background image

18-BC60D1-6 

 

    23 

STEP 3

 - Check the liquid line temperature and 

liquid gage pressure to obtain a minimum of 10º 
subcooling in heating mode.

Measured Liquid Line Temp = __________  º F

Liquid Gage Pressure = __________ PSIG

STEP 4

 - Add charge if a minimum of 10º sub-

cooling is not obtained with the namplate charge 
plus additional charge previously added.

STEP 5

 - Return to site for adjustment.

Important:

 Return in the spring or summer to 

accurately charge the system in the cooling 
mode with outdoor ambient 

above 55º F

.

  1.  Leak check refrigerant lines.  ........................................  [  ]
  2.  Properly insulate suction lines and fittings. ...................  [  ]
  3.  Properly secure and isolate all refrigerant lines. ...........  [  ]
  4.  Seal passages through masonry.  

If mortar is used, prevent mortar from coming  

into direct contact with copper tubing. ..........................  [  ]

  5.  Verify that all electrical connections are tight. ...............  [  ]
  6.  Observe outdoor fan during on cycle for clearance  

and smooth operation. ..................................................  [  ]

Section 15. Checkout Procedures and Troubleshooting

15.1 Operational And Checkout Procedures

CHECKOUT PROCEDURE

After installation has been completed, it is recommended that the entire system be checked against the following list:

Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units 
must be operated and charge adjustments made.

Important: 

Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if nec-

essary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly 
secured.

  7.  Be sure that indoor coil drain line drains freely. Pour water  

into drain pan. ...............................................................  [  ]

  8.  Be sure that supply registers and return grilles are open 

and unobstructed. .........................................................  [  ]

  9.  Be sure that a return air filter is installed. .....................  [  ]
 10.  Be sure that the correct airflow setting is used.  

(Indoor blower motor) ...................................................  [  ]

 11.  Operate complete system in each mode to  

ensure safe operation. ..................................................  [  ]

20 MIN.

STEP 2 

- Stabilize the system by operating for a 

minimum of 20 minutes.

At startup, or whenever charge is removed or 
added, the system must be operated for a mini-
mum of 20 minutes to stabilize before accurate 
measurements can be made.

Содержание 4TWX5018B

Страница 1: ...roved matched indoor and outdoor systems All of the manufacture s split systems are A H R I rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency optimum performance and the best overall system reliability 4TWX5 Installer s Guide Table of Contents Section 1 Safety 2 Section 2 Unit Location Considerations 3...

Страница 2: ... for component replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches the rolled edge No torque is required Failure to follow this warning will result in abrupt release of system charge and may...

Страница 3: ...from outdoor to indoor unit should NOT exceed sixty 60 feet 2 The maximum vertical change should not exceed sixty 60 feet 3 Service valve connection diameters are shown in Table 5 1 Note For line lengths greater than sixty 60 feet Refer to Refrigerant Piping Application Guide SS APG006 EN or Refrigerant Piping Software Program 32 3312 03 or latest revi sion 061 Heat Pump is restricted to maximum v...

Страница 4: ...bbery to ensure adequate airflow Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit NOTE It is recommended that these precau tions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur Units should be elevated 3 12 inches above the pad or roof...

Страница 5: ...east 1 larger than the unit on all sides The pad must be separate from any structure The pad must be level The pad should be high enough above grade to allow for drainage The pad location must comply with National State and Local codes For other applications refer to Application Guide SSC APG006 EN If installed within one mile of salt water including seacoasts and inland waterways models without f...

Страница 6: ... Line Insulation Important The Vapor Line must always be insulated DO NOT allow the Liquid Line and Vapor Line to come in direct metal to metal contact Vapor Line Liquid Line Insulation Determine required line length and lift You will need this later in STEP 2 of Section 14 Total Line Length __________ Ft Total Vertical Change lift __________ Ft Trane outdoor condensing units are factory charged w...

Страница 7: ... structure due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings Where the refrigerant lines run through a wall or sill they should be insulated and isolated ...

Страница 8: ... or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant Line Brazing 7 1 Braze The Refrigerant Lines STEP 1 Remove caps or plugs Use a debur ing tool to debur the pipe ends Clean both internal and external surfaces of the tubing using an emery cloth ...

Страница 9: ... avoid heat damage and continue the dry nitrogen purge Braze the refrigerant lines to the service valves Continue the dry nitrogen purge Do not re move the wet rag until all brazing is completed Important Remove the wet rag before stopping the dry nitrogen purge NOTE Precautions should be taken to avoid heat damage to basepan during brazing It is recommended to keep the flame directly off of the b...

Страница 10: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Leaks STEP 1 Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen 150 PSIG ...

Страница 11: ...te blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION VALVE STEM GAS LINE CONNECTION UNIT SIDE OF VALVE PRESSURE TAP PORT Important Leak check and evacuation must be completed before opening the service valves NOTE Do n...

Страница 12: ...e System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches the rolled edge No torque is required Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and or property damage WARNING Section 11 Electric...

Страница 13: ...talled jumper Air Handler Hook up Diagram Red Yellow Green White Blue Orange W1 O B X2 G Y1 Yellow Yellow Blue Orange Blue Black X2 Red Red Orange R Comfort Control Comm Variable Speed Furnace or Air Handler Heat Pump Black W1 W2 W3 G Y2 B O BK D Y1 R Neatly bundle all low voltage wires behind the service valve cover as shown Notes 1 See User Interface 24 V Mode setup menu for control mode and coo...

Страница 14: ...dler Heat Pump Neatly bundle all low voltage wires behind the service valve cover as shown Field wiring Yellow Blue Black X2 Red Orange Red Yellow Orange Green White Blue B B Blue W X2 G Y1 Y1 Yellow R O O R B YI W1 YO DH BK G W2 W3 R Red O Orange In Out W1 White Variable Speed Furnace Hook up Diagram AM7 Air Handler Hook up Diagram 1 1 1 2 3 4 5 1 2 3 4 5 HP 2 Compressor 2 Stages AC System OUTDOO...

Страница 15: ...e cut Jumper J2 to achieve 70 F when at or below 30 F ambient See Service Facts shipped in the outdoor unit for more information Pin Identification See Illustration at right 1 TEST_COMMON Shorting any of the other pins to this pin causes the function of the other pin to be executed Leaving this pin open results in the normal mode of operation 2 TST Test Shorting TEST_COMMON to this pin speeds up a...

Страница 16: ...h Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be nec essary to work with live electrical components Failure to follow all electrical safety precau tions when exposed to live electrical compo nents could result in death or serious injury WARNING Insta...

Страница 17: ...s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is used and the Outdoor Ambient is below 70ºF 60 MIN STEP 1 Ensure Sections 7 through 12 have been completed ON DONE CANCEL ...

Страница 18: ...empera ture is above 55º F For best results the indoor temperature should be kept between 70º F to 80º F STEP 1 Use the refrigerant line total length and lift measurements from Section 5 3 Total Line Length __________ Ft Vertical Change Lift __________ Ft Section 14 System Charge Adjustment 14 1 Temperature Measurements 14 2 Subcooling Charging in Cooling Above 55º F Outdoor Temp LIFT Indoor Temp ...

Страница 19: ...GERANT LINE LENGTH FT 5 Ton Heat Pump 60 50 30 ft Maximum Lift 40 30 Add 1º 25 20 15 10 0 10 20 25 30 40 60 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABLE Use Design Subcooling TOTAL REFRIGERANT LINE LENGTH FT 2 1 2 Ton Heat Pump 60 Add 2º 50 Add 1º 40 30 25 20 15 Use Design Subcooling 10 0 10 20 25 30 40 60 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABLE TOTAL...

Страница 20: ... Pressure should be ap proximately 327 PSIG This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 195 198 201 204 208 211 215 211 215 218 222 225 229 232 229 232 236 240 243 247 251 247 251 255 259 263 267 271 267 271 275 279 283 287 291 287 291 296 300 304 309 313 309 313 318 322 327 331 336 33...

Страница 21: ...e F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER INDOOR CFM ALLOW PRESSURES TO STABILIZE MEASURE INDOOR WET BULB TEMPERATURE OUTDOOR TEMPERATURE DISCHARGE AND SUCTION PRESSURES ON THE PLOTS LOCATE OUTDOOR TEMPERATURE 1 LOCATE INDOOR WET BULB 2 FIND INTERSECTION OF OD TEMP...

Страница 22: ...erant shipped in the outdoor unit and is compatible with 15 feet of AHRI rated refrigerant lines and the smallest AHRI rated coil Using Table 14 3 find the charge associated with the additional length of tubing above 15 ft and record it below Namplate charge ____________ Oz Charge adder ______________ Oz from Table 14 2 14 3 Subcooling Charging Below 55º F Outdoor Temp In Heating Only TUBING INFOR...

Страница 23: ...kout Procedures CHECKOUT PROCEDURE After installation has been completed it is recommended that the entire system be checked against the following list Final phases of this installation are the unit Operational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Important Perform a final unit inspection to be sure that factory tubing has not ...

Страница 24: ... E R C H A R G E E X C E S S I V E E V A P L O A D N O N C O N D E N S A B L E S R E S O D A I R F L O W O D A I R R E C I R C U L A T I O N T X V E E V S T U C K O P E N S U P E R H E A T R E S I D A I R F L O W R E F C I R R E S T R I C T I O N S S O V L E A K I N G S O V C O I L D E F E C T I V E C H E C K V A L V E L E A K I N G D E F R O S T R E L A Y D E F D E F R O S T C O N T R O L D E F C...

Отзывы: