Installer’s Guide

RETURN AIR FILTERS FOR UPFLOW FURNACE
IN HORIZONTAL CONFIGURATION

When the Upflow Furnace is installed in a horizontal configu-
ration, the filter must never be installed inside or outside the
cabinet directly above the blower assembly. See Figure 11
(page 9). Remote filter grilles may be used for homeowner
convenience or the filters may be installed in the duct work
upstream of the furnace.  See Figures 11 (page 9) and 21 (page
11).

ALTERNATE UPFLOW
FILTER CLIP / BRACKET INSTALLATION - KIT09224

1. Determine the location to be used. The furnace cabinet

has dimples for location of the alternate furnace clips
(

Side return only

).  Pre-drill clearance holes with a

3/16" drill.  Bottom return holes are pre-drilled.

2. Install the clips in front and rear of the desired location

using the screws provided.  The filter clip with the leaf
spring mounts in the rear of the cabinet.  See Figure 22.

REAR

SIDE

CUT

-OUT

ALTERNATE FILTER
CLIPS LOCATION

s

UNIT

SIZE

RETURN AIR

BOTTOM

SIDE

14-1/2"

CUT ON LINE DO NOT CUT

17-1/2"

DO NOT CUT

DO NOT CUT

21"

DO NOT CUT CUT ON LINE

24-1/2"

DO NOT CUT CUT ON LINE

TABLE 6

INSTALLING THE OPTIONAL FILTER

The filter may need to be cut to fit the unit depending on the
location of the return air filter.

A score line and the words “CUT HERE” are located on the
end of the filter.  If your application requires cutting the filter,
do so as indicted by the score mark.

TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS

Two high velocity type air filters are required for each down-
flow furnace.   Downflow furnace filters must be located
outside the furnace cabinet.  Typical installations are shown
in Figures 23 and 24. Tables 7 and 8 provide information for
installation of the filter retaining brackets shipped with
downflow furnaces.

Optional horizontal filter conversion kits are BAYFLTR203
for 17 1/2"  width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets.  These
include filters and brackets necessary for horizontal filters.
In addition, optional door kit BAYFLTR206 is also available.
See Figures 21 and 24.

Airflow

Airflow

d

f

CABINET

WIDTH

RETURN

DUCT

WIDTH

FILTER ACCESS

OPENING -

DIMENSION "A"

FILTER ACCESS

OPENING -

DIMENSION "B"

14-1/2"

13-1/4"

12"

14"

17-1/2"

16-1/4"

15"

14"

21"

19-3/4"

19-1/2"

14"

24-1/2"

23-1/4"

22"

14"

TABLE 7

CABINET

WIDTH

FILTER

SIZE

FILTER BRACKET

LOCATION *

14-1/2"

2 - 14X20X1

12-7/8"

17-1/2"

2 - 16X20X1

14-3/8"

21"

2 - 16X20X1

13-1/8"

24-1/2"

2 - 16X20X1

11-5/8"

* Location dimension is from end of duct to the screw holes for the bracket.

TABLE 8

Optional door kit
BAYFLTR206

Содержание ADX2B060A9362A

Страница 1: ...ler s Guide __First letter may be A or T Upflow Horizontal Downflow Horizontal Gas Fired Direct Vent 2 Stage Condensing Furnaces with Variable Speed Inducer A341624P03 UX2B060A9362A UX2B080A9422A UX2C...

Страница 2: ...result in serious injury death or property damage Improper servicing could result in dangerous operation serious injury death or property damage CARBON MONOXIDE POISONING HAZARD Failure to follow the...

Страница 3: ...cial venting systems which must be gas tight and water tight These Category IV Direct Vent furnaces are approved for installa tion in Manufactured Mobile housing when used with BAYMFGH001A LOCATION AN...

Страница 4: ...B080A9422A 17 1 2 2 1 4 16 1 4 16 7 1 2 2 UX2C100A9482A 21 2 1 2 19 3 4 19 1 2 9 3 UX2D120A9602A 24 1 2 2 15 16 23 1 4 23 10 3 Prefix May Be A or T Notes 1 UX2D120A9602A Requires 3 Diameter Vent Pipe...

Страница 5: ...See Note 1 DIM A DIM B DIM C DIM D DX2B060A9362A DX2B080A9422A 17 1 2 2 1 4 16 1 4 16 DX2C100A9482A 21 2 1 2 19 3 4 19 1 2 DX2D120A9602A 24 1 2 2 15 16 23 1 4 23 Prefix May Be A or T Notes 1 Diameter...

Страница 6: ...1234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234...

Страница 7: ...for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals Deicing salts or chemicals Carbon Tetrachloride Halogen type re...

Страница 8: ...turn air grille Although these furnaces are designed with large blowers operating at moderate speeds any blower moving a high volume of air will produce audible noise which could be objectionable when...

Страница 9: ...of the furnace is accessible it is recommended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths should be placed over t...

Страница 10: ...inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the furnace cabinet side See Figures 13 14 16 NOTE Remove the bottom front c...

Страница 11: ...side of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 14 15 17...

Страница 12: ...e cut to fit the unit depending on the location of the return air filter A score line and the words CUT HERE are located on the end of the filter If your application requires cutting the filter do so...

Страница 13: ...m 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condi...

Страница 14: ...the building NOTE It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV This will enable the pipes to be removed later without cutting Be sure to p...

Страница 15: ...assifications covered in ASTM D1784 Deflection Temps Under Load 264 PSI Allowable temperatures based on classifications covered in ASTM D3965 Deflection Temps Under Load 264 PSI NOTE Follow venting in...

Страница 16: ...ote 6 below for exception The inlet pipe can be of a larger diameter but never smaller than the vent pipe 3 MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED THE LENGTH SHOWN IS NOT A COMBINED TOTAL IT IS THE...

Страница 17: ...MUM j ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE NOTE VENT AND INLET MUST BE SUPPORTED AT A MAXIMUM OF 3 INTERVALS BAYAIR30AVENTA TEE BAYVENT200B k 40 UPFLOW OR DOWNFLOW MODELS SEE VENTING TA...

Страница 18: ...osen to meet the requirements of Figure 39 for either direct or nondirect vent applications PITCH Venting through the wall must maintain 1 4 per foot pitched upward to insure that condensate drains ba...

Страница 19: ...RT FIELD SUPPLIED VENT BAYAIR30AVENTA VERTICAL v b n GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3 7 8 DIA HOLE FOR SUPPORT FLANGE 12 x 12 PANEL OR 12 DIA MIN VENTING THROUGH CEILING CEILING SUPPORT...

Страница 20: ...ed for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings IMPORTANT The single wall flue pipe joi...

Страница 21: ...ight 15 feet 4 5 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm J Clearance to nonmechanical air supply inlet to building or the combustion air inlet to...

Страница 22: ...o permanently closed window D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 61 cm from the center line of the terminal E Clearance to unvent...

Страница 23: ...th the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 2 APPROVED CARBON MONOXIDE DETECTORS Each...

Страница 24: ...all excess tubing to avoid kinks Downflow furnace The furnace is shipped with the left side drainage setup To change the right side drain remove the drain lines from the trap rotate the trap 180 so it...

Страница 25: ...causing slippery conditions that could lead to personal injury Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants NOTE Use 1 2 or larger PVC or...

Страница 26: ...JUMPER W1 TO W2 2ND STAGE WILL FIRE 10 MINUTES AFTER 1ST SEE NOTE 8 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SEE NOTE 5 FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 1 ST...

Страница 27: ...STAGE COOLING USING A 2 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From Dwg B342019 Rev 0 SEE NOTE 8 FIELD ADDED JUMPER NOTE 9...

Страница 28: ...SEE NOTE 4 ISOLATION RELAY SEE NOTE 4 JUMPER W1 TO W2 ON BOTH UNITS 2ND STAGE WILL FIRE 10 MINUTES AFTER 1ST B C B C B C From Dwg 21B341336 Rev 2 TWIN TWIN TWINNING CONNECTION DIAGRAM FOR TWINNING UX...

Страница 29: ...ould result in carbon monoxide poisoning or death ELECTRICAL CONNECTIONS Make wiring connections to the unit as indicated on enclosed wiring diagram As with all gas appliances using electrical power t...

Страница 30: ...FROM EITHER SIDE Typical UPFLOW Furnace in horizontal configuration shown AUTOMATIC GAS VALVE WITH MANUAL SHUT OFF Q UPFLOW MAY BE LEFT OR RIGHT HAND GAS PIPING AUTOMATIC GAS VALVE WITH MANUAL SHUT OF...

Страница 31: ...ressure to the gas valve for natural gas is 13 8 W C Minimum pressure is 5 0 W C Maximum pressure to the gas valve for propane is 13 8 W C Minimum pressure is 11 0 W C All gas fittings must be checked...

Страница 32: ...regulator cover screw securely 6 Adjust 2nd stage gas heat by removing the high HI adjustment regulator cover screw a To increase outlet pressure turn the regulator adjust screw clockwise b To decrea...

Страница 33: ...t be changed LP installations will require an orifice change IMPORTANT Reinstall the propane orifices to the same depth as the orifices supplied with the equipment Installation of this furnace at alti...

Страница 34: ...nt freeze up of all water pipes and water receptacles Whenever your house is to be vacant arrange to have someone inspect your house for proper temperature This is very important during freezing weath...

Страница 35: ...ified on the furnace rating name plate If the airflow needs to be increased or decreased see the wiring diagram for information on changing the speed of the blower motor WARNING Disconnect power to th...

Страница 36: ...flame control module will then recycle the ignition sequence then if ignition is not achieved it will shut off the gas valve and lock out the system 3 POWER FAILURE If there is a power failure during...

Страница 37: ...VERY On power up last 4 faults if any will be flashed on the red LED The newest fault detected will flash first and the oldest last There will be a 2 second delay between fault code flashes Solid red...

Страница 38: ...improvement it reserves the right to change design and specifications without notice Trane 6200TroupHighway Tyler TX75707 Formoreinformationcontact yourlocaldealer distributor Literature Order Number...

Отзывы: