General Information

ACC-SVN67M-EN

General

ALL phases of this installation must comply with NATIONAL, 
STATE AND LOCAL CODES. Installer must mark unit 
nameplate with heater information per instructions on 
nameplate.

Note:

If digit 9 in the unit model number equals “E” 
(electromechanical control), accessory relay 
BAY24X042 is required if the thermostat does not 
energize the fan circuit in the heating mode. See 

Figure 1

 for wiring information.

Inspection 

1. Unpack all components of the kit.
2. Check carefully for any shipping damage. If any damage is 

found it must be reported immediately and a claim made 
against the transportation company.

3. Check the heater nameplate model number and compare 

with the electrical data tables. Ensure that the available 
power supply and unit's model number complies with the 
particular heater being used.

BAYHTRW309

TSC090H3

WSC072H3

BAYHTRW318

TSC090H3

WSC072H3

BAYHTRW327

TSC090H3

WSC072H3

BAYHTRW336

TSC090H3

WSC072H3

BAYHTRW409

TSC090H4

WSC072H4

BAYHTRW418

TSC090H4

WSC072H4

BAYHTRW427

TSC090H4

WSC072H4

BAYHTRW436

TSC090H4

WSC072H4

BAYHTRWW18

TSC090HW

WSC072HW

BAYHTRWW27

TSC090HW

WSC072HW

BAYHTRWW36

TSC090HW

WSC072HW

(a) These kits to be used with Title 24/SZVAV models.

Table 1. Heater information (continued) 

Model Number

Used With

Figure 1. Electromechanical wiring diagram

Содержание BAY24X042

Страница 1: ...and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe...

Страница 2: ...ous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or prope...

Страница 3: ...ment are the trademarks of their respective owners Revision History Updated Heater Model Number for WSC120H3 in Electrical Data chapter WARNING Follow EHS Policies Failure to follow instructions below...

Страница 4: ...4 ACC SVN67M EN Table of Contents General Information 5 General 7 Inspection 7 Installation 8 Electrical Data 12...

Страница 5: ...H3 a WHC074H3 WHC092H3 WHC102H3 THC102F3 WSC120H3 BAYHTRA327 TSC120H3 WSC090H3 a THC074F3 TZC072F3 WSC102H3 a WSC120H3 THC092F3 TZC090F3 THC102F3 TZC102F3 TSC092H3 TSC102H3 WSC092H3 a WHC074H3 WHC092H...

Страница 6: ...HC120H4 BAYHTRB436 WHC120H4 BAYHTRB454 WHC120H4 BAYHTRBW18 TZC120FW WHC120HW BAYHTRBW36 WHC120HW BAYHTRBW54 WHC120HW BAYHTRD318 THC120E3 TZC120F3 BAYHTRD327 THC120E3 TZC120F3 BAYHTRD336 THC120E3 BAYHT...

Страница 7: ...must be reported immediately and a claim made against the transportation company 3 Check the heater nameplate model number and compare with the electrical data tables Ensure that the available power s...

Страница 8: ...the same as any in this table and the application is for horizontal airflow the limit control TCO A must be replaced with the extra limit control shipped with the heater Replace TCO A following the in...

Страница 9: ...rt rod hanger The BAYHTRA BAYHTRB and BAYHTRD models will have a guide rod and a support bracket to help with the installation See Figure 5 Be very careful to avoid dragging the heater element on the...

Страница 10: ...ush against center post and secure each door stop with 1 or 2 screws See zoom view in Figure 8 or Figure 9 14 Remove the wire nuts from W1 W2 and W3 15 For models with the control box in the outdoor s...

Страница 11: ...with ohmmeter and verify that heater element terminals are electrically isolated from cabinet and ground infinite resistance On downflow units with or without duct work installed or horizontal units w...

Страница 12: ...nimum allowable airflow for a TSC120EF TZC120F and THC120E with a 54 kW heater is 3400 cfm e The minimum allowable airflow for a WSC120 with a 54 kW heater is 4000 cfm Table 4 Unit wiring with electri...

Страница 13: ...35 34 35 33 35 7 5 c TSC092H4 BAYHTRT427 BAYHTRA427 d 27 2 44 45 48 50 47 50 7 5 c TSC092H4 BAYHTRT436 BAYHTRA436 d 36 2 58 60 61 70 60 60 8 5 TSC102H4 BAYHTRT409 BAYHTRA409 d 9 1 21 25 23 25 22 25 8...

Страница 14: ...er Model Number Heater kW Rating Control Stages Standard Indoor Fan Motor a Oversized Indoor fan Motor Optional EBM Fan Motor MCA Max Fuse Size or Max Circuit Breaker MCA MaxFuseSize or Max Circuit Br...

Страница 15: ...1 34 40 35 40 34 40 8 5 WSC102H4 BAYHTRU418 BAYHTRA418 18 0 1 47 50 49 50 48 50 8 5 WSC102H4 BAYHTRU427 BAYHTRA427 27 0 2 61 70 62 70 61 70 8 5 WSC102H4 BAYHTRU436 BAYHTRA436 36 0 2 74 80 76 80 75 80...

Страница 16: ...or Max Circuit Breaker MCA Max Fuse Size or Max Circuit Breaker 208 230 Volts Three Phase 6 WHC074H3 BAYHTRA309 6 8 9 0 1 66 69 70 70 6 WHC074H3 BAYHTRA318 13 5 18 0 1 89 96 90 100 6 WHC074H3 BAYHTRA...

Страница 17: ...nnection high efficiency and eFlex 6 to 10 tons Standard Indoor Motor Oversized Indoor Motor Tons Unit Model Number Heater Model Number Heater kW Rating a Control Stages MCA Max Fuse Size or Max Circu...

Страница 18: ...AYHTRA409 9 0 1 18 9 25 6 THC074F4 BAYHTRA418 18 0 1 32 5 35 6 THC074F4 BAYHTRA427 27 0 2 46 0 50 460 Volts Three Phase 6 THC074F4 BAYHTRA436 36 0 2 59 5 60 6 TZC072F4 BAYHTRA409A 9 1 10 8 26 6 TZC072...

Страница 19: ...egrees C b Degrees F c 6 Ton 7 5 Ton 10 Ton 6 Ton 7 5 Ton 10 Ton kW Voltage Stages 4100 M3 H 5100 M3 H 6800 M3 H kW Voltage Stages 2400 cfm 3000 cfm 4000 cfm WSC072ED WSC090ED WSC120 ED WSC072ED WSC09...

Страница 20: ...umCircuit Breaker TSC072ED BAYHTRS418 11 3 13 5 39 47 1 26 9 28 9 35 35 28 1 30 1 35 35 BAYHTRS427 16 9 20 2 58 69 2 37 5 40 5 40 45 38 8 41 8 40 45 BAYHTRS436 22 6 26 9 78 92 2 48 3 52 1 50 60 49 5 5...

Страница 21: ...Notes ACC SVN67M EN 21...

Страница 22: ...Notes 22 ACC SVN67M EN...

Страница 23: ...Notes ACC SVN67M EN 23...

Страница 24: ...cations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and reside...

Отзывы: