Installation - Controls

54

 UNT-SVX041D-EN

After the channel scan is finished, LED3 begins blinking 
(one-blink pattern) to show that the receiver is ready to be 
associated with a sensor.

Associating Sensor to Receiver

To associate the sensor to the receiver:

1. Remove the sensor cover by firmly pressing the thumb 

tab at the bottom of the cover and pulling the cover 
away from the back plate.

2. Verify that the sensor is set to the same address as the 

receiver it is to be associated with.

3. Power the sensor by removing the insulation strip from 

between the two batteries.

Association is automatically initiated between the sensor 
and the receiver. When LED3 on the receiver stops 
blinking, association has been established.

If the first association attempt is unsuccessful, the sensor 
automatically re-attempts association with the receiver 
every 10 minutes.

Note:

An associated sensor that has lost communication 
with the receiver will transmit an association 
request every 50 minutes. You can manually 
initiate association (see 

“Manual Association,” 

p. 76

”).

Testing Signal Strength and Battery

To verify that the association process was successful and 
that the batteries have adequate charge: 

1. Firmly press and release the Test button on the bottom 

of the sensor as illustrated in the figure below.

2. For model WZS, view LED1, LED2, and LED3 to 

determine the signal strength. View LED5 to determine 
the battery status (see the figure below for model WZS 
sensors).

Note:

The LEDs will turn Off after 5 seconds to 
conserve battery strength.

Figure 47.

Receiver conducts 20 second channel scan

Figure 48.

LED3 blinks after channel scan to show 
receiver is ready

0

20

Sec.

LED3

Figure 49.

Power sensor by removing insulation strip

Содержание FCV

Страница 1: ...lation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment...

Страница 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Страница 3: ...ption chapter Updated top discharge unit front and side discharge unit and unit without risers graphics in the Dimensions and Weights chapter Updated pipe connections for units without risers graphics...

Страница 4: ...rimary Secondary Unit 21 Riser Packages 22 Location of Floor Opening for Risers 24 Installation Piping 26 Coil Identification 26 Piping Arrangements for Chilled and Hot Wa ter Coils 26 Two Pipe Coils...

Страница 5: ...gs 61 WDS Operating Mode 61 Changing Room Temperature 62 Changing Heating Cooling Settings 62 Changing Fan Settings 62 Requesting Temporary Occupancy 62 Error Codes 62 Lock Symbol 62 Testing Signal St...

Страница 6: ...Modes 77 Measuring Output Resistance 78 Cleaning the Sensor 78 LED Activity 79 Overriding Outputs 80 Diagnostics 80 Diagnostics Types 80 Fans with UC400 B Controller 81 Valves with UC400 B Controller...

Страница 7: ...4 kW 208V 3 kW 050 5 kW 208V 3 8 kW 060 6 kW 208V 4 5 kW 070 7 kW 208V 5 3 kW 080 8 kW 208V 6 kW 100 10 kW Digit 23 Disconnect Switch 0 None D Disconnect Switch Digit 24 Filter Type 0 No Filter 1 1 i...

Страница 8: ...0 75 in Main Risers B 1 00 in Main Risers C 1 25 in Main Risers D 1 50 in Main Risers E 2 00 in Main Risers F 2 50 in Main Risers Digit 40 Auxiliary Riser Insulation 0 No Insulation Ship Separate Rise...

Страница 9: ...Insulation 2 3 4 in Closed Cell 3 1 in Closed Cell 4 1 5 in Closed Cell Digit 8 DIA Auxiliary Supply Riser 0 No Auxiliary Riser A 0 75 in Auxiliary Risers B 1 00 in Auxiliary Risers C 1 25 in Auxilia...

Страница 10: ...submittals and ensure that the drywall does not interfere with the side wall grille Make allowance for the one inch flange around the grille Wall sleeves are not included which might be needed to brid...

Страница 11: ...ngs can loosen during transportation and handling The coil is leak and proof tested at the factory Two way Control Valves When two way valves are used pump and chiller bypass or pump speed control mus...

