Product Specification
Model
4WCZ5024E1000A
4WCZ5036E1000A
4WCZ5048E1000A
4WCZ5060E1000A
RATED Volts/PH/Hz
208–230/1/60
Performance Cooling BTUH
(a)
23800
35200
47500
56500
Indoor Airflow (CFM)
800
1110
1625
1175
Power Input (KW)
1.98
3.03
4.12
5.12
EER2 / SEER2 BTU/Watt-Hr
(b)
11.0/15.0
11.0/14.65
Sound Power Rating [dB(A)]
(c)
66.8
70.0
72
74
PERFORMANCE HEATING
(High Temp.) BTUH (High/Low)
22800/16300
31000/22400
43000/32000
55500/37600
Power Input (KW)
1.89 / 1.40
2.75 / 2.02
3.48 / 2.49
4.62 / 3.26
(Low Temp.) BTUH (High/Low)
13600/7900
19400/11200
32000/17300
37600/19400
Power Input (KW)
1.70 / 1.31
2.64 / 2.09
3.20 / 2.44
4.20 / 3.15
HSPF2 (BTUH/Watt-Hr)
7.25
6.7
6.7
7.45
POWER CONN. — V/Ph/Hz
208–230/1/60
Min. Brch. Cir. Ampacity
(d)
LOCATED ON UNIT NAMEPLATE
Fuse Size — Max. (amps)
LOCATED ON UNIT NAMEPLATE
Fuse Size — Recmd. (amps)
LOCATED ON UNIT NAMEPLATE
COMPRESSOR
2 STAGE SCROLL
VOLTS/PH/HZ
208–230/1/60
R.L. Amps — L.R. Amps
LOCATED ON UNIT NAMEPLATE
OUTDOOR COIL — TYPE
SPINE FIN
Rows/F.P.I
2 / 24
Face Area (sq. ft.)
15.49
15.49
23.57
23.57
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
INDOOR COIL — TYPE
PLATE FIN
Rows/F.P.I
4/15
4/15
4/15
4/15
Face Area (sq. ft.)
3.5
3.5
5.0
5.0
Tube Size (in.)
3/8
Refrigeration Control
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
OUTDOOR FAN — TYPE
PROPELLER
DIA. (IN.)
23.4
23.4
28.2
28.2
DRIVE/NO. SPEEDS
DIRECT / 1
CFM @ 0.0 in. w.g.
(e)
2550
3020
4220
4700
Motor — HP/R.P.M
1/12 /810
1/6 /830
1/6 /830
1/4 /830
Volts/Ph/Hz
208–230/1/60
F.L. Amps/L.R Amps
LOCATED ON UNIT NAMEPLATE
INDOOR FAN — TYPE
CENTRIFUGAL
Dia. x Width (in.)
10x10
10x10
10x10
11x10
Drive/No. Speeds
DIRECT / VARIABLE
CFM @ 0.0 in. w.g.
(f)
SEE FAN PERFORMANCE TABLE
Motor — HP / R.P.M.
1/2 / VARIABLE
3/4 / VARIABLE
1 / VARIABLE
Volts/Ph/Hz
208–230/1/60
F.L. Amps
LOCATED ON UNIT NAMEPLATE
FILTER / FURNISHED
NO
Type Recommended
THROWAWAY
Recmd. Face Area (sq. ft)
(g)
4.0
4.0
5.3
5.3
REFRIGERANT
R-410
Charge (lbs.)
LOCATED ON UNIT NAMEPLATE
Subcooling
8° F
10° F
(a)
Rated in accordance with AHRI Standard 210/240.
(b)
Rated in accordance with D.O.E. test procedure.
(c)
Sound Power values are not adjusted for AHRI 270–95 tonal corrections.
(d)
Calculated in accordance with currently prevailing Nat’l Electrical Code.
(e)
Standard Air — Dry Coil — Outdoor.
(f)
Standard Air — Dry Coil — Indoor
(g)
Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per
manufacturer’s recommendation with a clean resistance of 0.05” W.C.