Commissioning

 •

 Water loop electric heating conditions

   During heating, when the discharge water temperature 

 

"

set heating temperature

"

 – 

"

heater start-up temperature difference

"

, the 

   water loop electric heating will be activated; when the discharge water temperature 

 

"

set heating temperature

"

 - 

"

heater stop temperature 

   difference

"

, the water loop electric heating will be turned off.

6-3. Controller Operation Instructions

 

Centralized controller (MC-11) is used for the start/stop control of multiple units. Please refer to instructions for the operation of centralized con

-

troller. For single unit, user can use TM71 controller to control the unit.
The controller is connected to the CN4 interface of the mainboard of electric control box. The centralized controller uses CN29 interface.

1. Introduction

User can use this controller for operation mode selection, start/stop, timed start/stop, fault clearing and parameter setup.
The controller can display return water temperature, discharge water temperature and operation status of compressor and pump in real time.

TM71  Wired Cont roller User Manual

Material  Number: 690132030001/ Version:F

Please  read the manual and ope rate the cont roller acco rding to the inst ruction

1  

Illust ration of Cont rol and Displ ay Panel 

8

16

15
14

13

11

12

10

9

17

7

6

5

4

3

2
1

1.1  Control Panel

1. -

 

 ON/OFF bu tton.

2. -

 

 MODE bu tton. 

Press this bu tton before sta rt-up to choose 

cooling or heating.

3. -

 

 RESET bu tton. 

When malfunction alarm, press this bu tton 

to reset system manuall y.

4. -

 

 SETTING bu tton. 

Press this bu tton to set values ( Password 

needed).

5. -

 

 Time query/ se tting button.

6. -

 

 Timer bu tton, Press this bu tton to select the 

desired timer function.

7, 8. -

   Press these two bu ttons to view or modify 

the set values.

1.2  Display Panel

9. -

 

 Defrosting operation displa y.

10. -

   Water pump sta rt-up displa y.

11. -

   Anti-freeze mode displa y.

12. -

   Compressor #2 sta rt-up displa y.

13. -

   Auxiliary electrical heater sta rt-up displa y.

14. -

   Heating mode displa y.

15. -

   Compressor #1 sta rt-up displa y.

16. -

   Cooling mode displa y.

17. -

   Window for temperature and values displa y.

2  

Operation Int roduction

1.    On-off 

Choose required mode fi

r

stl

y, press 

 then unit 

will run on this mode. 

P

ress this bu tton again to 

shut down. Do not press 

 frequently.

2.    Mode selection  

Includeing cooling mode and heating mode. Mode 
should be selected a fter shut-down.

3.    Value browse  

Press 

 fi

rstly, then press 

 , 

 to browse the 

value.  

4.    Leaving  water temperature display During oper -

ation, press MODE bu tton to show leaving  water 
temperature for 6 seconds.

5.    Reset  

When malfunction displa y, press 

 .

6.    Value Se tting 

The five values mentioned ab

ove may be set 

through 

 and 

 , 

 .

7.    Normal displ ay 

On normal condition,entering  water temperature, 
compresso r, heater and  water pump paramete rs are 
displayed.  There will be ba cklight when communica -
tion fails.

4  

Factory Se tting

Code in

controller

name of  

parameter

MAX.

MIN.

regulation

accuracy

default 

setting

3

Max. time of defrost

15min

8min

1min

10min

5

600s

60s

10s

10

(100s)

6

no detect time of low pressure switch (after compressor 

running)

600s

10s

10s

4

(40s)

10

Min.running time of compressor

4min

2min

1min

3min

11

Min.stop time of compressor

4min

2min

1min

3min

14

Lock time of cooling antifreeze

60min

3min

1min

3min

20

cooling antifreeze enter temperature (outlet water)

5ºC

-20ºC

1ºC

3ºC

21

cooling antifreeze exit temperature (inlet water)

10ºC

-5ºC

1ºC

8ºC

23

standby antifreeze exit temperature (winter)

15ºC

1ºC

1ºC

15ºC

26

ambient temperature of allowing access to defrost 

20ºC

10ºC

1ºC

15ºC

30

Temperature difference of loading

3ºC

0ºC

1ºC

1ºC

31

Loading and unloading cycle

300s

10s

10s

9

(90s)

32

480 step EXV opening value (in defrost)

480step 100setp

10step

48

(480step)

35

Temperature difference of electric heater start

20ºC

0ºC

1ºC

10ºC

36

Temperature difference of electric heater stop

20ºC

0ºC

1ºC

6ºC

45

Mandatory defrosting interval

12h

1h

1h

4h

61

2000 step EXV opening value (in defrost)

2000step 400setp

100step

18

(1800step)

3  

Cus tomer Se tting

Code in controller

name of parameter

MAX.

MIN. regulation accuracy default setting

016

COOLING SETTING TEMP.

15ºC

5ºC

1ºC

7ºC

017

HEATING SETTING TEMP

50ºC

25ºC

1ºC

45ºC

022

8ºC

1ºC

1ºC

5ºC

001

Defrosting Time lag

90min

30min

3min

40min

Password range

75

50

1

50

Pass word En ter

Press 

 5 seconds, a fter display  “50” , press   or 

 , when display“66” and press   .

Cooling Se tting Temperatur

e Modification

Range:  10 

º

C ~ 25 

º

C.

Operation: af

ter confirm password, press 

 or 

 , when display“16”  in time area ( 

 ), press 

 and 

adjust the value, press 

 again to exit.

5  

Paramet

er Modification

8.1  Pass word En ter

Press 

 5 seconds, a fter display  “50”

, press

 or 

 , 

when display“72” and press   .

8.2  Water Switch Delay Time

Range: 60S ~ 6 00S.
Operation: af

ter confirm password, press 

 or 

 , 

when display  “05” in time area ( 

 ), press 

 

and adjust the value, press 

 again to exit.

8.3  Query So ftware Version

Press 

 5 seconds, a fter display“50” , and press   

again Main display area  “

” show the version of sin -

gle unit controller  Time display area“ 

 ”show 

the version of so ftware.

6  

Time Se tting 

9.1  Clock Se tting

Time se tting range:  00:00 ~ 23:59
Operation: press 

 ,  choose  “

” flash displa

y, and 

 ”also flash displa

y, press 

 or 

 to adjust 

time, if press 

 or 

 for 2 seconds, the time will 

decrease or increase qui ckly, press 

 to exit.

9.2  Se tting Open  Time

Time se tting range:

 00:00 ~ 23:59

Operation:

 press 

 ,choose  “

” flash displa

y, and 

 ”also flash displa

y, press 

 or 

 to adjust 

time, if press 

 or 

 for 2 seconds, the time will 

decrease or increase qui ckly, press 

 to exit.

9.3  Se tting Close  Time

Time se tting range:

 00:00 ~ 23:59

Operation:

 press 

 ,choose  “

” flash displa

y

, and 

 ”also flash displa

y, press 

 or 

 to adjust 

time, if press 

 or 

 for 2 seconds, the time will 

decrease or increase qui ckly, press 

 to exit.

9.4  Timer  Function

Operation:

 press 

 , when  “

” display, ON timer is 

activated;
Press 

 , when  

” display , OFF timer is activated;

Press 

 , when  

 

” display, ON OFF timer is 

activated;
Press 

 , when  

 

” disappear, ON OFF timer is 

inactivated;

2. Illustration of control and display panel 

3. Operation introduction 

• Control panel

1.ON/OFF button.
2.MODE button.
   Press this button before start-up to choose

 

cooling or 

   heating.
3.RESET button.
   When malfunction alarm, press this button to reset 
   system manually.
4.SETTING button.
   Press this button to set values ( Password needed).
5.Time query/ setting button.
6.Timer button, Press this button to select the desired 
   timer function.
7,8.Press these two buttons to view or modify the set values.

• Display panel

9.Defrosting operation display.
10.Water pump start-up display.
11.Anti-freeze mode display.
12.Compressor #2 start-up display.
13.Auxiliary electrical heater start-up display.
14.Heating mode display.
15.Compressor #1 start-up display.
16.Cooling mode display.
17.Window for temperature and values display.

 • On-off
   Choose required mode firstly, press      then unit will run on this mode. Press this button again to shut down. Do not press      frequently.
 • Mode selection
   Includeing cooling mode and heating mode. Mode should be selected after shut-down.
 • Value browse
   Press      firstly, then press      ,      to browse the value.
 • Leaving water temperature display During operation, press MODE button to show leaving water temperature for 6 seconds.
 • Reset
   When malfunction display, press      .
 • Value Setting
   The five values mentioned above may be set through      and      ,      .
 • Normal display
   On normal condition,entering water temperature,compressor, heater and water pump parameters are displayed. There will be backlight when 
   communication fails.

Содержание CGAJ065

Страница 1: ...operly installed adjusted or altered equipment by an unqualified pers on could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags...

Страница 2: ...ction 12 3 1 Cooling System Diagram 12 3 2 Main Components and Function Chart 14 3 3 Unit Appearance and Structure 15 3 4 Control Box Introduction 18 4 Unit Installation Requirements 21 4 1 Outdoor Un...

Страница 3: ...6 4 Adjustment and Judgement of Refrigerant Volume 36 6 5 Judgement of Water Flow in Water System 36 6 6 Non fault Phenomenon 36 7 Fault Handling 37 7 1 Fault Alarm Table 37 7 2 Fault Handling for Ou...

Страница 4: ...failure damage or personal safety When cleaning the unit do not sprinkle water directly on the unit which may cause electric shock Cut off all power supplies before contacting the wiring device Before...

Страница 5: ...nit is not used for a long time please cut off the main power supply of the system to extend the service life of the unit and save electrical energy Do not touch the fins of the heat exchanger Otherwi...

Страница 6: ...ust and water refill in water system Make sure the water temperature meets the operation requirements The air condition water pipeline and hot water pipeline must go through pressure test to ensure th...

Страница 7: ...FF by default if modular control is needed user should set the code on site as needed The Bit1 5 of the switch is used for code address of centralized control Note The modular host of must set to 00 S...

Страница 8: ...changer pipeline at water side is frozen it will be seriously damaged namely the heat exchanger will break or leak Such freezing damage is not covered in warranty therefore user should take anti freez...

Страница 9: ...y Digit 12 Controller S Modular Controller units 2 U Unit Controller unit 1 N None Digit 13 Service Sequence F 6th Time Digit 14 Ambient Temperature R Standard Digit 15 Connector Option A Without 2 pc...

Страница 10: ...9 2 38 0 Rated Heating Power kW 9 5 19 0 Rated Heating Current A 18 5 34 0 Refrigerant Category R410A Charge kg 13 12 5 2 13 12 5 2 Water Side Category of Heat Exchanger High efficiency shell tube hea...

Страница 11: ...2 55 0 98 2 Compressor Category Hermetic scroll No Pieces 2 4 2 4 Rated Cooling Power kW 9 2 9 2 9 2 9 2 Rated Cooling Current A 18 18 18 18 Rated Heating Power kW 9 1 9 1 Rated Heating Current A 18 1...

Страница 12: ...ing System Diagram CXAJ065 System Diagram F N F H Heating Cooling Refrigerant reservoir Fin coil condenser Evaporator Discharge temperature sensor TH6 Discharge temperature sensor TH5 4 way valve Suct...

Страница 13: ...waterTH1 Outlet water TH2 HP1 LP1 EXVA 1 4 way valve COMP A1 COMP A2 HP2 LP2 28 6 COMP B1 COMP B2 HPS1 HPS2 TH3 EXVB 1 TH8 Refrigerant reservoir Refrigerant reservoir Cooling Facing control box left s...

Страница 14: ...ate in the system EXV Control refrigerant flow rate by adjusting opening through pressure or temperature changes Fin coil Heat Exchanger Heat exchange with outdoor air Gas liquid Separator Separate ga...

Страница 15: ...20 Water pan 1 21 Compressor 2 22 Liquid receiver 1 23 Gas liquild separator 1 24 Shell tube HX 1 25 Cover plate of shell tube HX B 2 26 Cover plate of shell tube HX C 4 27 Cover plate A 4 28 Support...

Страница 16: ...r plate of shell tube HX A 2 17 Compressor 4 18 Tube 4 2 19 Support plate of compressor B 1 20 Shock pad 16 21 Suction tube B 1 22 4 ways valve assembly B 1 23 Drier EXV assembly B 1 24 Tube 5 1 25 Wo...

Страница 17: ...15 Suction tube A 1 16 Cover plate of shell tube HX B 2 17 Cover plate C 4 18 Water pan 1 19 Compressor 2 20 Suction tube B 1 21 Cover plate of shell tube HX A 1 22 Support plate of compressor B 1 23...

Страница 18: ...al block 1 18 Snap busing A 9 19 Snap busing B 1 R A S B T C Normal Phase reveres Phase loss 98 14 95 11 96 12 O U volt P0010 CN12 U1 CN15 CN14 CN11 CN16 OUT14 OUT13 OUT1 2 OUT12 OUT11 OUT10 OUT9 OUT8...

Страница 19: ...xx TH12 TH11 TH10 TH9 TH8 TH7 TH6 TH5 TH4 TH3 TH2 TH1 OUT1 1 EXVA 1 EXVA 2 EXVB 1 EXVB 2 R A S B T C Normal Phase reveres Phase loss 98 14 95 11 96 12 O U volt MFA MFB MCA 1 MCB 1 MCA 2 MCB 2 1 2 3 4...

Страница 20: ...xx V0xx TH12 TH11 TH10 TH9 TH8 TH7 TH6 TH5 TH4 TH3 TH2 TH1 OUT1 1 EXVA 1 EXVA 2 EXVB 1 EXVB 2 R A S B T C Normal Phase reveres Phase loss 98 14 95 11 96 12 O U volt MFA MFB OVCA 1 OVCB 1 1 2 3 4 5 6 7...

Страница 21: ...on and space for maintenance and repair The unit should be installed on a level surface with reliable load bearing capacity please refer to the parameter table for unit weight and outline dimensions I...

Страница 22: ...e inlet and outlet water pipelines Install filter in the inlet pipeline of the evaporator the mesh number of the filter should be 40 Install water discharge value and pipeline at the bottom of water p...

Страница 23: ...ly connected to reduce the vibration transmission The pipes shall be connected through welding anges and the secondary galvanization or antiseptic treatment shall be performed on the welding seam and...

Страница 24: ...on the cold water side of the unit Two way three way valve installation the two way valve or three way solenoid valve shall be installed at the outlet of the fan coil to avoid complaints of waterway v...

Страница 25: ...aving water temperature sensor TH12 if the units are installed in modular mode a place for installing the temperature sensor must be reserved on the main outlet pipe of the water system so as to insta...

Страница 26: ...nits shall be safely grounded Improper grounding may cause electric shock Please ensure that the earth wire is firmly connected to the grounding terminal and grounding electrode of the unit 9 There is...

Страница 27: ...supply is connected with the communication line through the terminal The modular controller is provided with a 220VAC 12VDC 500mA DC power accessory Optimal operating temperature of modular controller...

Страница 28: ...P1 OV FAN M FAN2 H FAN1 RUN IN AL OUT AL IN RUN OUT ADC_OD_CO1 FLOW OVHT HP2 FREZ LP2 C H N COM EN SAVE TH4 CN6 CN2 TH2 TH1 TH3 SW2 A G B A CN4 TH5 TH6 4WV1 CN1 SW1 COMP1 COMP2 HT EV1 A HAT 4WV2 PUMP...

Страница 29: ...the communication line The shielded twisted pair must be connected hand in hand and no star connection shall be allowed namely 1 is connected to 2 2 is connected to 3 and 3 is connected to 4 If 1 is c...

Страница 30: ...A U N U1 Model Table Model 65 F N 22 U1 65 F H 27 U1 TH4 TH9 Short Short Power Compressor Location Description Pump Overload Switch close Connect 26 and U1 Flow Switch Connect 25 and U1 Code Switch Se...

Страница 31: ...Connect 26 and U1 Flow Switch Connect 25 and U1 Code Switch Seting reference IOM Reserved control signal for controlling water pump and heating EN SAVE AL On site wiring Factory wiring FAN PUMP HT EV...

Страница 32: ...H TH4 TH9 Compressor Location Description Pump Overload Switch close Connect 26 and U1 Flow Switch Connect 25 and U1 Code Switch Seting reference IOM Reserved control signal for controlling water pump...

Страница 33: ...s Starting order of the unit Cooling mode 1 Starting process for cooling mode Select cooling mode start the unit display water temperature the electronic expansion valve reaches initial opening after...

Страница 34: ...Do not press frequently 2 Mode selection Includeing cooling mode and heating mode Mode should be selected a fter shut down 3 Value browse Press rstly then press to browse the value 4 Leaving water te...

Страница 35: ...opening value in defrost 480step 100step 10step 48 480step 35 Temperature difference of electric heater start 20 0 1 10 36 Temperature difference of electric heater stop 20 0 1 6 45 Mandatory defrost...

Страница 36: ...s please drain the pipeline 6 6 Non fault Phenomenon Phenomenon Fault Display Reason The outdoor fan does not operate during heating None Defrosting Part of the fan does not operate None The heating a...

Страница 37: ...system A 78 78 Switch off the compressor of the system A If this fault occurs twice switch off and give an alarm 26 CN14 Low pressure overrun of system B 7A 7A Switch off the compressor of the system...

Страница 38: ...displays corresponding alarm code Fault reason The interface is loose open short of the sensor the main control interface is disconnected or short circuited Fault handling process Error Error Yes Yes...

Страница 39: ...cation failure between modules unable to start the unit Fault handling process In addition if the input voltage of the transformer provided with PCB is too low it will cause low voltage in PCB and the...

Страница 40: ...volume is correct Check if the radiator is blocked or inefficient Check if the system is blocked or there is any refrigerant leakage Refill refrigerant or clean the radiator Check if the EEV is closed...

Страница 41: ...the required extent Check if the suction gas superheat is too high Replace the electronic expansion value or refresh the control program Error Error Error Error Error Error Error Error System overcur...

Страница 42: ...ion See P6 for the ambient temperature range for the reasonable operation of the unit If the range is exceeded before starting the unit the unit will not be able to be started and a fault code will be...

Страница 43: ...up of coil 2 Common reasons a There is air and moisture in the cooling system which affects the coil insulation and leads to long term operation under high temperature and high pressure and consequent...

Страница 44: ...t on electronic expansion valve body Connect to main board interface Electronic expansion valve coil Electronic expansion valve body Copper pipe interface E Compressor wear Compressor wear is usually...

Страница 45: ...ion and repair process of electronic expansion valve If there is a click sound after connecting power Check if the coil is properly fit to the body Check if the conductors are properly connected with...

Страница 46: ...f throttle is normal and if the evaporating temperature is normal during normal operation of the unit Check if the temperature sensor and system pressureare normal and if the installation is correct C...

Страница 47: ...he cooling system before installation to prevent foreign objects from jamming the valve body again E Notes for use of electronic expansion valve a Do not use valve body and coil with different brands...

Страница 48: ...fault for pressure switch is normally open or normally close which means the pressure is always in open or close status and does not respond to pressure changes no matter the system pressure If you u...

Страница 49: ...nected with outdoor unit and the other two pipes are also connected to create a cooling cycle When the solenoid coil is on the magnetic effect generated by the solenoid coil will overcome the force of...

Страница 50: ...s insufficient pressure difference needed for direction change h The circulation volume of refrigerant in compressor does not meet the requirement for direction change of four way valve i The necessar...

Страница 51: ...The controller will display H1 System A or H2 System B otherwise the system will continue running The disconnecting value is 4 4Mpa the reconnect value is below 3 5Mpa In case of this alarm please che...

Страница 52: ...ped When the fault occurs the Cooling plate type heat exchanger anti freezing locking time will be triggered when the time is over and the discharge temperature Cooling anti freezing stopping temperat...

Страница 53: ...tarted then the remained compressor in the system where the first compressor is picked will be selected as the third compressor to be started the final compressor will be the fourth to be started The...

Страница 54: ...pressure switch trips or the discharge water temperature Cooling anti freezing starting temperature fan coil plate type heat exchanger 2 the system will switch from defrosting to heating mode The low...

Страница 55: ...1 16 55 63 58 2 60 89 35 6 797 6 916 7 036 86 1 333 1 4 1 47 15 53 07 55 47 57 98 36 6 554 6 673 6 794 87 1 296 1 362 1 431 14 50 65 52 89 55 22 37 6 321 6 441 6 562 88 1 26 1 325 1 393 13 48 35 50 44...

Страница 56: ...09 1 323 3 338 353 2 60 23 64 24 8 26 01 121 3 352 3 654 3 982 0 307 9 321 6 335 7 61 22 79 23 92 25 1 122 3 261 3 556 3 877 1 293 3 306 1 319 2 62 21 97 23 08 24 23 123 3 172 3 461 3 775 2 279 5 291...

Страница 57: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications wi...

Отзывы: