88-A4HP5001-1B-EN      

Min. 12” to 

Shrubbery

Avoid Install 

Near Bedrooms

Min 5’ Unrestricted

Access Panel

Min 3’ 

Unrestricted 

2.4 Suggested Locations for Best Reliability

Min. 12” to 

Shrubbery

Min. 12” 

to Wall

2.5 Cold Climate Considerations 

Ensure the top discharge area is unrestricted for 
at least five (5) feet above the unit.

Three (3) feet clearance must be provided in 
front of the control box (access panels) and any 
other side requiring service. 

It is not recommended to install in a location 
where noise may distract the building occu-
pants.  Some examples of these types of loca-
tions are sleeping quarters and by windows of 
a living area.  Please discuss location with the 
building owner prior to installation. 

NOTE:

  It is recommended that these precau-

tions be taken for units being installed in areas 
where snow accumulation and prolonged below 
freezing temperatures occur.

• 

Units should be elevated 3-12 inches above 
the pad or roof top, depending on local 
weather. This additional height will allow 
drainage of snow and ice melted during 
defrost cycle prior to its refreezing. Ensure 
that drain holes in unit base pan are not 
 obstructed preventing draining of defrost 
water.

• 

If possible, avoid locations that are likely to 
accumulate snow drifts. If not possible, a 
snow drift barrier should be installed around 
the unit to prevent a build-up of snow on the 
sides of the unit. 

Min. 12”

Snow 

Barrier

3-12” Elevation

Snow Legs

Pad

Avoid locations such as near windows where 
condensation and freezing defrost vapor can 
annoy a customer.

Position the outdoor unit a minimum of 12” from 
any wall or surrounding shrubbery to ensure 
adequate airflow.

Outdoor unit location must be far enough away 
from any structure to prevent excess roof runoff 
water or icicles from falling directly on the unit.
 

Содержание A4HP5018D1000A

Страница 1: ...ng Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all pre cautions in the literature and on t...

Страница 2: ...um with air and always change the driers when opening the system for component replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG0...

Страница 3: ...ction 6 Refrigerant Line Routing 9 Section 7 Refrigerant Line Brazing 10 Section 8 Refrigerant Line Leak Check 12 Section 9 Evacuation 13 Section 10 Service Valves 13 Section 11 Electrical Low Voltage...

Страница 4: ...6 X 29 8 X 29 8 162 A4HP5024D 32 6 X 29 8 X 29 8 162 A4HP5030D 28 6 X 29 8 X 29 8 159 A4HP5036D 36 6 X 34 3 X 34 3 199 A4HP5042D 44 6 X 34 3 X 34 3 227 A4HP5048D 44 6 X 34 3 X 34 3 250 A4HP5060D 44 6...

Страница 5: ...h of refrigerant lines from outdoor to indoor unit should NOT exceed 150 feet including lift 2 The maximum vertical change should not exceed 50 feet 3 Service valve connection diameters are shown in T...

Страница 6: ...n areas where snow accumulation and prolonged below freezing temperatures occur Units should be elevated 3 12 inches above the pad or roof top depending on local weather This additional height will al...

Страница 7: ...Setting the Unit 4 1 Pad Installation When installing the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The pad mu...

Страница 8: ...4 Total Line Length __________ Ft Total Vertical Change lift __________ Ft The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit ten 10 feet...

Страница 9: ...from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolation hangers should also be used w...

Страница 10: ...ire or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant...

Страница 11: ...the service valves Continue the dry nitrogen purge Do not remove the wet rag until all brazing is completed Important Remove the wet rag before stopping the dry nitrogen purge Note Install drier in L...

Страница 12: ...P 2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For L...

Страница 13: ...lete blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COU...

Страница 14: ...lve System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touche...

Страница 15: ...rnace Furnace Outdoor Unit R G B W1 W2 B Y R G B C W1 W2 24 VAC HOT FAN 24 VAC Common COOL HEATING Y Y1 Y Y YLO Thermostat Outdoor Unit R G B W1 W2 B R G B C Y1 W1 W2 24 VAC HOT FAN 24 VAC Common COOL...

Страница 16: ...EN AUX 1 AUX 1 AUX 2 AUX 2 RC RH B C O Y1 Y2 G BK W1 ODT W2 W3 ODT RS1 RS1 R B C O Y1 YIo Y Y2 G BK W1 W2 AUX 1 AUX 2 24VAC HOT COMMON SOV COOLING FAN HEATING ODT RS B Y INDOOR UNIT OUTDOOR UNIT 2 Sta...

Страница 17: ...of operation 2 FRC_DFT Forced Defrost Short TEST_ COMMON to this pin for two 2 seconds to initiate a forced defrost Remove the short after defrost initiates Defrost Control Checkout Normal operation r...

Страница 18: ...High Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may...

Страница 19: ...t s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory i...

Страница 20: ...d lift measurements from Section 5 3 Total Line Length __________ Ft Vertical Change Lift __________ Ft Note Use this method when matched with a TXV or EEV indoor unit Section 14 System Charge Adjustm...

Страница 21: ...RISE Add 2 REFRIGERANT LINE LIFT FT 50 1 40 30 25 Use Design Subcooling 15 1 10 0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TAB...

Страница 22: ...ressure should be ap proximately 327 PSIG This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198...

Страница 23: ...gree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER INDOOR CFM ALLOW PRE...

Страница 24: ...25 27 28 30 31 95 4 6 8 10 13 14 16 18 20 22 23 25 26 28 29 100 6 8 10 12 13 16 18 20 21 23 25 27 29 105 4 6 7 9 11 13 15 18 20 22 24 26 28 110 4 7 9 11 13 16 18 21 23 26 28 115 6 9 12 14 16 19 21 24...

Страница 25: ...____ F Liquid Gage Pressure __________ PSIG Suction Gage Pressure __________ PSIG Calculating Charge Using the Weigh In Method STEP 1 Measure in feet the distance between the outdoor unit and the indo...

Страница 26: ...to direct contact with copper tubing 5 Verify that all electrical connections are tight 6 Observe outdoor fan during on cycle for clearance and smooth operation Section 15 Checkout Procedures and Trou...

Страница 27: ...A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N...

Страница 28: ...r com The AHRI Certified mark indicates company participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org The manufacturer has a policy...

Отзывы: