Economizer Controller
16
ACC-SVN203C-EN
SETPOINTS
EXH2 SET
75%
0 to 100%;
increment by 1
N/A
EXH2 SET is not available
SYSTEM
SETUP
INSTALL
1/1/2011
Present date
Display order = MM/DD/YY
Setting order = DD, MM, then YY
UNITS DEG
ºF
°F or °C
ºF
Sets economizer controller in degrees Fahrenheit or
Celsius
EQUIPMENT
CONV
CONV
HP
CONV
CONV = conventional
HP is not available
AUX2 I
N/A
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
Heat (W1)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating
mode
NOTE: If using 2-speed fan mode, you must
program CONV mode for W. Shutdown is not
available in the two-speed fan mode
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat
FAN SPEED
1 speed
1 speed/
2 speed
See unit
nameplate:
Digit 15 = 0 or 1 - 1
speed;
Digit 15 = 7 or 9 - 2
speed
Sets economizer controller for operation of 1 speed
or 2 speed supply fan. The controller does not
control the fan but positions the OA and RA dampers
to the heating or cooling mode. See
page 23 for modes and position
NOTE: 2-speed fan option also needs Heat (W1)
programmed in AUX 2 In
FAN CFM
5000cfm
100 to 15000
cfm;
increment by
100
5000cfm
This is the capacity of the RTU. The value is found
in the Unit Catalog. The cfm of the fan is only used
with DCV CAL ENABLE AUO
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
NONE
AUX1 OUT is a programmable output used for
System Alarm output
OCC
INPUT
INPUT or
ALWAYS
ALWAYS
When using a setback thermostat with occupancy
out (24 Vac), the 24 Vac is input “INPUT” to the OCC
terminal. If no occupancy output from the
thermostat then change program to “ALWAYS” OR
add a jumper from terminal R to OCC terminal
FACTORY DEFAULT
NO
NO or YES
NO
Resets all set points to factory defaults when set to
YES. LCD will briefly flash YES and change to NO but
all parameters will change to factory default values
ADVANCED
SETUP
MA LO SET
45ºF
35 to 55°F;
increment by 1°F
45ºF
Temp to activate Freeze Protection (close damper or
modulate to MIN POS if temp falls below set value)
FREEZE POS
CLO
CLO
MIN
CLO
Damper position when freeze protection is active
(closed or MIN POS)
CO
2
ZERO
0ppm
0 to 500 ppm;
increment by 10
0ppm
CO
2
ppm level to match CO
2
sensor start level. 0-
10 Vdc CO
2
sensors require CO2 ZERO to be 400
CO
2
SPAN
2000ppm
1000 to 3000
ppm;
increment by 50
2000ppm
CO
2
ppm span to match CO
2
sensor; e.g.; 500-1500
sensor output would be 500 CO
2
zero and 1000 CO
2
span. 0-10 Vdc CO
2
sensors require CO
2
SPAN to be
1600
STG3 DLY
2.0h
0 min, 5 min, 15
min, then 15
min intervals.
Up to 4h or OFF
2.0h
Delay after stage 2 for cool has been active. Turns
on 2nd stage of mechanical cooling when
economizer is 1st stage call and mechanical cooling
is 2nd stage call. Allows three stages of cooling, 1
economizer and 2 mechanical. OFF = no Stage 3
cooling
Table 4.
Controller menu structure (continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and
Increment
(a)
Parameter
Recommended
Value
(b)
Notes