Страница 12: ...UTSIDE AIR OPENING BALL VALVE RISER SUPPLY RETURN RISER DRAIN DRAIN PAN P TRAP COIL DUCT COLLAR FRONT VIEW RIGHT SIDE VIEW PLUG CONNECTION FOR THERMOSTAT CUSTOMER CONTROL WIRING 1 3 32 in HOLE WITH PL...

Страница 13: ...31 00 3 10 40 80 8 30 2 37 2 88 5 38 G 1 00 1 00 6 00 46 98 1 53 A B D RISER SUPPLY RETURN SUPPLY OPENING S DUCT COLLAR RISER DRAIN BLOWER DRAIN PAN FRONT VIEW PLUG CONNECTION FOR THERMOSTAT 86 00 64...

Страница 14: ...5 5 38 Figure 3 Units without risers CWS CWR HWS HWR 4 13 2 25 C C 4 pipe secondary unit with connection 2 pipe secondary unit with connection Supply and return connections 1 2 in Copper pipe Supply...

Страница 15: ...15 Fan Coil Weights The weights are approximate Risers external sheet metal accessories and supply air grilles are not included in the weight Table 4 Weights for fan coil units Size Weight 300 120 400...

Страница 16: ...penetration although 2 inches is preferable and allowed for into each swaged joint This condition will be met if floor to floor dimensions are as specified and each branch run out is properly centere...

Страница 17: ...be used It is designed to fit the 1 inch drywall flange around the return air access opening on the unit Use drywall screws no longer than 1 inch and follow the instructions on the page in the submit...

Страница 18: ...uver return air panel will ship with fasteners installed 2 Hook the panel over the bottom collar of the fan coil unit rotate the panel upright so that it is against the wall and turn the head of the f...

Страница 19: ...the floor slab usually sleevedbefore pouring the floor Refertothe catalogor submittals for sizes 2 Rotate the unit from the horizontal position to vertical so that the bottom end of the risers insert...

Страница 20: ...slab to avoid rebar 2 Install risers using the dimensions in the submittal for locating the riser stubs vertically and at the correct horizontal center lines Anchor the risers and make good the insula...

Страница 21: ...riser shut off valve 6 Make condensate connection 7 Cut P trap to size 8 Make condensate connection Table 11 P trap size when installed on side of unit Cutoff Dimension A B Size 3 04 2 20 in 5 90 in...

Страница 22: ...Risers S C R Left Risers S C R Right Risers S C R RA RA Figure 10 Riser 4 pipe package Top View 3 000 3 000 HWS Hot Water Supply Riser HWR Hot Water Return Riser CWS Chilled Water Supply Riser CWR Chi...

Страница 23: ...igure 11 Riser installation dimensions inches L F 2 inches Spool Piece Length F L 4 inches L F Spool Length 4 inches Standard Installation Standard Installation Using Field Supplied Spool Pieces 89 in...

Страница 24: ...ng in floor slab Insulated risers Return air opening flange on front of unit Alternative positions for return air opening L 3 4 C L 5 5 2 3 1 4 4 5 W Table 14 Dimensions Fan Coil Model Width inches Le...

Страница 25: ...risers will require stub out extensions Refer to the recommended installation diagram for details Figure 13 Recommended installation layout for field provided risers RA RA RA Back Riser Left Riser Rig...

Страница 26: ...r ensures that the thermostat operates in a mode compatible with the water temperature in the coil All coils are piped so that the inlet is always on the row farthest downstream from the incoming air...

Страница 27: ...inch or 3 4 inch copper tail piece soldered into valve body at factory Insulation lining on interior surface of fan coil cabinet Fan coil cabinet CWS CWR HWS HWR 4 13 2 25 C C 4 pipe secondary unit w...

Страница 28: ...ch diameter opening with a removable plug is provided on the left side of the unit for connection of low voltage control wiring If the control wiring is not wired in conduit then a strain relief fitti...

Страница 29: ...led by others terminal strip provided A Setpoint Dial Zone Sensor 3 inch B Setpoint Dial Zone Sensor w Comm 3 inch C Setpoint Dial On Cancel w Comm 3 inch D Digital Zone Sensor 3 inch E Telkonet 3 inc...

Страница 30: ...W Amps kW Amps kW Amps kW Amps 400 a 120 1 60 2 0 16 7 2 5 20 8 208 1 60 1 5 7 2 1 9 9 1 2 3 11 1 240 1 60 2 0 8 3 2 5 10 4 3 0 12 5 277 1 60 2 0 7 2 2 5 9 0 3 0 10 8 600 b 120 1 60 2 0 16 7 3 0 25 0...

Страница 31: ...electric heater Exception No 2 If the computed value of the overcurrentprotectivedeviceislessthantheminimum ampacity of the supply circuit the marked rating of the device shall be increased to the la...

Страница 32: ...he new equipment This literature focuses on unit motors and controls including three new circuit modules developed specifically for this series There are four primary components that enable the techno...

Страница 33: ...ile configurable auxiliary temperature sensor Incorporates various safety and lockout features such as maintaining proper fan speeds if electric heat is called for Status Display The motor control boa...

Страница 34: ...d supplied controller thermostat Adjustment and calibration of the variable speed inputs VSP 0 10V on the system Adjustment calibration or disabling of the optional auto changeover function on CSTI un...

Страница 35: ...isplayed the status will loop the following message WARNING Safety Alert You MUST follow all recommendations below Failure to do so could result in death or serious injury All settings take effect imm...

Страница 36: ...a fan missing condition a Indicates the status being calculated or Fan Motor 1 If off this indicates that either 1 No fan speed is being requested or 2 The fan performance is failing to meet the reque...

Страница 37: ...dons value if changed Long Press Hold in Status Display 3 sec Enters the configuration menu Long Press Hold in Configuration Display 3 sec If on a parameter name toggles to the value If on a parameter...

Страница 38: ...r Display Under special conditions the status display will interrupt briefly to prioritize display of events Notes During error displays the user interface will be disabled until the error is removed...

Страница 39: ...tive motor Electric heat and changeover heat will be shut down Indicates that Motor 1 has experienced a run away or over speed condition and has been shutdown The unit will offer limited limp in perfo...

Страница 40: ...nimum output of the controller is significantly greater than the floor setting the first point that the motor will turn on will be above the and value The full range of motor control will not be fully...

Страница 41: ...fore servicing could result in death or serious injury Disconnect all electric power including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout ta...

Страница 42: ...in addition will disable heating function on electric heat and on the changeover coil if there are fan failures The auxiliary heating coil function will continue to operate and respond to the custome...

Страница 43: ...rol board label WARNING Safety Alert You MUST follow all recommendations below Failure to do so could result in death or serious injury All settings take effect immediately including fan startup and e...

Страница 44: ...I Low Spd Mtr 2 Sets the minimum turn on rpm for Motor 2 when the analog input becomes active Op Mode Mtr 1 Sets the operational mode for Motor 1 Must be set to for blower coil units Op Mode Mtr 2 Set...

Страница 45: ...p the on board closed loop control to control Motor 2 with proper stability Do not change this setting Ht Sens Mk Val F Sets the make value for the motor control board triac output based on the thermi...

Страница 46: ...cal unit operating fan speeds Note The indicator is unit specific and may indicate Off at this point refer to thermistor function for more information 3 OPTIONAL While the fan is running if practical...

Страница 47: ...ompliance with NEC and local codes The wire must be low capacitance 18 gauge stranded tinned copper shielded twisted pair Note For more details refer to Wiring Guide Unit Controller Wiring for the Tra...

Страница 48: ...the UC400 B controller is always soft set by the system controller using the following scheme illustrated below Note The BACnet Device ID is displayed as the Software Device ID on the Tracer TU Contr...

Страница 49: ...as network coordinator Quantity of Networks per Tracer SC A Tracer SC can support up to eight wireless networks Automatic Network Formation When a WCI is connected to a Tracer SC it is auto assigned a...

Страница 50: ...l anchors for sheet rock walls Overall dimensions 2 9 inch 74 mm by 4 7 inch 119 mm Wireless protocol ZigBee PRO ZigBee Building Automation Profile ANSI ASHRAE Standard 135 2008 Addendum q BACnet ZigB...

Страница 51: ...r of devices In general sheetrock walls and ceiling tiles offer little restriction to the transmission range for the sensor is as follows Open range 2 500 ft packet error rate 2 Usable range 200 ft Ty...

Страница 52: ...over the top of the back plate Apply light pressure to the bottom of the cover until it snaps in place b Install the security screw into the bottom of the cover if desired see the following figure Wi...

Страница 53: ...events association with a sensor 2 Set the three rotary address switches locations S1 S2 S3 on the sensor to the same address as the receiver Note Do not use 000 as an address An address of 000 remove...

Страница 54: ...successful the sensor automatically re attempts association with the receiver every 10 minutes Note An associated sensor that has lost communication with the receiver will transmit an association requ...

Страница 55: ...ange temperature limits Sensor The end of range temperature setpoint limits for the WDS is 50 Fto 89 6 F Receiver Power up Sequence When power is applied to the receiver one of the following sequences...

Страница 56: ...nsor within 35 minutes zone temperature and setpoint outputs fail generating a unit controller alarm see FailureandDefaultModes p 77 Note Once a receiver communicates to a WZS sensor the receiver disa...

Страница 57: ...n 1 VA Housing Polycarbonate ABS blend UV protected UL 94 5VA flammability rating suitable for application in a plenum Mounting 3 24 in 8 26 cm for 2 mounting screws supplied Sensor battery 2 AA 1 5 V...

Страница 58: ...from F C Heat Cool Heat Cool or Backlight Operational Temperature F C Min 35 2 Max 120 49 INTERCONNECTIVITY AND CERTIFICATIONS I O Connections NTC Temperature Probe 1 Input Current Transformer Input...

Страница 59: ...s subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired opera...

Страница 60: ...1 on p 59 Note The sensor will revert to operating mode if no buttons are pressed for 10 minutes Figure 54 Center button of keypad Center button Table 28 Configuration options for wireless display sen...

Страница 61: ...he system menu press the down arrow to select the fan menu Use the left or right arrow to choose the setting 3 Press the left and right arrows for 4 seconds Note If you try to access a feature that is...

Страница 62: ...sired setting appears confirm your choice by pressing the home screen will appear Indicates that the fan setting is On The number of arrows indicates fan speed 3 high 2 medium 1 low The example shown...

Страница 63: ...assuming the following conditions Room temperature should be greater than 55 F and less than 85 F For a 2 pipe fan coil unit with an entering water temperature sensor the water temperature input is ap...

Страница 64: ...service tool Unoccupied Mode In unoccupied mode the controller attempts to maintain the space temperature based on the unoccupied heating or cooling setpoint The fan will cycle between high speed and...

Страница 65: ...implified zone controls runs In the unoccupied mode the controller maintains the zone temperature by calculating the required heating or cooling capacity 0 100 according to the measured zone temperatu...

Страница 66: ...ted fan speed signal HIGH MEDIUM LOW The associated fan speed switch is set to a specific fan speed The Supply Fan Speed Request point is overridden During unoccupied operation the fan cycles between...

Страница 67: ...peration the controller overdrives the actuator 135 percent of the stroke time whenever there is a request for a position of 0 percent or 100 percent At either power up after a power outage or when th...

Страница 68: ...a diagnostic reset is sent to the controller and the fan condition still exists the controller attempts to run the fan for 1 minute before generating another diagnostic and performing a unit shutdown...

Страница 69: ...tructions below could result in minor to moderate injury The service procedure described in this document involves working around sharp edges To avoid being cut technicians MUST put on all necessary P...

Страница 70: ...ts refer to model and serial number located on the unit nameplate which is located on the fan motor cover Table 30 Filter size Filter Size 1 inch thick Unit Size Width in Height in 300 12 15 18 375 40...

Страница 71: ...rtial loss of line voltage Check for loose connections Determine adequacy of main power supply Motor does not come up to speed Low voltage at motor terminals Check across AC line and correct voltage l...

Страница 72: ...e Verify valve operation Verify proper valve size Incorrect refrigerant charge Verify refrigerant charge and adjust if necessary Condensing unit failure Verify condensing unit operation Coil is piped...

Страница 73: ...1 Off LED2 Off LED3 2 blink pattern repeated continuously a Address set to 000 Address not set to between 001 999 LED1 Off LED2 Off LED3 3 blink pattern repeated continuously a Not configured Receiver...

Страница 74: ...cation LED1 Off LED2 On LED3 On Displays for 5 seconds then constantly Off Satisfactory signal strength Adequate signal strength for reliable communication Moving sensor or receiver may improve signal...

Страница 75: ...es already installed Replacement batteries are available at Trane Service Parts Centers p n X13770035010 or other local suppliers Battery Life Battery life is five years under normal conditions If the...

Страница 76: ...tion The receiver disassociates from the sensor by removing all stored association information conducts a channel scan and restarts itself if any of the following are true The receiver address is chan...

Страница 77: ...Measuring Output Resistance 4 When the test is complete reset the receiver address to its previous setting 5 Press the Test button on the sensor to force re association 6 Confirm association and commu...

Страница 78: ...ered consequently resistance can be measured without risk of damage to the volt ohm meter Cleaning the Sensor You can clean the sensor by applying glass cleaner to a soft non abrasive cloth and gently...

Страница 79: ...antly blink as it continually looks for devices to communicate to LED not lit Determine if for example a Tracer SC or BACnet device is trying to talk to the controller or if it is capable of talking t...

Страница 80: ...to as latching cause the unit to shut down Manual diagnostics can be cleared from the UC400 B controller in one of the following ways By using the Tracer TU service tool to reset latching diagnostics...

Страница 81: ...mper Unaffected Electric heat Unaffected Automatic CO2 sensor failure Invalid or missing value for CO2 Fan Unaffected Valves Unaffected Outdoor air damper Unaffected Electric heat Unaffected Informati...

Страница 82: ...t configuration does not match the actual end device the valves may not work correctly Random start observed After power up the controller always observes a random start from 5 to 30 seconds The contr...

Страница 83: ...lectric heat operation For detailed information about these diagnostics refer to Table 42 p 81 Normal operation The controller controls compressor or electric heat outputs as needed to meet the unit c...

Страница 84: ...d will display troubleshooting information and contains dual tachometers to aid in performance verification Under normal circumstances the VelociTach display will display the operational status of the...

Страница 85: ...due to engine locked rotor protection Motor 1 has an obstruction Status Display will be interrupted to display Remove obstruction from the fan wheel Ensure that motor plugs and all plugs to adapter bo...

Страница 86: ...ld be maintained to retain the order of the motors with respect to the motor plugs On a unit with two motors the double shafted motor will always be tothe leftside and willbe designated as Motor 2 by...

Страница 87: ...he unit by performing at a minimum Fan Speed Response Verification p 46 Application Notes The ECM motor has some notable differences to traditional designs NOTICE Equipment Damage Failure to follow th...

Страница 88: ...ors cannot achieve rpm close to the target for a specific period of time the unit will disable electric heat and fan status indicators MCA MOP and Power Draw ECM motors have variable output but are sh...

Страница 89: ...EN 89 Wiring Diagrams Figure 66 High voltage wiring diagram SAMPLE L L L LE LE LE LE LE LE LE LE LE E E E S S S S S SA SA SA SA SA SA SA SA SA SAM M MP P P P M M M M M M M M M M M M M M M M M AM AM A...

Страница 90: ...A S S S S S S S S SA SA SA SA SA SA A A A A A A A A SA SA A A A A A A SAM M M M M M MP MP MP MP P P P PLE E E E A S S S SA SA SA SA AMP AM AM SA A A PL LE PL PL PL PL PL L LE LE PL PL PL PL PL PL PL P...

Страница 91: ...SVX041D EN 91 Figure 68 UC400 B wiring diagram SAMPLE PL S S S S S S S S S S S S S S S S S S S S SA S S S S S S S S S S SA SA PL S S S M M M M M M MP MP MP MP P P P P P P P P P P P P P P P PL PL P P...

Страница 92: ...Wiring Diagrams 92 UNT SVX041D EN Figure 69 Electric heat wiring diagram SAMPLE E MP S L L L L L L L L L L L L LE L LE LE LE LE LE LE E...

Страница 93: ...Wiring Diagrams UNT SVX041D EN 93 Figure 70 UC400 B component layout S A M P L E E E E E...

Страница 94: ...Wiring Diagrams 94 UNT SVX041D EN Figure 71 CSTI component layout S A M P L E...

Страница 95: ......

Страница 96: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: