When replacing the bulb and bulb clip, reinstall the bulb in 

the proper orientations.  See Figure 12. 

9. For models with a TXV, wrap the TXV with insulation after 
the bulb clip has been installed.

L.  LEAK CHECK

1. Using a manifold gauge, connect an external supply of dry 
nitrogen to the gauge port on the liquid line.  
2. Pressurize the connecting lines and indoor coil to 150  PSIG 
maximum.
3. Leak check brazed line connections using soap bubbles.  
Repair leaks (if any) after relieving pressure.
4. Evacuate and charge the system per the instructions pack-
aged with the outdoor unit.

M.  CONDENSATE DRAIN PIPING

Condensate drain connections are located in the drain pan 
at the bottom of the coil/enclosure assembly.  The female 
threaded fitting protrudes outside of the enclosure for external 
connection.  A field fabricated trap is not required for proper 
drainage due to the positive pressure of the furnace; however, 
it is  recommended to prevent efficiency loss of conditioned air. 
1. The drain hole in the drain pan must be cleared of all 
insulation.
2. Insulate the primary drain line to prevent sweating where 
dew point temperatures may be met.  (Optional depending on 
climate and application needs)  
3. Connect the secondary drain line to a separate drain line 
(no trap is needed in this line).  

Figure 12

Capillary tubes will 

come out the top of 

bulb when positioned 

correctly.

Содержание A4MXA1824AC6HA

Страница 1: ...oil before beginning the installation Figure 1 18 AD37D1 1 EN Cased Aluminum Convertible Coils Models A4MXA1824AC6HA A4MXB1832AC6HA A4MXA3036AC6HA A4MXB3642AC6HA A4MXC3642AC6HA A4MXB4248AC6HA A4MXC4248AC6HA A4MXD4248AC6HA A4MXC4260AC3HA A4MXD4260AC3HA NOTE OPTIONAL DOWNFLOW GASKET INSTALLATION For unusually humid applications that expect prolonged operation above 70 RH it is recommended to use the...

Страница 2: ...GAS FURNACE a Apply gasket material duct seal field supplied to ALL mating surfaces between the furnace and the coil case b Set the coil case on top of the furnace Connect the duct work to the coil case using field supplied screws c Secure the coil case to the furnace and seal for air leaks as required FOR UPFLOW HORIZONTAL LEFT INSTALLATIONS Figure 3 Figure 2 Remove and Discard Replace UPFLOW FUR...

Страница 3: ...A0 gasket kit to prevent water from form ing on the bottom of the drain pan and dripping into the supply ductwork a Lay the coil on its back side b Locate the 4 wide gasket material found in BAYGSKT001A0 c Attach the 4 gasket material to three sides of the bottom of the drain pan as shown Make sure to start by matching up the edge of the gasket material to the inner edge of the drain pan by the co...

Страница 4: ...ay be laid on either side for horizontal application The condensing downflow horizontal right and upflow horizontal left furnaces may only be rotated onto their left side While not required optional removal of some coil components will maximize airflow efficiency a Remove the coil by sliding the coil out of the coil enclosure b Optional but recommended Remove the factory installed two piece baffle...

Страница 5: ...on the coil enclosure two on each side at the bottom Each of the rear brackets will be attached with the wide side of the bracket resting on the top and bottom of the horizontal coil and furnace see Figure 11 Four additional screws will be used to attach each rear bracket f The front bracket is positioned as close to the center as possible with the narrow edge against the coil enclosure and the wi...

Страница 6: ...o be replaced with the included 0 077 orifice COIL MODEL NOMINAL TONS FACTORY INSTALLED ORIFICE SIZE ADDITIONAL INCLUDED ORIFICE SIZES A4MXA1824AC6HA 2 0 057 0 052 A4MXB1832AC6HA 0 052 0 064 A4MXA3036AC6HA 2 5 0 064 0 068 A4MXB3642AC6HA 3 0 068 0 077 A4MXC3642AC6HA 0 077 A4MXB4248AC6HA 3 5 0 077 0 082 A4MXC4248AC6HA 4 0 082 0 077 A4MXD4248AC6HA 0 077 A4MXC4260AC3HA 5 TXV none A4MXD4260AC3HA none T...

Страница 7: ...t coil 1 Remove both rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run the refrigerant tubing into the stub tube sockets of the indoor unit coil UNIT PANELS MUST BE SHIELDED DURING BRAZ ING 4 Flow a small amount of nitrogen through the tubing while braz...

Страница 8: ...he outdoor unit M CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assembly The female threadedfittingprotrudesoutsideoftheenclosureforexternal connection A field fabricated trap is not required for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air ...

Страница 9: ...aller s Guide Outline Drawing for models A4MXA1824AC6HAA A4MXB1832AC6HAA A4MXA3036AC6HAA A4MXB3642AC6HAA A4MXC3642AC6HAA A4MX B4248AC6HAA A4MXC4248AC6HAA A4MXD4248AC6HAA A4MXC4260AC3HAA A4MXD4260AC3HAA From Dwg D346409 RevA ...

Страница 10: ... NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is s...

Страница 11: ...18 AD37D1 1 EN 11 Installer s Guide ...

Страница 12: ...licy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor 06 19 ...

Отзывы: