background image

4

18-GE12D1-8

Installer’s Guide

C. UNIT INSTALLATION

UPFLOW

a.

For maximum efficiency

, the horizontal drip

tray should be removed. See Figures 5, 6  and 7.
Tray removal requires that the coil be removed
by sliding the coil out on the coil channel sup-
ports. There is a coil support tab at the top of the
coil connected to the case must be removed first.
Remove 1 inch insulation strip covering the lip of
the drip tray. The tray is detached by removing
the two screws at the drain pan. Remove the two
screws holding the two brackets at the top of the
coil. Remove drip tray by gently breaking the
seal between the drip tray and drain pan.

b. Remove the factory installed baffle assembly

from the apex of the coil by using a 5/16"
nutdriver to remove the screw. Replace this
baffle with the factory supplied narrow coil baffle
using the screws removed previously. See Figure
8. Reinstall coil assembly.

CAUTION

!

When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.

c. Position unit on Pedestal or other suitable foun-

dation. If Pedestal is not used, a frame strong
enough to support the total weight must be pro-
vided. Provide a minimum height of 14 inches for
proper unrestricted airflow.

d. If a return air duct is connected to the air han-

dler, it must be the same dimensions as shown in
the outline drawing on page 14.

e. Pedestal and unit should be isolated from the

foundation using a suitable isolating material.

f.

Openings where field wiring enters the
cabinet must be completely sealed.

 Location

of power entry is shown on the Outline Drawing.
Use 2.5" clear stickers provided to seal all unused
electrical knockouts. See Figure 13.

g. After ductwork connections are made, seal air-

tight and per Local codes.

DOWNFLOW

a.

For maximum efficiency

, the horizontal drip

tray should be removed. See the Downflow Kit
Installer's Guide 18-GJ23D1-1 for complete in-
structions.

b. If a return duct is connected to the air handler, it

must be the same dimensions as the return
opening shown in the outline drawing on page
15.

Figure 5 Drip Pan Foam Removal

Figure 6 Horitzontal Drip Pan Removal

Figure 7 Drip Pan Bracket Removal

Содержание 4TEE3F39A1000A

Страница 1: ...for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made against the transportation company immediately Check to be sure all major com Co...

Страница 2: ...fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are suitable for installa tion in an attic garage or crawl space with ducted sup ply a...

Страница 3: ...placed on a plenum TAYPLNM100 Connecting return duct directly to the side front or rear of the cabinet is not ap proved 12 Route refrigerant condensate drain lines away from air handler so they do not...

Страница 4: ...es so NOT to puncture the coil tubing c Position unit on Pedestal or other suitable foun dation If Pedestal is not used a frame strong enough to support the total weight must be pro vided Provide a mi...

Страница 5: ...twork connections are made seal air tight and per Local codes DOWNFLOW BAFFLE KIT X X 7 8 GASKET SCREWS TO REMOVE COIL SCREWS TO REMOVE COIL DISCARD DRIP TRAY 1 2 GASKET INSIDE SURFACE OF BAFFLE 7 8 G...

Страница 6: ...PAN TO CLEAR TABS ON COIL CHANNEL SUPPORTS FOR DOWNFLOW OR HORIZONTAL LEFT APPLICATIONS DRAINPAN SHOWN IN PLACE TAB AS MOUNTED ON COIL CHANNEL SUPPORT Figure 10 TO REMOVE BLOWER ASSEMBLY WHEN COIL IN...

Страница 7: ...as well as the middle to prevent sagging The service access must remain unobstructed If the unit is sup ported along the length of the front and back with rails the air handler only needs to be sus p...

Страница 8: ...urn opening shown in the outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers pro...

Страница 9: ...o secondary drain connections are provided for the different orientations See Figure 17 The lower of the two should be connected as a backup to prevent conden sate overflow by a blocked primary drain...

Страница 10: ...the drain line to a closed drain sys tem 9 Use Teflon tape on the air handler drain line con nections Do Not Use pipe joint compound or PVC CPVC cement It is always recommended that an auxiliary drain...

Страница 11: ...Options Switches 7 8 Auxiliary Heat DIP SWITCHES AS SHIPPED COOLING HEATING AIRFLOW FAN OFF DELAY AUXILIARY HEAT SPEEDS Figure 21 K CHECKOUT PROCEDURE 1 Check the Air Handler installation in accordanc...

Страница 12: ...ERS WITH SINGLE STAGE COOLING 2 STAGE HEAT From Dwg No B801074 COMFORT CONTROL VARIABLE SPEED AIR HANDLER HEAT PUMP O D SECTION SINGLE SPEED NOTES 1 LOW VOLTAGE WIRING TO BE NO 18 A W G MINIMUM CONDUC...

Страница 13: ...w during the defrost cycle 5 Connect only if used with applicable indoor thermostat 6 When heaters are used discard power leads with polarized plug PM A and connect 1 PF to mating plug in the heater c...

Страница 14: ...ER CONTROL BOX AS SHOWN 4TEE3F48 AIR HANDLERS WITH 2 STAGE HEAT PUMP COMFORT CONTROL VARIABLE SPEED AIR HANDLER HEAT PUMP O D SECTION 2 STAGE NOTES 1 LOW VOLTAGE WIRING TO BE NO 18 A W G MINIMUM CONDU...

Страница 15: ...18 GE12D1 8 15 Installer s Guide OUTLINE DRAWING FOR 4TEE3F39 48 64 From Dwg D802101 Rev 9...

Страница 16: ...12D1 8 Installer s Guide 4TEE3F39 48 64 AIR HANDLERS DIMENSIONAL DATA Model No H W 4TEE3F39A1000A 57 90 23 50 4TEE3F48A1000A 4TEE3F48B1000A 4TEE3F64A1000A 4TEE3F39A 48A 48B 60A Are two piece cabinets...

Страница 17: ...18 GE12D1 8 17 Installer s Guide...

Страница 18: ...r size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM 1 Make sure power is OFF at...

Отзывы: