6
PRGF-SVN001B-EN
General Information
Specifications
Performance Specifications
Electrical Power Requirements
Note:
Voltage range is +10%, -15%
115 Vac, 60 Hz, 1-Phase, 10.3 Amps
110 Vac, 50 Hz, 1-Phase, 10.3 Amps
Fault Relay Output Rating
120 Vac, 1 Amp
Operating Environment
34° F (1°C) to 110° F (43°C); 5% to 95% relative humidity, non-
condensing
Storage Environment
-40° F (-40°C) to 150° F (66°C); 5% to 95% relative humidity, non-
condensing
Mounting
Direct-mounted on condenser shell above liquid-level of highest
condenser.
Optionally mounted below condenser using liquid separator.
Dimensions (Approx.)
25” high (635 mm) x 31 1/2” wide (800 mm) x 23 1/8” deep (587 mm)
with filter drier canister and DynaView installed
Weight
140 lbs. (64 Kg) with filter drier canister installed
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury. Technicians, in order to protect
themselves from potential electrical, mechanical, and
chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as
the following instructions: Unless specified otherwise,
disconnect all electrical power including remote
disconnect and discharge all energy storing devices
such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can not
be inadvertently energized.When necessary to work
with live electrical components, have a qualified
licensed electrician or other individual who has been
trained in handling live electrical components perform
these tasks.
Purge Nameplate
The nameplate is located on the top of the control panel.
Always provide the model number, serial number and
product description information from the nameplate when
making inquiries, or ordering parts or literature for the
purge unit.
Figure 1.
Typical purge nameplate
MODEL NO: PRGFA001AA0
SERIAL NO: L18G09795
RATED VOLTAGE;110/50/1, 115/60,1
TOTAL UNIT AMPS:10.3 AMPS
MIN CKT AMPACITY:12.3 AMPS
MAX OVERCURRENT
PROTECTIVE DEVICE:15 AMPS
FACTORY CHARGED:.1.00 LBS OF R513A
DESIGN PRESSURE:HIGH SIDE 335 PSIG
LOW SIDE 175 PSIG
UNIT SUITABLE FOR USE WITH
REFRIGERANTS:R123, R11, R113
SERVICE LITERATURE:PRGF-SVN01A-EN
PRGF-SVX001A-EN
MANUFACTURED UNDER ONE OR MORE OF THE
LISTED U.S. PATENTS OWNED BY
AMERICAN STANDARD INC.: 5,031,410