Table 6. Filter Sizes (field supplied filter rack)

UNIT

NOMINAL

CFM

FILTER

(a)

SIZE

(Sq Ft)

FILTER

RESISTANCE

(“W.C.)

4*CY5024A

800

2.67

0.08

4*CY5030A

1000

3.33

0.08

4*CY5036A

1200

4.00

0.08

4*CY5042A

1400

4.67

0.08

4*CY5048A

1600

5.33

0.08

4*CY5060A

2000

6.67

0.08

(a)

Filters must be installed in the return air system. The above square
footages are based on 300 F.P.M. face velocity. If permanent filters
are used, size per mfg. Recommendation with clear resistance of
0.05”WC.

IIm

mp

po

orrtta

an

ntt:: Air filters and media wheels or plates shall

meet the test requirements in UL 900

E

Elle

eccttrriicca

all W

Wiirriin

ng

g

N

No

otte

e:: This unit is factory wired for 230V. See wiring

diagram for 208V conversion.

E

Elle

eccttrriicca

all C

Co

on

nn

ne

eccttiio

on

nss

Electrical wiring and grounding must be installed in
accordance with local codes or, in the absence of local
codes, with the National Electrical Code ANSI/NFPA 70,
Latest Revision.

E

Elle

eccttrriicca

all P

Po

ow

we

err

It is important that proper electrical power be available
for the unit. Voltage variation should remain within the
limits stamped on the unit nameplate.

D

Diisscco

on

nn

ne

ecctt S

Sw

wiittcch

h

Provide an approved weatherproof disconnect within
close proximity and w

wiitth

hiin

n ssiig

gh

htt o

off tth

he

e u

un

niitt..If

disconnect must be mounted to the cabinet, the
location shown in

Figure 12, p. 16

should be the only

one considered.

O

Ov

ve

err C

Cu

urrrre

en

ntt P

Prro

otte

eccttiio

on

n

The branch circuit feeding the unit must be protected
as shown on the unit's rating plate.

P

Po

ow

we

err W

Wiirriin

ng

g

The power supply lines must be run in weather-tight
conduit to the disconnect and into the side of the unit
control box. Provide strain relief for all conduit with
suitable connectors.

Provide flexible conduit supports whenever vibration
transmission may cause a noise problem within the
building structure.

1. Remove the Control/Heat access panel. Pass the

power wires through the Power Entry hole in the
end of the unit. See

Figure 10, p. 16

.

2. Connect the high voltage wires to the appropriate

contactor terminals. Single phase units use a two
(2) pole contactor and three phase units use three
(3) pole contactor. Connect the ground to the
ground lug on the chassis. See

Figure 11, p. 16

.

Figure 10.

Power Wiring

Run power supply lines through weather-tight

conduit and secure to unit with strain relief.

Figure 11.

Power Connections

Unit Ground 

Lug

Contactor

Figure 12.

Mounted Disconnect Location

S

Stte

ep

p 4

4 —

— U

Un

niitt IIn

nsstta

alllla

attiio

on

n

Содержание 4WCY5024A1000A

Страница 1: ...n unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipm...

Страница 2: ...tr ri ic ca al l c cu ur rr re en nt t a ar re e g gr ro ou un nd de ed d I If f g gr ro ou un nd di in ng g w wi ir re es s s sc cr re ew ws s s st tr ra ap ps s c cl li ip ps s n nu ut ts s o or r w...

Страница 3: ...3 Introduction 4 Step 2 Determine Unit Clearances 5 Step 3 Review Location and Recommendation Information 9 Step 4 Unit Installation 10 Step 5 Unit Startup 19 Sequence of Operation 20 Maintenance 21 T...

Страница 4: ...t 1 Check for damage after the unit is unloaded Report promptly to the carrier any damage found to the unit Do not drop the unit I Im mp po or rt ta an nt t To prevent damage to the sides and top of t...

Страница 5: ...18 BB38D1 1D EN 5 Step 2 Determine Unit Clearances Figure 1 2 0 3 0 Ton Models D673945G01revc...

Страница 6: ...6 18 BB38D1 1D EN Figure 2 2 0 3 0 Ton Models D673645G01revc S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 7: ...18 BB38D1 1D EN 7 Figure 3 3 5 5 0 Ton Models D673946G01revc S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 8: ...8 18 BB38D1 1D EN Figure 4 3 5 5 0 Ton Models D673946G01_revc S St te ep p 2 2 D De et te er rm mi in ne e U Un ni it t C Cl le ea ar ra an nc ce es s...

Страница 9: ...fer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabric...

Страница 10: ...cture 5 Do not expose the unit to direct roof water runoff 6 Seal all holes through exterior walls in accordance with local codes 7 Continue with the following installation sections to complete the in...

Страница 11: ...requires accessory kit BAYLIFT002BA It includes a kit of four 4 lifting lugs 2 Insert the four lifting lugs in the openings provided in the drip lip on each end of the unit A tap or jerk to the lug w...

Страница 12: ...cture must be insulated and weatherproofed in accordance with local codes 11 Access and service clearances for the unit must be given careful consideration when locating the duct entrance openings See...

Страница 13: ...repared by the manufacturer in order to provide detail regarding job layout only This drawing is not intended to be used as a basis to construct build or modify the item depicted in the drawing The ma...

Страница 14: ...port Center Support required on all frame applications Angle Iron Frame Table 5 Typical Rooftop Down Airflow Application with Frame Return Air Roof Flashing Channel Iron Center Support center support...

Страница 15: ...erproofed between the unit and the building When attaching ductwork to a horizontal unit provide a flexible watertight connection to prevent noise transmission from the unit to the ducts The flexible...

Страница 16: ...wi it tc ch h Provide an approved weatherproof disconnect within close proximity and w wi it th hi in n s si ig gh ht t o of f t th he e u un ni it t If disconnect must be mounted to the cabinet the...

Страница 17: ...ry only For further unit connection details refer to the other figures 8 The W1 WH wire is first stage electric heat If the electric heater accessory has two heating stages the W2 WH wire is second st...

Страница 18: ...c heater accessory is not installed omit the electric heater associated power wires and the W and X2 thermostat wires 7 Fig 2 demonstrates connection of the outdoor thermostat accessory only For furth...

Страница 19: ...y Do the condenser fan and indoor blower turn free without rubbing and are they tight on the shafts Has all work been done in accordance with applicable local and national codes Are all covers and acc...

Страница 20: ...O ON N current is supplied to the transformer Starting at the R R terminal on the indoor comfort control current goes through the system switch which is in A AU UT TO O position to the T TS SH H 1 1 c...

Страница 21: ...as the system been checked with a charging chart Has the voltage and running current been checked to determine if it is within limits Has the thermostat been checked for calibration and the air discha...

Страница 22: ...lacement and connection tightness condensate drain for proper sealing and cleaning unit duct connections to see that they are physically sound and sealed to the unit casing unit mounting support for s...

Страница 23: ...18 BB38D1 1D EN 23 N No ot te es s...

Страница 24: ...com The AHRI Certified mark indicates company participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org The manufacturer has a policy o...

Отзывы: