20
18-CD29D1-11
Installer’s Guide
HORIZONTAL VENTING
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200B
may be used instead of the horizontal and vertical termi-
nation options shown in the following figures.
For Canadian applications, venting systems must meet
ULC-S636 requirements..
▲
CAUTION
!
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces,
etc., the pipe must be insulated with 1/2 inch (22.7 mm)
thick Armaflex-type insulation or equal. If the space is
heated sufficiently to prevent freezing, then the insula-
tion would not be required. If domestic water pipes are
not protected from freezing then it is assumed the space
meets the condition of a heated space.
6” Min.
24” Max.
12” Min.
15” Max
.
9” Minimum
minimum from end
of exhaust pipe to
end of inlet pipe
6” Min.
24” Max.
12” Min.
15” Max
.
9” Minimum
minimum from end
of exhaust pipe to
end of inlet pipe
6” Min.
24” Max
.
12” Min.
15” Max
.
9” Minimum
minimum from end
of exhaust pipe to
end of inlet pipe
6” Min.
24” Max.
6” Min.
24” Max.
ELBOW AND TEE MUST
BE AS CLOSE TOGETHER
AS POSSIBLE
j
DO NOT Install return air through the side of furnace cabi-
net on horizontal applications.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as
shipped) or as nondirect vent. Installation must con-
form to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation lev-
el.
VENT
COMBUSTION
AIR
VENT
VENT
PLATE
VENT
CAP
12" MINIMUM
TO OVERHANG
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE WHICHEVER IS GREATER
SCREWS
(4 req.)
ANCHORS
(4 req.)
7.2"
3.2"
BAYVENT200B
k
For Canadian applications, horizontal vent termination kits must meet ULC-
S636.
▲
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Do not replace any of the factory supplied venting
components with field fabricated parts. Failure to fol-
low this safety warning exactly could result in dam-
aged vents, damaged components, carbon monoxide
poisoning, or death.
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS WHEN
BOTH TERMINATIONS ARE LOCATED IN THE SAME PRESSURE ZONE