18-BC85D1-2

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service informa-
tion pack upon completion of work.

Heat Pumps

These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with 
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the 
purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.

Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split 

systems are AHRI rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and out-

door split systems are maximum efficiency, optimum performance and the best overall system reliability.

4TWB3018–060

Installer’s Guide

Table of Contents

Section 1. Safety ..................................................................................... 2
Section 2. Unit Location Considerations.............................................. 3
Section 3. Unit Preparation .................................................................... 5
Section 4. Setting the Unit ..................................................................... 5
Section 5. Refrigerant Line Considerations ......................................... 6
Section 6. Refrigerant Line Routing ..................................................... 7
Section 7. Refrigerant Line Brazing ...................................................... 8
Section 8. Refrigerant Line Leak Check ............................................. 10
Section 9. Evacuation ........................................................................... 11
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 13
Section 12. Electrical - High Voltage ................................................... 16
Section 13. Start Up .............................................................................. 17
Section 14. System Charge Adjustment ............................................. 18
Section 15. Checkout Procedures and Troubleshooting ................... 23

Содержание 4TWB3018-060

Страница 1: ...ed matched indoor and outdoor systems All of the manufacture s split systems are AHRI rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and out door spl...

Страница 2: ...onent replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN or APPAPG012 EN Extreme caution should be exercised when opening th...

Страница 3: ...indoor unit should NOT exceed sixty 60 feet 2 The maximum vertical change should not exceed sixty 60 feet 3 Service valve connection diameters are shown in Table 5 1 Note For line lengths greater than...

Страница 4: ...f top depending on local weather This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing Ensure that drain holes in unit base pan are not obstruc...

Страница 5: ...g the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The pad must be separate from any structure The pad must be le...

Страница 6: ...tion Important The Vapor Line must always be insulated DO NOT allow the Liquid Line and Vapor Line to come in direct metal to metal contact Vapor Line Liquid Line Insulation Determine required line le...

Страница 7: ...e due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolati...

Страница 8: ...or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant Lin...

Страница 9: ...avoid heat damage and continue the dry nitrogen purge Braze the refrigerant lines to the service valves Continue the dry nitrogen purge Do not re move the wet rag until all brazing is completed Import...

Страница 10: ...Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Leak...

Страница 11: ...e blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUNTE...

Страница 12: ...System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches t...

Страница 13: ...Comfort control must be dual fuel capable or use accessory TAYPLUS103A 2 Ylo and BK may not be present on unit 3 W1 X2 is a field installed jumper Variable Speed Furnace Hook up Diagram Red Yellow Gr...

Страница 14: ...W2 Pink W3 Brown W1 White For multiple stages of electric heat jumper W1 W2 and W3 together if comfort control has only one stage of heat YI andYO connections must be made as shown for proper operatio...

Страница 15: ...multiple stages of electric heat jumper W1 W2 and W3 together if comfort control has only one stage of heat Some models have a terminal strip Refer to air handler Installer s Guide Red Yellow Green W...

Страница 16: ...White YI andYO connections must be made as shown Internally mounted condensate switch is optional and must be ordered separately If a 3rd party condensate overflow switch is installed it should be wir...

Страница 17: ...speeds up all defrost board timings 3 FRC_DFT Forced Defrost Short TEST_COMMON to this pin for two 2 seconds to initiate a forced defrost Remove the short after defrost initiates Defrost Control Chec...

Страница 18: ...Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be ne...

Страница 19: ...to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is u...

Страница 20: ...t tempera ture is above 55 F For best results the indoor temperature should be kept between 70 F to 80 F Section 14 System Charge Adjustment 14 1 Temperature Measurements 14 2 Subcooling Charging in C...

Страница 21: ...NGTH FEET REFRIGERANT LINE LIFT FEET 10 20 25 30 40 60 Add 4 of Subcooling Add 3 of Subcooling Add 2 of Subcooling Add 1 of Subcooling Use Design Subcool Value 60 50 40 30 25 20 15 10 0 SUBCOOL CHARGI...

Страница 22: ...201 204 208 211 215 211 215 218 222 225 229 232 229 232 236 240 243 247 251 247 251 255 259 263 267 271 267 271 275 279 283 287 291 287 291 296 300 304 309 313 309 313 318 322 327 331 336 331 336 341...

Страница 23: ...5 70 415 420 370 385 380 60 375 380 335 345 345 80 430 435 390 395 395 70 390 390 350 360 355 60 350 355 315 325 320 80 415 420 375 380 380 70 370 375 335 345 340 60 335 335 295 305 305 80 390 390 355...

Страница 24: ...value represents the amount of refrigerant shipped in the outdoor unit and is compatible with 15 feet of AHRI rated refrigerant lines and the smallest AHRI rated coil Using Table 14 3 find the charge...

Страница 25: ...ained with the namplate charge plus additional charge previously added STEP 5 Return to site for adjustment Important Return in the spring or summer to accurately charge the system in the cooling mode...

Страница 26: ...inst the following list Final phases of this installation are the unit Operational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Important...

Страница 27: ...C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C...

Страница 28: ...cturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations included in this d...