Trane Belimo B2 Series Скачать руководство пользователя страница 2

4

7

5

6

Specifications

Supply Voltage

: 24Vac, 50-60Hz

Power Consumption

: 1 VA

Control Type

: 24Vac 3-wire floating point or 2-10Vdc analog

Nominal 90° Valve Open Cycle Time

: 90s @ 60Hz, 108s @ 50Hz

Electrical Termination

: 8” plenum rated cable with AMP 172166-1 3-

position connector

Operating Ambient Temperature

: -30 to 50°C (-22 to 122°F)

Minimum and Maximum Fluid Temperature

: 0 to 94°C (32 to 201°F)

Shipping and Storage Temperature

: -40 to +80°C (-40 to 176°F)

Atmosphere

: Non-corrosive, non-explosive

Close Off Pressure

: 1.38 mPa (200 psi)

Rated Body Pressure

: 4.14 mPa (600 psi)

Valve Body

: Brass

Valve Ball

: Chrome plated brass

Valve Ball Seals

: PTFE+5% graphite

Valve Ball Stem

: Nickel plated brass

Actuator Cover

: Fire-retardant GRPA6-230

Actuator Chassis

: Reinforced nylon GRPA6-230

Actuator Gear

: GRPA6-230 + Brass HPb59-1 + iron-base powder

metallurgy

Flow Characteristics

: Linear, Equal Percentage

Note:

The specifications above are nominal and conform to generally

acceptable industry standards. Belimo or Trane is not responsible for
damages resulting from misapplication or misuse of its products.

Table 1.

Modulating CCV - 3-wire floating point

Type

X-Code

Kv

Cv

Thread

Pressure (Mpa)

Close off

Rated Body

2-way

X15333105010

0.26

0.30

1/2” NPT

1.4

4.14

X15333105020

0.40

0.46

X15333105030

0.69

0.80

X15333105040

1.03

1.20

X15333105050

1.64

1.90

X15333105060

2.59

3.00

X15333105070

4.05

4.70

3-way

X15333106010

0.26

0.30

1/2” NPT

1.4

4.14

X15333106020

0.40

0.46

X15333106030

0.69

0.80

X15333106040

1.03

1.20

X15333106050

1.64

1.90

X15333106060

2.59

3.00

X15333106070

4.05

4.70

Table 2.

Modulating CCV - 2-10Vdc analog

Type

X-Code

Kv

Cv

Thread

Pressure (Mpa)

Close Off

Rated Body

2-way

X15333107010

0.26

0.30

1/2” NPT

1.4

4.14

X15333107020

0.40

0.46

X15333107030

0.69

0.80

X15333107040

1.03

1.20

X15333107050

1.64

1.90

X15333107060

2.59

3.00

X15333107070

4.05

4.70

3-way

X15333108010

0.26

0.30

1/2” NPT

1.4

4.14

X15333108020

0.40

0.46

X15333108030

0.69

0.80

X15333108040

1.03

1.20

X15333108050

1.64

1.90

X15333108060

2.59

3.00

X15333108070

4.05

4.70

Dimensions and Positions

Figure 1.

Valve dimensions

2.38

4.00`.03

2.45

3.31

2.63

8.00`1.00

2.39

1.29

4.55`.03

PORT A

PORT B

PORT AB

 2

Figure 2.

Flow pattern

Installation

WARNING

Hazardous Voltage!

Failure to disconnect power before servicing could result in death or serious
injury.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is present with a voltmeter.

1. Read instructions carefully. Failure to follow them could damage the

product or cause hazardous condition.

2. Check ratings given in instructions and on product to make sure the

product is suitable for your application.

3. Installer must be a trained and experienced service technician.
4. See

Figure 1

for actuator dimensions, and

Figure 3

for exploded view.

5. Always conduct a thorough check-out when installation is completed.
6. While not necessary to remove the actuator from the body, it can be

removed for ease of installation. The orientation of the actuator must
be set as shown in

Figure 2

.

7. An extra 4 inches (101 mm) head clearance above the actuator is

required to remove the actuator.

Note:

For trouble-free operation of the product, good installation

practice must include initial system flushing, chemical water treatment,
and the use of a 50 micron (or finer) system side stream filter(s).