Table 2. General data (SI)
Unit Size (tons)
140
160
180
200
215
230
Compressor Model
Quantity
#
4
4
6
6
6
6
Tonnage/ckt
(a)
30+40
40+40
30+30+30
30+30+40
30+40+40
40+40+40
Evaporator
Water storage
l
66.0
66.0
66.0
66.0
66.0
81.8
Min. flow
(b)
l/s
10.6
12.1
13.6
15.1
16.3
17.4
Max. flow
l/s
31.8
36.3
40.9
45.4
48.8
52.2
Water connection
mm
101.6
101.6
101.6
101.6
101.6
101.6
Condenser
Quantity of coils
#
8
8
10
10
12
12
Coil length
mm
1914
1914
1914
1914
1914
1914
Coil height
mm
1252
1252
1252
1252
1252
1252
Tube width
mm
25.4
25.4
25.4
25.4
25.4
25.4
Fins per foot
(fpf)
276
276
276
276
276
276
Fan
Quantity
#
8
8
10
10
12
12
Diameter
mm
914
914
914
914
914
914
Airflow per fan
m3/h
19262
19257
19260
19257
19262
19258
Power per motor
kW
2.2
2.2
2.2
2.2
2.2
2.2
Motor RPM
rpm
820
820
820
820
820
820
Tip speed
m/s
39.3
39.3
39.3
39.3
39.3
39.3
General Unit
Refrigerant circuits
#
2
2
2
2
2
2
Capacity steps
%
21-43-
71-100
25-50-
75-100
17-33-50-
67-83-100
15-30-50-
65-80-100
14-32-50-
64-82-100
17-33-50-
67-83-100
Min ambient - low/wide
°C
-29
-29
-29
-29
-29
-29
Min ambient - std/high
°C
0
0
0
0
0
0
Refrig charge/ckt
kg
28.6
32.7
36.8
40.8
43.9
47.0
Oil charge/ckt
l
12
12
18
18
18
18
Pump Package (Single Pump)
Avail Head Pressure
(c)
kPa
284
297
267
270
302
272
Power per motor
HP
21.4
22.3
23.2
27.3
27.1
26.3
Pump Package (Twin Pump)
Avail Head Pressure
kPa
272
280
247
245
274
240
Power per motor
HP
20.9
22.6
22.9
27.1
26.3
26.5
(a)
Data shown for one circuit only. The second circuit always matches.
(b)
Minimum and maximum flow rates apply to constant-flow chilled water system running at AHRI conditions, without freeze inhibitors added to the water
loop.
(c)
Pump available head pressure is based on 44/54° evaporator water, .0001 hr-ft-°F/Btu, 95°F ambient and 0 ft. elevation.