3

3

Test Mode

Installer’s Guide

Test Mode

Test Mode

Settings

Description

Blower (Non-VS)

Blower On

Energize "G" circuit 

Blower (VS)

50%, 100%

Energize "G" and "BK" circuit 

Cooling

Single Stage, 1st Stage, 2nd Stage Energize selected "Y", "Y1" or "Y2", "O" and "G" circuit (BK also for 

VS indoor unit)

Comp Heating

Single Stage, 1st Stage, 2nd Stage Energize selected "Y", "Y1" or "Y2" and "G" circuit ("BK" also for VS 

indoor unit)

Indoor Heating

Single Stage, 1st Stage, 2nd Stage Energize selected "W", "W1" or "W2" ("G" circuit also for electric heat)

Aux Relay

Relay On

Close normally open dry contacts

Once testing is complete, press the Done button to exit and return to Menu.

Test Mode allows the servicer to test system operation without waiting for the system to stage up/down. Also all 

minimum on and off times are disabled during test mode. Once a specific test has started, the test will last for 30 

minutes unless the servicer ends the test by pressing the Done button. A countdown timer will be displayed during test 

mode indicating how much time is left in the test.  To access Test Mode press the Menu button, then press Next until 

Service is displayed. Now press Select and hold for 5 seconds until “Installer Settings” is displayed. Press Next until 

Test Mode is displayed. Now press Select again to enter Test Mode.

Restore Defaults

Setting

Range

Description

Restore Default

Yes, [No]

Select "Yes" to restore all the 

User

 and 

Installer

 settings to the 

factory defaults. If "Yes" is selected "Restoring" will be displayed. 

"Done" will be displayed once all settings have been restored.

Note: To reset all 

User

Installer

 and 

Z-Wave

 settings, press and hold the "Yes" button for 5 seconds. Release when "Factory Defaults" is 

displayed. "Done" will be displayed once all settings have been restored and the control will automatically return to the home screen..

Restore Defaults

Restore Defaults is used to restore the control to factory default settings. To access “Restore Defaults” press the 

Menu button, then press Next until “Service” is displayed. Now press Select and hold for 5 seconds until “Installer 

Settings” is displayed. Press Next until “Restore Default” is displayed. Now press Select again to enter “Restore 

Default”. The default setting will be shown in brackets. After each selection press Done to save changes.

Содержание 7CONT624AS42DA

Страница 1: ...tions 11 HD12D1 2 Contents User Guide Features 2 Operation 3 User Settings 4 Scheduling 5 Enrolling into Z Wave Network 8 About 9 Clean Screen 9 Installer s Guide Product Specifications 10 Installatio...

Страница 2: ...4 schedules day Built in humidity sensor with RH display Filter maintenance humidifier service reminders Remote temperature sensing option 1 indoor 1 outdoor Auxiliary compressor heat lockouts Dehumid...

Страница 3: ...t by pressing the up or down arrows To change setpoint mode press the MODE button The setpoints will push each other if they are adjusted to within the minimum heat cool separation setting This is nor...

Страница 4: ...s the Done button to exit and return to Menu Press Next to navigate to the next setting Display Setting Range Description Screen Timeout 0 90 Seconds Select how long after the last button press before...

Страница 5: ...preset at the factory with a 7 Day energy savings schedule Each day of the week is pre programmed with the following schedule Time Date Setting Range Description Hour 1 12 am 1 12 pm Select the curren...

Страница 6: ...et point temperature for one or more periods press Done to save edits If Done is not pressed edits will not be saved After Pressing Done Copy Schedule is dis played at the top of the screen Yes and No...

Страница 7: ...on Yes or No buttons until the copy to day is selected Press Done COPY SCHEDULE Continue copying one days schedule at a time to another or Press Done until the Home Screen Appears Press Done SCHEDULE...

Страница 8: ...Press Menu Button on the main Comfort Control screen b Press the Next Button to advance to the About screen and press the Select Button c Press the Next Button to advance through the menu options to N...

Страница 9: ...energized in cooling or heating mode In Type Identifies the type of indoor unit installed Once all selections have been made press the Done button to exit and return to Menu Press Next to navigate to...

Страница 10: ...thermostat in the trash Dispose of properly Contact your local waste management authority for instructions regarding recycling and proper disposal of the old thermostat A listing of heating ventilati...

Страница 11: ...rtighten AUX C J2 AUX NC C R W1 W2 O B G BK J2 J1 RS RS ODT ODT AUX NO Y1 Y2 J1 AUX C J2 AUX NC C R W1 W2 O B G BK J2 J1 RS RS ODT ODT AUX NO Y1 Y2 J1 AUX C J2 AUX NC C R W1 W2 O B G BK J2 J1 RS RS OD...

Страница 12: ...BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 YO VS Air Handler Electric Heat One or Two Stage Cooling Only Note 1 Note 2 Note 2 Note 3 Note 5 Note 4 Installer s Gui...

Страница 13: ...or W3 Non VS Air Handler Electric Heat One Stage Cooling Only Note 1 Note 2 O Non VS Air Handler Electric Heat Heat Cool Diagram 4 2 Step Cooling w GAM5B Model Air Handler G W1 Y R B C Y2 W2 Two Step...

Страница 14: ...C Y B Notes 1 YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly 2 If third party condenstate overflow switched are...

Страница 15: ...2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 Non VS Air Handler Electric Heat Heat Cool Diagram 8 1 Stage Cooling w TEM3 Model Air Handler G W1 R B C W2 One Stage...

Страница 16: ...Remote Tempurature Sensor Connections and Operation Note 1 Note 4 Note 3 Aux relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 Note 2...

Страница 17: ...w Variable Speed Gas Furnace G W1 Y1 R B C Y2 BK W2 One or Two stage Cooling Only Y1 R B Y2 Notes 1 Cut remove the factory installed BK jumper at the indoor unit 2 Y2 R connections at outdoor are only...

Страница 18: ...Cool Diagram 14 1 or 2 Stage Cooling w Variable Speed Oil Furnace G W1 Y1 R B C Y2 BK W2 One or Two Stage Cooling Only Y1 R B Y2 Notes 1 Cut remove the factory installed BK jumper at the indoor unit 2...

Страница 19: ...nsor wires in the same bundle with HVAC wires Keep away from high voltage wiring to avoid interference Remote Tempurature Sensor Connections and Operation Note 1 Note 2 Package Unit G W Y R B C Aux re...

Страница 20: ...r Sensor Remote Sensor O W3 X2 O YO Variable Speed Air Handler Electric Heat One or Two stage Heat Pump Note 2 Note 3 Note 4 Note 1 Variable Speed Air Handler Electric Heat Heat Pump Diagram 2 1 Stage...

Страница 21: ...Thermostat Connection Outdoor Sensor Remote Sensor O W3 X2 O Note 1 Note 2 Non VS Air Handler Electric Heat Heat Pump Diagram 4 2 Step Heat Pump w GAM5B Model Air Handler G W1 YI R B C Y W2 Two step...

Страница 22: ...2 36M Model Air Handler G W1 YI R B C Y One stage Heat Pump Y R B Notes 1 YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work...

Страница 23: ...Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor W3 X2 O Note 1 Non VS Air Handler Electric Heat Heat Pump Diagram 8 1 Stage Heat Pump w TEM3 Model Air Handler G W1 R B C W2 One stag...

Страница 24: ...Connections and Operation Aux relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O W3 X2 O Note 2 Note 3 Note 1 Air Handler Electric Heat...

Страница 25: ...ensor wires in the same bundle with HVAC wires Keep away from high voltage wiring to avoid interference Remote Tempurature Sensor Connections and Operation X2 Note 1 Note 2 Package Unit G W1 Y R B C W...

Страница 26: ...rature Sensor Connections and Operation Aux relay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O O X2 Note 1 Note 2 Note 3 Non VS One or Tw...

Страница 27: ...ay outputs RS C RS R ODT W1 W2 BK ODT NO C Y1 NC Y2 O B G Thermostat Connection Outdoor Sensor Remote Sensor O X2 O T T R1 Oil Burner Primary R1 Note 2 Note 1 Note 3 Note 4 Note 4 Non Variable Speed O...

Страница 28: ...e same bundle with HVAC wires Keep away from high voltage wiring to avoid interference Remote Tempurature Sensor Connections and Operation X2 Note 2 Note 1 Note 3 Package Unit G W1 Y R B C W2 Aux rela...

Страница 29: ...arate cable from the Comfort Control cable IMPORTANT Follow directions below for averaging These instructions replace the averaging information found in the Installer s Guide for the ZZSENSAL0400AA Re...

Страница 30: ...s Setting Range Description Sensor Calibration 7 7 Degrees 0 Calibrate the indoor temperature sensor do not attempt to calibrate the indoor temperature within the 1st hour upon power up Remote Sensor...

Страница 31: ...t stage indoor heat Indoor Heat Delta Stage 2 Off 0 8 Degree Select the delta off for 2nd stage indoor heat Cooling Delta Stage 1 On 5 8 Degree Select the delta on for 1st stage cooling Cooling Delta...

Страница 32: ...sor heating blower on delay Blower On Delay Heating 0 60 Seconds Select the hydronic heating blower on delay Blower Off Delay Heating Disabled 30 Seconds At 35 3 Minutes At 50 1 5 Minutes At 50 30 Sec...

Страница 33: ...st To access Test Mode press the Menu button then press Next until Service is displayed Now press Select and hold for 5 seconds until Installer Settings is displayed Press Next until Test Mode is disp...

Страница 34: ...0 degrees 2 Intended operation if objectionable lower the minimum on time lowest setting available is 3 minutes Cooling will not come on 1 System mode is not set to Cool Auto or setpoint is set too h...

Страница 35: ...ttp www trane com Residential For Owners Warranties or http www americanstandardair com servicesupport pages warranty aspx and click Begin Online Registration If a Purchaser does not register within t...

Страница 36: ...ations 20 Corporate Woods Dr Bridgeton MO 63044 Or visit our website at www trane com or www americanstandardair com Table 1A Warranty Time Periods for Controls Zoning Products Humidifiers Energy Reco...

Страница 37: ...pment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or m...

Отзывы: