Specifications
Supply Voltage
: 24Vac, 50-60Hz
Power Consumption
: 1 VA
Control Type
: 24Vac 3-wire floating point or 2-10Vdc analog
Nominal 90° Valve Open Cycle Time
: 90s @ 60Hz, 108s @ 50Hz
Electrical Termination
: 8” plenum rated cable with AMP 172166-1 3-
position connector
Operating Ambient Temperature
: -30 to 50°C (-22 to 122°F)
Minimum and Maximum Fluid Temperature
: 0 to 94°C (32 to 201°F)
Shipping and Storage Temperature
: -40 to +80°C (-40 to 176°F)
Atmosphere
: Non-corrosive, non-explosive
Close Off Pressure
: 1.38 mPa (200 psi)
Rated Body Pressure
: 4.14 mPa (600 psi)
Valve Body
: Brass
Valve Ball
: Chrome plated brass
Valve Ball Seals
: PTFE+5% graphite
Valve Ball Stem
: Nickel plated brass
Actuator Cover
: Fire-retardant GRPA6-230
Actuator Chassis
: Reinforced nylon GRPA6-230
Actuator Gear
: GRPA6-230 + Brass HPb59-1 + iron-base powder
metallurgy
Flow Characteristics
: Linear, Equal Percentage
Note:
The specifications above are nominal and conform to generally
acceptable industry standards. Belimo or Trane is not responsible for
damages resulting from misapplication or misuse of its products.
Table 1.
Modulating CCV - 3-wire floating point
Type
X-Code
Kv
Cv
Thread
Pressure (Mpa)
Close off
Rated Body
2-way
X15333105010
0.26
0.30
1/2” NPT
1.4
4.14
X15333105020
0.40
0.46
X15333105030
0.69
0.80
X15333105040
1.03
1.20
X15333105050
1.64
1.90
X15333105060
2.59
3.00
X15333105070
4.05
4.70
3-way
X15333106010
0.26
0.30
1/2” NPT
1.4
4.14
X15333106020
0.40
0.46
X15333106030
0.69
0.80
X15333106040
1.03
1.20
X15333106050
1.64
1.90
X15333106060
2.59
3.00
X15333106070
4.05
4.70
Table 2.
Modulating CCV - 2-10Vdc analog
Type
X-Code
Kv
Cv
Thread
Pressure (Mpa)
Close Off
Rated Body
2-way
X15333107010
0.26
0.30
1/2” NPT
1.4
4.14
X15333107020
0.40
0.46
X15333107030
0.69
0.80
X15333107040
1.03
1.20
X15333107050
1.64
1.90
X15333107060
2.59
3.00
X15333107070
4.05
4.70
3-way
X15333108010
0.26
0.30
1/2” NPT
1.4
4.14
X15333108020
0.40
0.46
X15333108030
0.69
0.80
X15333108040
1.03
1.20
X15333108050
1.64
1.90
X15333108060
2.59
3.00
X15333108070
4.05
4.70
Dimensions and Positions
Figure 1.
Valve dimensions
2.38
4.00`.03
2.45
3.31
2.63
8.00`1.00
2.39
1.29
4.55`.03
PORT A
PORT B
PORT AB
2
Figure 2.
Flow pattern
Installation
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is present with a voltmeter.
1. Read instructions carefully. Failure to follow them could damage the
product or cause hazardous condition.
2. Check ratings given in instructions and on product to make sure the
product is suitable for your application.
3. Installer must be a trained and experienced service technician.
4. See
for actuator dimensions, and
for exploded view.
5. Always conduct a thorough check-out when installation is completed.
6. While not necessary to remove the actuator from the body, it can be
removed for ease of installation. The orientation of the actuator must
be set as shown in
.
7. An extra 4 inches (101 mm) head clearance above the actuator is
required to remove the actuator.
Note:
For trouble-free operation of the product, good installation
practice must include initial system flushing, chemical water treatment,
and the use of a 50 micron (or finer) system side stream filter(s).