Installation
58
AFDR-SVN001D-EN
Existing UC800 with Software
Already Installed
1. If an AFDR retrofit is installed on an RTHD chiller with
an existing UC800 controller/Tracer AdaptiView™
display, the software installation will be slightly
different than in
“UC800 Software Installation and
. Because the UC800 already has
code and configurations installed, when Tracer™ TU is
launched on the service laptop with a direct USB
connection to the controller, Tracer TU displays its
Unit Summary
tab; refer to
2. If a Chiller Service Report has not already been
generated, Trane recommends creating one at this
time. Select
Reports > Chiller Service
to open the
Chiller Service Report dialog box, and save the report
both as XML and PDF (check
Convert Report to PDF
).
Be sure to note the location where the files will be
stored, or use
Browse
to specify a different location.
Click
Save
.
Figure 97.
Figure 98.