Trane AM7A0C36H31SA Series Скачать руководство пользователя страница 7

 

7

 

AM7A0C36H31-SF-1A

dip Switch S1

Set the S1-1 and S1-2 dip switches for the OD 

 

multiplier (tonnage) per the chart.

Set the S1-3 dip switch for AC or HP.

 

OD TYPE

S1‐3

HP

OFF

AC

ON

S1

Airflow Control (AFC)

1

1

1
2
3
4
5

1
2
3
4
5

HP

2 (Compressor)

2 (Stages)

AC (System)

}

OUTDOOR

Capacity (Tons)

OUTDOOR

}

Torque

CFM/Ton

Cool Off Delay

}

INDOOR

CFM

+12V

R13

R14

R1

R4

1

U1

R NET 1

S1

on

on

S2

R NET 2

R

6

C

22

C

19

C

15

C

12

C

18

C

21

C10

D9

L1

R22

Set the S1-4 dip switch for the number of stages 

 

on the outdoor unit.

OD STAGES

S1‐4

1

OFF

2

ON

Set the S1-5 dip switch for the number of 

 

compressors.

# COMPRESSORS

S1‐5

1

OFF

2

ON

16 SEER = 1 Compressor
19 SEER = 2 Compressors
20 SEER = 2 Compressors

16 SEER = 2 Stages
19 SEER = 2 Stages
20 SEER = 2 Stages

INDOOR MODEL

S1‐1

S1‐2

OD MULTIPLIER

OFF

OFF

3

OFF

ON

2

ON

OFF

2.5

ON

ON

3.5

* May be "A" or "T"

*AM7A0C36H31SA

NOTE: The OD multiplier in conjuction with the CFM/TON can 
be used to adjust total airflow for your application.  Example: 
4.5T x 370 CFM/TON = 1665 CFM

Содержание AM7A0C36H31SA Series

Страница 1: ...ESSURE BEFORE OPENING THE SYSTEM DO NOT USE NON APPROVED REFRIGERANTS OR REFRIGERANT SUBSTITUTES OR REFRIGERANT ADDITIVES WARNING LIVE ELECTRICAL COMPONENTS During instal lation testing servicing and...

Страница 2: ...AM7A0C36H31 SF 1A 2 WIRING DIAGRAM FOR AM7A0C36H31SA...

Страница 3: ...stage control circuit 3 R G contacts close on comfort control sending 24VAC to the G terminal of the AFC 4 The AFC micro processor sends a command to the serial communicating blower motor to run at 1...

Страница 4: ...to the AFC for that correct cfm The EHC determines the amount of heat per stage by either factory programming or by the kw jumper position 5 The AFC micro processor sends a command to the serial commu...

Страница 5: ...ults that have occurred Each device will report the last four faults after each power cycle of the unit See the Fault Table section in the Service Facts for a list of fault codes Clearing Faults To cl...

Страница 6: ...R3 R2 R5 R7 Q8 Q4 PTC1 MOV1 L2 L3 K1 J3 J6 J9 D36 D35 D34 D1 D22 D29 D25 D24 D7 D4 D2 D28 C57 C54 C56 C51 C49 C48 C47 C52 C43 C42 C36 C35 C34 C31 C30 C29 C13 C7 C3 C2 C1 U1 C58 R105 C50 U2 J7 R24 R17...

Страница 7: ...C22 C19 C15 C12 C18 C21 C10 D9 L1 R22 Set the S1 4 dip switch for the number of stages on the outdoor unit OD STAGES S1 4 1 OFF 2 ON Set the S1 5 dip switch for the number of compressors COMPRESSORS S...

Страница 8: ...minute FAN OPERATION CFM COMPRESSOR OPERATION ON OFF as required S2 1 1 1 2 3 4 5 1 2 3 4 5 HP 2 Compressor 2 Stages AC System OUTDOOR Capacity Tons OUTDOOR Torque CFM Ton Cool Off Delay INDOOR CFM 12...

Страница 9: ...s 879 68 876 110 877 153 881 197 884 240 400 CFM ton CFM Watts 992 91 991 138 998 188 1005 237 1014 287 370 CFM ton CFM Watts 923 77 924 121 927 167 932 213 936 258 420 CFM ton CFM Watts 1036 101 1040...

Страница 10: ...7 50 BAYEVAC10LG3 1 3 PH 9 60 32785 23 1 32 35 7 20 24589 20 0 28 30 BAYEVBC15LG3 1 3 PH 14 40 49178 34 6 47 50 10 80 36883 30 0 41 45 9 60 32785 40 0 54 60 7 20 24589 34 6 47 50 4 80 16392 20 0 25 25...

Страница 11: ...J7 R24 R17 D6 D3 D14 D17 R NET 1 R NET 2 R73 1 J8 Yo R B O Y1 J1 W2 W1 R63 R62 R56 D21 D20 C32 C33 R38 R36 R16 R15 R32 R11 R28 R27 R26 D13 D12 D5 D11 D10 C24 C25 C4 C5 C16 C17 D8 R50 R45 R85 R84 D16...

Страница 12: ...C has detected a fault condition refer to Fault LED on EVC 12 EHC HHC has detected a fault condition refer to Fault LED on EHC HHC 1 If Unit LED on AFC is flashing 2 times second AFC is causing the er...

Страница 13: ...l 1 4 Evaporator Gas Sensor input out of range Verify resistance 5VDC output from control 1 5 Stepper Motor Coil is shorted Replace coil 2 6 Valve is not responding to a change in position Possible st...

Страница 14: ...E Standby mode STATUS LED will flash 1 time per second Unit LED 1 Flash Normal Rapid Communication Busy Error Off No power EHC STATUS LEDS EHC FAULT CODES EHC Fault LED Description OFF No fault 1 Inte...

Страница 15: ...eak and make to initialize To clear faults stored in memory apply a jumper between Close and Test pins for 10 seconds Open Valve Test Touch OPEN pin to TEST pin EEV drives open 5 sec max and stays ope...

Страница 16: ...1 82 63 17 2 13824 1 79 64 17 8 13476 1 76 65 18 3 13138 1 73 66 18 9 12810 1 70 67 19 4 12491 1 67 68 20 0 12181 1 65 69 20 6 11879 1 62 70 21 1 11586 1 59 TEMP F TEMP C THERMISTOR RESISTANCE OHMS V...

Страница 17: ...J3 connector on EVC See EVC table for J3 location Does voltage s measured correspond to return air temperature Verify resistance per Thermal Resistance Table and Voltage table Sensors are good No remo...

Страница 18: ...at drop below 30F Is indoor temperature 85F NO Perform CLOSE VALVE test at EVC YES Does suction pressure go down EEV and coil are working Replace EVC Check operation YES YES Perform temperature sensor...

Страница 19: ...check YES Perform CLOSE VALVE test at EVC Does suction pressure drop Perform OPEN VALVE test at EVC Does suction pressure rise Replace EVC YES Replace EVC YES Replace EEV Check operation Ohm coil per...

Страница 20: ...7 www trane com For more information contact your local dealer distributor 01 11 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change de...

Отзывы: