BAS-SVX45F-GB
31
Wiring Inputs and Outputs
Wiring 0–10 VDC Analog Inputs
Connect 0–10 VDC analog inputs to sensors such as indoor air quality sensors and pressure
sensors. Wiring can be done on the top tier or the bottom tier by using a combination of universal
and analog input terminations.
To wire a 0–10 VDC analog input:
1.
Connect the shield wire (as common connection) to a common terminal as shown in
.
2. Connect the signal wire to an available input terminal.
3. Connect the supply wire to a 24 VDC or 24 VAC terminal as required.
4. Use the Tracer TU service tool to configure the analog input that references the corresponding
hardware termination.
Figure 11. Typical wiring, 0–10 VDC
IMC
IMC
AO
6
UI
14
AO
5
UI
13
AO
4
UI
12
AO
3
UI
11
AO
2
UI
10
AO1
UI
9
BO
4
BO
3
BO
2
BO
1
RELAYS
0
.
5
A MAX
1
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+
24
VDC
LINK
OUT
+
24
VDC
+
24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVICE
LINK
ACT
IMC
MBUS
LINK
RX
TX
UC
600
ADDRESS
0 1
2
3
4
56
7
8
9
x1
0 1
2
3
4
56
7
8
9
x10
0 1
2
3
4
56
7
8
9
x100
BO
4
BO
3
BO
2
BO
1
24 VDC
0-10 VDC ou
t
Common
24 VDC
0-10 VDC out
Common
Top tier wiring: Connect to any
universal input (UI1 through UI8).
Bottom tier wiring: Connect to any
AO/UI input. Connect 24 VDC wire to
available 24 VDC on top tier.