh air options 
module access (D cabinet)

Fresh air options 
module access (B and C cabinet)

Содержание FIAECON003 Series

Страница 1: ...nstall and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improper...

Страница 2: ...rdous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or pro...

Страница 3: ...arks All trademarks referenced in this document are the trademarks of their respective owners WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury A...

Страница 4: ...recedent 5 Field Installed Option 5 Factory Installed Option 5 Installation Precedent 6 Field Installed Option 6 Factory Installed Option Field Set Up 8 Mist Eliminator Servicing 9 Minimum Position Se...

Страница 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Страница 6: ...ves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions Unless specified otherwis...

Страница 7: ...post flange as illustrated in following figure c Position the left side flange on the economizer in front of the corner post flange d With the screws provided secure the bottom right hand side of the...

Страница 8: ...Figure 12 7 With the screws provided secure each side of the economizer assembly by inserting a screw through the clearance hole in the bottom of the corner post and into the engagement hole in the e...

Страница 9: ...screws provided 11 Using field supplied silicone sealant seal all seams cracks and gaps around the back panel and vertical edge of the hood panels Mist Eliminator Servicing 1 Remove screws from end p...

Страница 10: ...made using the Symbio service and installation mobile app or Symbio 700 on board UI Wiring Connections Refer to main unit schematic sheet 6 for electrical connections to Fresh air module located in re...

Страница 11: ...Notes ACC SVN232A EN 11...

Страница 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Отзывы: